Plan Review Details - Permit 11020155
Plan Review Stops For Permit 11020155
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-03-23 Cont ID  
Sent By jwitmer Date 2011-03-23 Time 08:47 Rev Time 0.77
Received By jwitmer Date 2011-03-23 Time 08:46 Sent To  
Notes
2011-03-23 09:07:41BUILDING PLAN REVIEW
 PERMIT: 11020155
 ADD: 111 EXECUTIVE CENTER BUILDING# 4 FLOORS 1-3
 CONT: WALKER CONTRACTING GROUP
 TEL: (239)289-4815
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2007 EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PLEASE COMPLY WITH 712.6 IF WORK IS ABOVE DROPPED
 ACOUSTICAL CEILING: 2007 FBC-B 712.6 FIRE WALLS, FIRE
 BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
 PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 2) PROVIDE 1 HOUR UL LISTING ASSEMBLY OR EQUIVALENT FOR
 1 HOUR RATED CORIDOR BY TIME OF INSPECTION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-02-28 Cont ID  
Sent By jwitmer Date 2011-02-28 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2011-02-28 Time 08:26 Sent To  
Notes
2011-02-28 09:22:54BUILDING PLAN REVIEW
 PERMIT: 11020155
 ADD: 111 EXECUTIVE CENTER BUILDING# 4 FLOORS 1-3
 CONT: WALKER CONTRACTING GROUP
 TEL: (239)289-4815
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2007 EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) THE SUBMITTED PLAN IS A COPY, EITHER A SIGNMED AND
 SEALED ORIGINAL PLAN IS REQUIRED OR THE CONTRACTOR WILL
 NEED TO SUPPLY A PLAN THAT IS THEIR OWN DESIGN,
 CONTRACTOR OD RECORD WILL NEED TO SIGN AND PRINT THE
 QUALIFIERS NAME AND LICENSE NUMBER.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS OR EXEMPTION
 FL ADMIN CODE 61G16.003 ARCHITECTS OR EXEMPTION
  
 2) THE DESIGNER OF RECORD WILL NEED TO PICK A
 COMPLIANCE METHOD 101.5 2007 FBC-EXISTING BUILDING
 CODE, IF THE WORK AREA COMPLIANCE METHOD IS PICKED
 (101.5.2) THEN A LEVEL OF ALTERATION WILL ALSO NEED TO
 BE INDICATED, 2007 FBC-EXISTING 401.4).
  
 3) THE PLANS FAIL TO INDICATE THE HEIGHT OF THE
 BUILDING AND IF THE BUILDING IS FIRE SPRINKLERED? IF
 THE SPRINKLERS CONFORM WITH 2007 FBC 903.3..1.1 OR
 903.3.1.2?
  
 4) THE PLANS DO NOT INDICATE THE OCCUPANCY BUT THE
 HEADER STRIP DOES INDICATE A RETIREMENT COMMUNITY, IS
 THIS A I-1 OR A R-2 OCCUPANCY?
 IN EITHER CASE 2007 FBC-B TABLE 1017.1REQUIRES THE
 CORRIDOR WALLS TO BE A 1 HOUR FIRE RATING, PLEASE
 PROVIDE A CUT SECTION OF WALL AND EITHER A UL LISTING
 OR GYPSUM NUMBER.
  
 5) THE PERMIT APPLICATION INDICATES THE RESIDENT ENETRY
 DOORS ARE TO BE REPLACED, PLEASE PROVIDE ADDITIONAL
 INFORMATION, 2007 FBC-B
 TABLE 715.4 OPENING PROTECTIVES, WILL THERE BE GLAZING
 WITHIN THE DOOR UNIT, IF SO HOW MANY SQUARE INCHES?
  
 6) THE PLANS FAIL TO INDICATE IF THE RATED CEILING OF
 THE CORRIDOR IS TO BE REPLACED? PLEASE REVIEW 2007
 FBC-BUILDING 438.3 HORIZONTAL SEPERATION SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH 711.
  
 7) PLEASE ADD NOTE ON PLANS FOR COMPLIANCE WITH: 2007
 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-04-08 Cont ID  
Sent By wjolin Date 2011-04-08 Time 13:11 Rev Time 0.00
Received By wjolin Date 2011-04-08 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-03-22 Cont ID  
Sent By ddaniels Date 2011-03-22 Time 11:14 Rev Time 0.00
Received By ddaniels Date 2011-03-22 Time 11:14 Sent To B
Notes
2011-03-22 11:16:4203/22/11 PLANS REVIEWED BY FIRE **DENIED**
 CONTRACTOR DID NOT ADDRESS PREVIOUS COMMENTS MADE.
  
 DERRICK DANIELS CAPTAIN
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-02-16 Cont ID  
Sent By wjolin Date 2011-02-16 Time 15:23 Rev Time 0.00
Received By wjolin Date 2011-02-16 Time 14:49 Sent To  
Notes
2011-02-16 15:23:38111 EXECUTIVE CENTER DRIVE, BUILDING 4 (FLOORS 1-3)
 PERMIT #11020155
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 PROVIDE ADDRESS AND CORRECT DATE IN TITLEBLOCK.
  
 DRAWING INDICATES THIS FLOOR PLAN IS TYPICAL FOR FLOORS
 TWO THROUGH SIX; HOWEVER, FIRST FLOOR IS INCLUDED IN
 SCOPE OF WORK DESCRIPTION.
  
 DRAWINGS INDICATE REMOVAL OF WALLS, FLOORING/CEILING
 AND DOORS. INDICATE THE MATERIALS THAT WILL BE
 REPLACING THOSE THAT HAVE BEEN REMOVED. INDICATE THE
 QUANTITY OF DOORS TO BE REPLACED AND THE FIRE RATING OF
 THESE DOORS.
  
 INDICATE HOW ANY PENETRATIONS THROUGH FIRE RATED FLOORS
 OR WALLS WILL BE FIRESTOPPED.
  
 HAVE ANY ELECTRICAL DEVICES (WALL OUTLETS, LIGHTING
 FIXTURES, SMOKE DETECTORS ETC.) BEEN AFFECTED BY THE
 WATER DAMAGE?
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-04-08 Cont ID  
Sent By wjolin Date 2011-04-08 Time 13:11 Rev Time 0.00
Received By wjolin Date 2011-04-05 Time 07:53 Sent To  
Notes
2011-04-06 07:53:52SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2011-04-08 Cont ID  
Sent By wjolin Date 2011-04-08 Time 13:06 Rev Time 0.00
Received By wjolin Date 2011-03-17 Time 09:06 Sent To  
Notes
2011-03-17 09:07:19INCOMING SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-28 Cont ID  
Sent By jwitmer Date 2011-02-28 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2011-02-07 Time 14:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-02-23 Cont ID  
Sent By eschneid Date 2011-02-23 Time 10:37 Rev Time 0.25
Received By eschneid Date 2011-02-23 Time 10:37 Sent To  
Notes
2011-02-23 10:38:01LESS THAN 50% VALUE OF BUILDING - INTERIOR ONLY.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved