| 2011-02-28 09:22:54 | BUILDING PLAN REVIEW |
| | PERMIT: 11020155 |
| | ADD: 111 EXECUTIVE CENTER BUILDING# 4 FLOORS 1-3 |
| | CONT: WALKER CONTRACTING GROUP |
| | TEL: (239)289-4815 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | 2007 EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) THE SUBMITTED PLAN IS A COPY, EITHER A SIGNMED AND |
| | SEALED ORIGINAL PLAN IS REQUIRED OR THE CONTRACTOR WILL |
| | NEED TO SUPPLY A PLAN THAT IS THEIR OWN DESIGN, |
| | CONTRACTOR OD RECORD WILL NEED TO SIGN AND PRINT THE |
| | QUALIFIERS NAME AND LICENSE NUMBER. |
| | |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS OR EXEMPTION |
| | FL ADMIN CODE 61G16.003 ARCHITECTS OR EXEMPTION |
| | |
| | 2) THE DESIGNER OF RECORD WILL NEED TO PICK A |
| | COMPLIANCE METHOD 101.5 2007 FBC-EXISTING BUILDING |
| | CODE, IF THE WORK AREA COMPLIANCE METHOD IS PICKED |
| | (101.5.2) THEN A LEVEL OF ALTERATION WILL ALSO NEED TO |
| | BE INDICATED, 2007 FBC-EXISTING 401.4). |
| | |
| | 3) THE PLANS FAIL TO INDICATE THE HEIGHT OF THE |
| | BUILDING AND IF THE BUILDING IS FIRE SPRINKLERED? IF |
| | THE SPRINKLERS CONFORM WITH 2007 FBC 903.3..1.1 OR |
| | 903.3.1.2? |
| | |
| | 4) THE PLANS DO NOT INDICATE THE OCCUPANCY BUT THE |
| | HEADER STRIP DOES INDICATE A RETIREMENT COMMUNITY, IS |
| | THIS A I-1 OR A R-2 OCCUPANCY? |
| | IN EITHER CASE 2007 FBC-B TABLE 1017.1REQUIRES THE |
| | CORRIDOR WALLS TO BE A 1 HOUR FIRE RATING, PLEASE |
| | PROVIDE A CUT SECTION OF WALL AND EITHER A UL LISTING |
| | OR GYPSUM NUMBER. |
| | |
| | 5) THE PERMIT APPLICATION INDICATES THE RESIDENT ENETRY |
| | DOORS ARE TO BE REPLACED, PLEASE PROVIDE ADDITIONAL |
| | INFORMATION, 2007 FBC-B |
| | TABLE 715.4 OPENING PROTECTIVES, WILL THERE BE GLAZING |
| | WITHIN THE DOOR UNIT, IF SO HOW MANY SQUARE INCHES? |
| | |
| | 6) THE PLANS FAIL TO INDICATE IF THE RATED CEILING OF |
| | THE CORRIDOR IS TO BE REPLACED? PLEASE REVIEW 2007 |
| | FBC-BUILDING 438.3 HORIZONTAL SEPERATION SHALL BE |
| | CONSTRUCTED IN ACCORDANCE WITH 711. |
| | |
| | 7) PLEASE ADD NOTE ON PLANS FOR COMPLIANCE WITH: 2007 |
| | FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| | SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |