Plan Review Details - Permit 11020189
| Plan Review Stops For Permit 11020189 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-03-07 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-03-08 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-03-07 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2011-03-07 10:57:47 | NEED TO ADDRESS THE FIRE COMMENTS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-02-16 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-16 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-16 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2011-02-16 10:41:00 | PENDING FIRE |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-03-08 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-03-04 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-03-04 |
Time |
15:51 |
Sent To |
E |
|
| Notes |
| 2011-03-04 15:56:06 | 250 SOUTH AUSTRALIAN AVENUE SUITE #800 | | | PERMIT #11020189 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | REMOVE ACCESS CONTROLLED EGRESS DEVICE (CARD READER) | | | FROM ONE ELEVATOR LOBBY DOOR THAT ALLOWS OCCUPANTS FREE | | | EGRESS TO A SECOND STAIR EXIT. THIS DOOR MAY BE | | | EQUIPPED WITH 15 SECOND DELAYED EGRESS HARDWARE AND | | | SHALL MEET ALL THE CRITERIA REQUIRED IN SECTION | | | 7.2.1.6.1. | | | | | | WESLEY JOLIN/MIKE CARSILLO | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2011-02-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2011-02-14 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2011-02-14 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2011-02-14 10:07:05 | 250 SOUTH AUSTRALIAN AVENUE, 8TH FLOOR | | | PERMIT NUMBER 11020189 | | | NEW ACCESS CONTROL EQUIPMENT | | | | | | 1. WRONG EDITION OF NFPA 101, THE LIFE SAFETY CODE | | | REFERENCED. SHOULD READ 2006 EDITION NOT THE 2003 | | | EDITION. THE 2006 EDITION OF 7.2.1.6.2 HAS EIGHT (8) | | | INFORMATION SECTIONS NOT SEVEN (7) AS ILLUSTRATED ON | | | SHEET A-1.0. PLEASE REVISE PLANS. | | | | | | 2. THE EXISTING CARD READERS DISPLAYED ON SHEET A-1.0 | | | IN THE EXISTING EXIT STAIR AND EXISTING EXIT STAIR | | | VESTIBULE CANNOT BE ONE OF THE ASSIGNED RE-ENTRY POINTS | | | FOR THE BUILDING. PLEASE SEE NFPA 101, SECTION | | | 7.2.1.5.7 AND 7.2.1.5.7.1. | | | | | | 3. THE INSTALLATION OF SECURITY DEVICES CANNOT | | | INTERFERE WITH ANY EXITING. | | | | | | 4. A STICKER ON THE PLAN INDICATES THE INSTALLATION OF | | | ONE CARD READER HOWEVER THE PLANS INDICATES THE | | | INSTALLATION OF AT LEAST TWO NEW CARD READERS. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-02-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2011-02-22 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-02-22 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2011-02-22 14:46:15 | IN FIRE BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-02-16 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-16 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-16 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2011-02-09 09:10:36 | TO FIRE BOX |
|
|
|