Plan Review Details - Permit 11010633
Plan Review Stops For Permit 11010633
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-02-01 Cont ID  
Sent By jwitmer Date 2011-02-01 Time 15:22 Rev Time 0.55
Received By jwitmer Date 2011-02-01 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-31 Cont ID  
Sent By rlecky Date 2011-01-31 Time 15:35 Rev Time 0.00
Received By rlecky Date 2011-01-31 Time 15:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-02-09 Cont ID  
Sent By ddaniels Date 2011-02-09 Time 11:54 Rev Time 0.00
Received By ddaniels Date 2011-02-09 Time 11:21 Sent To  
Notes
2011-02-09 12:00:152/09/11 PLANS REVIEWED BY FIRE ***APPROVED***
  
 1. PROVIDE SEPARATE PLANS FOR FIRE ALARM DETAILS AND
 SPRINKLER SYSTEM
  
 2. PLANS SHOW 2004 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE, THIS OFFICE RECOGNIZE THE 2007 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE
  
 CAPTAIN DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-17 Cont ID  
Sent By hmoser Date 2011-02-17 Time 09:59 Rev Time 0.00
Received By hmoser Date 2011-01-27 Time 13:22 Sent To  
Notes
2011-01-27 13:26:12B--2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-02-17 Cont ID  
Sent By hmoser Date 2011-02-17 Time 09:45 Rev Time 0.00
Received By hmoser Date 2011-02-17 Time 09:45 Sent To  
Notes
2011-02-17 09:58:42PASS PROVISO
 REFER TO SECTION 602.2.1 MATERIALS EXPOSED WITHIN
 PLENUMS.
 MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE
 OR SHALL HAVE A FLAM SPREAD INDEX OF NOT MORE THAN 25
 AND A SMOKE DEVELOPED INDEX NOT MORE THAN 50
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-01-31 Cont ID  
Sent By lwagner Date 2011-01-31 Time 11:24 Rev Time 0.00
Received By lwagner Date 2011-01-31 Time 11:12 Sent To  
Notes
2011-01-31 11:24:51712.2 FULL OPEN VALVE ALSO REQUIRED FOR PUMP

Review Stop Z ZONING
Rev No 1 Status N Date 2011-02-04 Cont ID  
Sent By aaponte Date 2011-02-04 Time 11:34 Rev Time 0.00
Received By aaponte Date 2011-02-04 Time 11:34 Sent To  
Notes
2011-02-04 11:34:30INTERIOR OFFICE RENOVATION


Account Summary | Usage Policy | Privacy Policy