Plan Review Details - Permit 11020187
| Plan Review Stops For Permit 11020187 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-03-07 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-03-08 |
Time |
18:26 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-03-07 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2011-03-07 11:40:18 | STILL NEED TO ADDRESS FIRE COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-02-16 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-16 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-16 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2011-02-16 10:27:09 | PENDING FIRE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-03-08 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-03-04 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-03-04 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2011-03-04 15:51:04 | 250 SOUTH AUSTRALIAN AVENUE SUITE #1700 | | | PERMIT #11020187 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | REMOVE ACCESS CONTROLLED EGRESS DEVICE (CARD READER) | | | FROM BOTH STAIR EXITS BECAUSE THE 17TH FLOOR IS A | | | DESIGNATED RE-ENTRY FLOOR THAT MUST ALLOW OCCUPANTS | | | RE-ENTRY AT ALL TIMES. | | | | | | WESLEY JOLIN/MIKE CARSILLO | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2011-02-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2011-02-14 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2011-02-14 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2011-02-14 11:23:57 | 250 AUSTRALIAN AVENUE, 17TH FLOOR | | | PERMIT NUMBER 11020187 | | | ACCESS CONTROL EQUIPMENT | | | | | | | | | 1. WRONG NFPA 101, LIFE SAFETY CODE REFERENCED. SHOULD | | | READ 2006 EDITION INSTEAD OF 2003 EDITION. THE 2006 | | | EDITION SECTION 7.2.1.6.2 HAS EIGHT (8) SECTIONS NOT | | | (7) SECTIONS. | | | | | | 2. A STICKER ON THE PLANS INDICATES THE INSTALLATION OF | | | THREE CARD READERS BUT THE PLANS INDICATES FIVE CARD | | | READERS. | | | | | | 3. THE EXISTING CARD READERS IN THE STAIRWELL AND THE | | | EXISTING STAIR VESTIBULE MAY IMPACT THE RE-ENTRY POINT | | | FROM THE STAIR. PLEASE SEE NFPA 101, THE LIFE SAFETY | | | CODE SECTIONS 7.2.1.5.7 AND 7.2.1.5.7. | | | | | | 4. SECURITY DEVICES INSTALLED CANNOT INTERFERE WITH | | | EXITING. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-02-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2011-02-22 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-02-22 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2011-02-22 14:50:58 | IN FIRE BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-02-16 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-16 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-09 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2011-02-09 09:00:23 | TO FIRE BOX |
|
|
|