Plan Review Details - Permit 11020118
Plan Review Stops For Permit 11020118
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-23 Cont ID  
Sent By rlecky Date 2011-02-23 Time 09:55 Rev Time 0.00
Received By rlecky Date 2011-02-23 Time 09:38 Sent To  
Notes
2011-02-11 15:24:30TO ROBERT LECKY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-09 Cont ID  
Sent By rlecky Date 2011-02-09 Time 12:41 Rev Time 0.00
Received By rlecky Date 2011-02-08 Time 09:26 Sent To  
Notes
2011-02-09 12:42:50SHOW RELATIVE LOCATION OF ELECTRICAL PANELS AND
 DISCONNECTS. VERIFY MAIN SERVICE DISCONNECTS ARE
 GROUPED IN ONE LOCATION. INDICATE LOCATION OF NEW
 ELECTRICAL EQUIPMENT ON A FLOOR PLAN. NEC 230.71
 VERIFY THE EXISTING SERVICE AND ELECTRICAL EQUIPMENT
 INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS HAS A
 SUFFICIENT INTERRUPTING RATING. PROVIDE SPECIFICATIONS
 AND FAULT CURRENT INTERRUPTING RATING FOR PANELS AND
 DISCONNECTS. NEC 110.9, 110.10
 PROVIDE SPECIFICATIONS ON THE NEW TRANSFORMER.
 TRANSFORMERS OF MORE THAN 112 ?? KVA REQUIRE A FIRE
 RESISTANT TRANSFORMER ROOM. NEC 450.21
 SECONDARY OVERCURRENT PROTECTION IS REQUIRED AT THE
 TRANSFORMER. NEC 450.3, 240.21 ( C )
 HOW WILL THE TRANSFORMER BE PHYSICALLY PROTECTED? NEC
 450.8
 PROVIDE A LOAD CALCULATION FOR DETERMINING CONDUCTOR
 SIZE AND OVERCURRENT PROTECTION ON THE PRIMARY AND
 SECONDARY SIDE OF THE NEW TRANSFORMER. NEC 450-3(B)
 NOTE: A SEPARATE ELECTRIC PERMIT AND PLAN IS REQUIRED
 FOR ELECTRICAL CONNECTION OF THE NEW EQUIPMENT.
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-09 Cont ID  
Sent By rlecky Date 2011-02-09 Time 12:43 Rev Time 0.00
Received By rlecky Date 2011-02-07 Time 15:32 Sent To  
Notes
2011-02-07 15:33:12INCOMING SENT TO < $5,000 ELEC