Plan Review Details - Permit 11020189
Plan Review Stops For Permit 11020189
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-07 Cont ID  
Sent By wjolin Date 2011-03-08 Time 18:28 Rev Time 0.00
Received By rlecky Date 2011-03-07 Time 10:56 Sent To  
Notes
2011-03-07 10:57:47NEED TO ADDRESS THE FIRE COMMENTS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-16 Cont ID  
Sent By rlecky Date 2011-02-16 Time 10:40 Rev Time 0.00
Received By rlecky Date 2011-02-16 Time 10:40 Sent To  
Notes
2011-02-16 10:41:00PENDING FIRE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-03-08 Cont ID  
Sent By wjolin Date 2011-03-04 Time 15:56 Rev Time 0.00
Received By wjolin Date 2011-03-04 Time 15:51 Sent To E
Notes
2011-03-04 15:56:06250 SOUTH AUSTRALIAN AVENUE SUITE #800
 PERMIT #11020189
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 REMOVE ACCESS CONTROLLED EGRESS DEVICE (CARD READER)
 FROM ONE ELEVATOR LOBBY DOOR THAT ALLOWS OCCUPANTS FREE
 EGRESS TO A SECOND STAIR EXIT. THIS DOOR MAY BE
 EQUIPPED WITH 15 SECOND DELAYED EGRESS HARDWARE AND
 SHALL MEET ALL THE CRITERIA REQUIRED IN SECTION
 7.2.1.6.1.
  
 WESLEY JOLIN/MIKE CARSILLO
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-02-14 Cont ID  
Sent By mcarsill Date 2011-02-14 Time 10:07 Rev Time 0.00
Received By mcarsill Date 2011-02-14 Time 09:46 Sent To  
Notes
2011-02-14 10:07:05250 SOUTH AUSTRALIAN AVENUE, 8TH FLOOR
 PERMIT NUMBER 11020189
 NEW ACCESS CONTROL EQUIPMENT
  
 1. WRONG EDITION OF NFPA 101, THE LIFE SAFETY CODE
 REFERENCED. SHOULD READ 2006 EDITION NOT THE 2003
 EDITION. THE 2006 EDITION OF 7.2.1.6.2 HAS EIGHT (8)
 INFORMATION SECTIONS NOT SEVEN (7) AS ILLUSTRATED ON
 SHEET A-1.0. PLEASE REVISE PLANS.
  
 2. THE EXISTING CARD READERS DISPLAYED ON SHEET A-1.0
 IN THE EXISTING EXIT STAIR AND EXISTING EXIT STAIR
 VESTIBULE CANNOT BE ONE OF THE ASSIGNED RE-ENTRY POINTS
 FOR THE BUILDING. PLEASE SEE NFPA 101, SECTION
 7.2.1.5.7 AND 7.2.1.5.7.1.
  
 3. THE INSTALLATION OF SECURITY DEVICES CANNOT
 INTERFERE WITH ANY EXITING.
  
 4. A STICKER ON THE PLAN INDICATES THE INSTALLATION OF
 ONE CARD READER HOWEVER THE PLANS INDICATES THE
 INSTALLATION OF AT LEAST TWO NEW CARD READERS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-22 Cont ID  
Sent By lmartine Date 2011-02-22 Time 14:46 Rev Time 0.00
Received By lmartine Date 2011-02-22 Time 14:46 Sent To  
Notes
2011-02-22 14:46:15IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-16 Cont ID  
Sent By rlecky Date 2011-02-16 Time 10:41 Rev Time 0.00
Received By rlecky Date 2011-02-16 Time 10:41 Sent To  
Notes
2011-02-09 09:10:36TO FIRE BOX