Plan Review Details - Permit 11020129
Plan Review Stops For Permit 11020129
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-03-18 Cont ID  
Sent By rmcdouga Date 2011-03-18 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2011-03-18 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-03-11 Cont ID  
Sent By rmcdouga Date 2011-03-11 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2011-03-11 Time 07:53 Sent To  
Notes
2011-03-11 11:38:502007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 EXTERIOR DOOR AND WINDOWS. IF THE WINDOWS ARE MULLED
 TOGETHER, SUBMIT TWO COPIES OF THE PRODUCT APPROVALS
 FOR THE STRUCTURAL MULLIONS. DCA RULE 9B-72
  
 2) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS FBC 106.3.3
  
 3) SUBMIT TWO COPIES OF RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING IN ORDER TO MEET THE HIGHER UPLIFT
 REQUIREMENTS AT THE CORNER AND PERIMETER AREAS OF THE
 ROOF AS REQUIRED BY LIMITATION #7 OF THE PRODUCT
 APPROVAL FOR THE TAMKO MODIFIED BITUMEN ROOF SYSTEM.
  
 4) THE ENERGY CALCULATIONS THAT WERE SUBMITTED CONTAINS
 NUMEROUS ERRORS. THE FLOOR TYPE SHOWN ON THE PLANS IS A
 CRAWL SPACE NOT A SLAB, WHICH REQUIRES INSULATION. THE
 WALL TYPE ON PLANS IS 2 X 6 WOOD FRAME NOT CONCRETE
 BLOCK. THE CEILING TYPE FOR THE ADDITION SHOWN ON THE
 PLANS IS A SINGLE ASSEMBLY 2 X 8 FLAT ROOF NOT UNDER
 ATTIC. PLEASE CORRECT.
  
 5) THE ENERGY FORM IS REQUIRED TO BE SIGNED BY THE
 OWNER/AGENT. PLEASE CORRECT.
  
 6) THE ENERGY FORM INDICATES THAT THE CEILING FAN
 CREDIT IS BEING TAKEN. SUBMIT PLANS SHOWING THE
 LOCATIONS AND SIZES OF THE CEILING FANS AS REQUIRED BY
 SECTION C4.2.1.1 OF THE REVISED 2007 FLORIDA ENERGY
 GLITCH AMENDMENTS.
  
 7) THE PLANS WILL REQUIRE REVIEW FOR IMPACT FEES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-02-17 Cont ID  
Sent By rmcdouga Date 2011-02-17 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2011-02-16 Time 11:35 Sent To  
Notes
2011-02-16 16:29:192007 FBC W/2009 REVISIONS
  
 1) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS, DOOR, IMPACT PROTECTION DEVICES, ROOF
 COVERING MATERIAL AS REQUIRED BY DCA RULE 9B-72. THE
 PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY THE 2007 ENERGY GLITCH
 AMENDMENTS N1100.0.3. THE FORM IS REQUIRED TO BE SIGNED
 BY THE PREPARER AN THE OWNER/AGENT.
  
 3) SPECIFY THE CEILING, WALL AND UNDER-FLOOR INSULATION
 THAT WILL BE INSTALLED. THE TYPICAL EXTERIOR WALL
 SECTION ON A-4 SHOWS A 2 X 4 FRAME WALL WITH R-30
 INSULATION. PLEASE CORRECT.
  
 4) SHOW COMPLIANCE WITH FBC R319.1(5) PROTECTION
 AGAINST DECAY FOR WOOD SHEATHING AND FRAMING WITHIN 6
 INCHES OF THE GROUND.
  
 5) SHOW COMPLIANCE WITH R320.1 FOR TERMITE PROTECTION.
  
 6) SPECIFY THE ROOF OVERHANG AT THE ADDITION. IF IT IS
 LESS THAN 6 INCHES, GUTTERS ARE REQUIRED IN ACCORDANCE
 WITH R320.7.
  
 7) SHOW COMPLIANCE WITH R408.2 FOR UNDER-FLOOR
 VENTILATION.
  
 8) SHOW COMPLIANCE WITH R408.4 FOR UNDER-FLOOR SPACE
 ACCESS.
  
 9) SHOW COMPLIANCE WITH R704.1 FOR THE REQUIRED BOND
 BREAK BETWEEN THE WATER-RESISTANT BARRIER AND THE
 STUCCO ON THE EXTERIOR WALLS.
  
 10) SHOW COMPLIANCE WITH R704.1 FOR THE CLEARANCE
 BETWEEN THE EXTERIOR WALL COVERING AND THE FINAL EARTH
 GRADE OF NOT LESS THAN 6 INCHES FOR INSPECTION FOR
 TERMITE INFESTATION.
  
 11) SHOW COMPLIANCE WITH R806.1 FOR VENTILATION
 REQUIRED FOR ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS.
  
 12) FBC R905.11.1 REQUIRES MODIFIED BITUMEN MEMBRANE
 ROOFS TO HAVE A MINIMUM SLOPE OF 1/4" PER FOOT. THE
 PLANS SPECIFY 1/8" PER FOOT. PLEASE CORRECT.
  
 13) SHOW COMPLIANCE WITH R313.2.1 FOR THE INSTALLATION
 OF SMOKE ALARMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-07 Cont ID  
Sent By rlecky Date 2011-03-07 Time 15:19 Rev Time 0.00
Received By rlecky Date 2011-03-07 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-17 Cont ID  
Sent By rlecky Date 2011-02-17 Time 11:09 Rev Time 0.00
Received By rlecky Date 2011-02-17 Time 10:56 Sent To  
Notes
2011-02-17 11:14:30PROVIDE SMOKE DETECTORS. FBC R313.2
 PROVIDE INTERSYSTEM BONDING STRIP. NEC. 250.94
 ALL NEW RECEPTICALES SHALL BE TAMPER RESISTANT. NEC
 406.11
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2011-02-11 Cont ID  
Sent By jpapa Date 2011-02-11 Time 13:36 Rev Time 0.00
Received By jpapa Date 2011-02-11 Time 13:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-03-18 Cont ID  
Sent By rmcdouga Date 2011-03-18 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2011-03-16 Time 15:01 Sent To  
Notes
2011-03-16 15:01:17TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-11 Cont ID  
Sent By rmcdouga Date 2011-03-11 Time 11:39 Rev Time 0.00
Received By rmcdouga Date 2011-03-03 Time 16:45 Sent To  
Notes
2011-03-03 16:45:47R--4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-17 Cont ID  
Sent By rmcdouga Date 2011-02-17 Time 13:47 Rev Time 0.00
Received By rmcdouga Date 2011-02-04 Time 10:10 Sent To  
Notes
2011-02-14 10:11:13R1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-03-18 Cont ID  
Sent By rmcdouga Date 2011-03-18 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2011-03-18 Time 08:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-02-16 Cont ID  
Sent By rmcdouga Date 2011-02-16 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2011-02-16 Time 10:07 Sent To  
Notes
2011-02-16 10:08:25IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-02-16 Cont ID  
Sent By rmcdouga Date 2011-02-16 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2011-02-16 Time 10:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-03-18 Cont ID  
Sent By rmcdouga Date 2011-03-18 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2011-03-18 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-03-11 Cont ID  
Sent By rmcdouga Date 2011-03-11 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2011-03-11 Time 07:20 Sent To  
Notes
2011-03-11 07:53:082007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PLUMBING RISER DIAGRAM ON SHEET A-3 OF THE
 REVISED PLAN IS ILLEGIBLE. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-02-16 Cont ID  
Sent By rmcdouga Date 2011-02-16 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2011-02-16 Time 07:54 Sent To  
Notes
2011-02-16 09:46:312007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLUMBING RISER DIAGRAM ON SHEET A-3 DOES NOT
 CORRESPOND WITH THE PLANS. THE DIAGRAM DOES NOT SHOW
 THE THIRD FULL BATH AND DOES NOT DIFFERENTIATE BETWEEN
 THE FIRST AND SECOND FLOORS. PLEASE CORRECT.
  
 2) SPECIFY THE DIMENSIONS OF THE NEW SECOND FLOOR
 BATHROOM ON THE PLANS AND SHOW COMPLIANCE WITH FBC
 R307.1 FOR MINIMUM FIXTURE CLEARANCES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2011-02-11 Cont ID  
Sent By jpapa Date 2011-02-11 Time 13:36 Rev Time 0.00
Received By jpapa Date 2011-02-11 Time 13:36 Sent To  
Notes
***NONE***