Plan Review Details - Permit 11020183
Plan Review Stops For Permit 11020183
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-02-16 Cont ID  
Sent By wjolin Date 2011-03-08 Time 18:18 Rev Time 0.00
Received By rlecky Date 2011-02-16 Time 10:35 Sent To  
Notes
2011-02-16 10:36:04PENDING FIRE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-03-08 Cont ID  
Sent By wjolin Date 2011-03-04 Time 15:39 Rev Time 0.00
Received By wjolin Date 2011-03-04 Time 14:56 Sent To  
Notes
2011-03-04 15:35:52250 SOUTH AUSTRALIAN AVENUE SUITE #1800
 PERMIT #11020183
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 REMOVE ACCESS CONTROLLED EGRESS DEVICE (CARD READER)
 FROM ONE ELEVATOR LOBBY DOOR THAT ALLOWS OCCUPANTS FREE
 EGRESS TO A SECOND STAIR EXIT. THIS DOOR MAY BE
 EQUIPPED WITH 15 SECOND DELAYED EGRESS HARDWARE AND
 SHALL MEET ALL THE CRITERIA REQUIRED IN SECTION
 7.2.1.6.1.
  
 WESLEY JOLIN/MIKE CARSILLO
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-02-14 Cont ID  
Sent By mcarsill Date 2011-02-14 Time 15:49 Rev Time 0.00
Received By mcarsill Date 2011-02-14 Time 15:42 Sent To  
Notes
2011-02-14 15:49:08250 AUSTRALIAN AVENUE, 18TH FLOOR
 PERMIT NUMBER 11020183
 ACCESS CONTROL EQUIPMENT
  
  
 1. WRONG LIFE SAFETY CODE REFERENCED. SHOULD READ NFPA
 101, THE LIFE SAFETY CODE, 2006 EDITION NOT THE 2003
 EDITION. THE 2006 EDITION HAS EIGHT BULLET POINTS FOR
 7.2.1.6.2 NOT THE SEVEN LISTED ON THE PLAN.
  
 2. SECURITY DEVICE INSTALLATION SHALL NOT INTERFERE
 WITH EXITING.
  
 3. THE STICKER ON THE PLANS DO NOT MATCH THE DRAWINGS
 INDICATING HOW MANY CARD READERS ARE PLANNED TO BE
 INSTALLED.
  
 4. THE EXITING CARD READERS IN THE EXIT STAIR AND THE
 EXISTING EXIT STAIR VESTIBULE MAY CREATE PROBLEMS IF
 THIS FLOOR IS BEING USED AS RE-ENTRY. PLEASE SEE NFPA
 101, SECTION 7.2.1.5.6 AND 7.2.1.5.7.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-22 Cont ID  
Sent By lmartine Date 2011-02-22 Time 14:49 Rev Time 0.00
Received By lmartine Date 2011-02-22 Time 14:49 Sent To  
Notes
2011-02-22 14:49:34IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-16 Cont ID  
Sent By rlecky Date 2011-02-16 Time 10:36 Rev Time 0.00
Received By rlecky Date 2011-02-09 Time 09:07 Sent To  
Notes
2011-02-09 09:08:01TO FIRE BOX