Plan Review Details - Permit 11010629
Plan Review Stops For Permit 11010629
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-03-22 Cont ID  
Sent By shill Date 2011-03-22 Time 08:04 Rev Time 0.00
Received By shill Date 2011-03-21 Time 09:50 Sent To  
Notes
2011-03-21 17:41:08****PROVISOS****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ELEVATION CERTIFICATE REQUIRED BEFORE CONCRETE POUR.
 INCLUDE PROPOSED ELEVATION OF MECHANICAL EQUIPMENT
 (9.5' PER PLAN). THIS INFORMATION IS REQUIRED TO ALSO
 BE ON THE SIGNED AND SEALED ELEVATION CERTIFICATE PER
 FEMA.
  
 2. BOND BREAK REQUIRED FOR STUCCO OVER FRAME WALL FBC R
 703.6.3.
  
 3. PROVIDE A DETAIL FOR STAIR AND GUARDRAIL.
 DETAIL/SHOP DRAWINGS (REVIEWED BY DOR) TO COMPLY WITH
 FBC R311, R312, R301.5.
  
 4. ROOF NOA PROVIDED 07-0710.05 - FOAM ADHESIVE PRODUCT
 APPROVAL REQUIRED FOR ROOF. THIS MAY BE SUBMITTED
 EITHER WITH THE ROOF PERMIT APPLICATION OR WITH A
 REVISION TO THE MASTER PERMIT.
  
 5. THE TWO SETS OF PRODUCT APPROVAL FOR THE GARAGE DOOR
 ARE NOT THE SAME. PLEASE DETERMINE WHICH DOOR WILL BE
 INSTALLED AND SUBMIT PRODUCT APPROVAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-02-03 Cont ID  
Sent By shill Date 2011-02-03 Time 17:27 Rev Time 0.00
Received By shill Date 2011-02-03 Time 17:27 Sent To  
Notes
2011-02-03 17:28:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THIS PARCEL IS LOCATED IN A HIGH HAZARD FLOOD ZONE.
 THE PROPOSED ELEVATION OF 9.15 ON THE SITE PLAN IS
 NOTED. PLEASE INCLUDE ELEVATION OF MECHANICAL EQUIPMENT
 AND GARAGE. PROVIDE AN ELEVATION CERTIFICATE,
 CONSTRUCTION DRAWINGS.
  
 HTTP://WWW.FEMA.GOV/LIBRARY/VIEWRECORD.DO?ID=1383
  
 2. UNITY OF TITLE TO BE RECORDED PRIOR TO PERMIT
 ISSUANCE, FBC302.1.
  
 3. SEE SOILS REPORT. DESIGN SPECIFIC SOILS EXPLORATION
 REQUIRED. FBC R 401.4.
  
 4. THE ARCHITECT???S SEAL IS NOT LEGIBLE, AND
 ARCHITECT???S INFORMATION (LICENSE NUMBER, PRINTED
 NAME) ARE NOT ON THE PLAN. PLEASE ADDRESS.
  
 5. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  
 6. PROVIDE INFORMATION REGARDING THE FIREPLACE. PROVIDE
 A DETAIL AND LISTING INFORMATION IF APPLICABLE, FBC106.
  
 7. FBC R 311.4.1, EXIT DOOR WITH A LEAF OF 36IN
 REQUIRED. SEE ALSO THE FOLLOWING NON BINDING
 INTERPRETATION. PLEASE FEEL FREE TO CONTACT ME TO
 DISCUSS.
  
 HTTP://WWW.FLORIDABUILDING.ORG/UPLOAD/FBC/CODEID_6758_6
 475.PDF
  
 8. INSULATION ON THE FRAME WALL IS SHOWN AS PERMAFOIL
 4.1, PLEASE SEE REQUIREMENTS OF FBC R CHAPTER 11.
  
 9. SPECIFY PLYWOOD FLOOR DIMENSION, FBC R 501.2.
  
 10. PROVIDE INFORMATION REGARDING THE ATTIC STORAGE
 (SPECIFY LOAD REQUIREMENT) FBC R 301.5.
  
 11. NO VAPOR BARRIER, LATH, BOND BREAK, STUCCO
 THICKNESS, SHOWN ON WALL DETAIL FBC R. SEE ITEM 8,
 INCORRECT INSULATION TYPE AND NO PLYWOOD OR FASTENING
 SPECIFIED. PLEASE REVISE.
  
 12. PROVIDE A DETAIL FOR STAIR AND GUARDRAIL.
  
 13. FOUNDATION PLAN DOES NOT PROVIDE ELEVATION CHANGES.
  
 14. SPECIFY ROOF UPLIFT LOADS, FBC R 301.
  
 15. PRIOR TO RESUBMITTAL, PLEASE CONFIRM THAT PLANS ARE
 COMPLETE WITH ALL APPLICABLE DETAILS.
 ENOUGH INFORMATION AND DETAIL IS TO BE PROVIDED TO
 DETERMINE CODE COMPLIANCE AND TO PERFORM INSPECTIONS. A
 COMPLETE REVIEW CANNOT BE DONE AT THIS TIME.
  
 16. IMPACT FEES DUE TO PALM BEACH COUNTY, 561-233-5025.
 PLANS ARE TO BE STAMPED AND RECEIPT PROVIDED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-17 Cont ID  
Sent By rlecky Date 2011-03-17 Time 10:20 Rev Time 0.00
Received By rlecky Date 2011-03-17 Time 10:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-02-03 Cont ID  
Sent By rlecky Date 2011-02-03 Time 15:00 Rev Time 0.00
Received By rlecky Date 2011-02-02 Time 13:43 Sent To  
Notes
2011-02-03 15:07:50PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE.
 NEC 250.94
 PROVIDE THE INTERRUPTING (AIC) CURRENT RATING FOR THE
 ELECTRICAL SERVICE. NEC 110.9
 NOTE ON THE PLAN THAT THE SMOKE DETECTORS ARE TO BE
 INTERCONNECTED. FBC R313.2
 PROVIDE AN APPLIANCE RECEPTACLE OUTLET AT THE ISLAND
 COUNTERTOP SPACE. NEC 210.50(C)(2).
 PROVIDE A SUPPORTING CALCULATION FOR THE REDUCTION IN
 SIZE OF THE GROUNDED CONDUCTOR (NEUTRAL) NEC 310.15 (A)
 (6), 215.2
 PROVIDE A LIGHTING OUTLET AND A SWITCH FOR THE ATTIC
 STORAGE AREA. NEC 210.70(3)
 NOTE ON THE PLANS THE REQUIRED WORKING CLEARANCES FOR
 THE AC COMPRESSOR DISCONNECTS. NEC 110.26
 NOTE THE SERVICE EQUIPMENT AND WIRE WAY MUST BE LISTED
 FOR OUTDOOR USE. NEC 110.11
 LOCATE THE ELECTRIC SERVICE EQUIPMENT AND ELECTRIC
 PANELS ON THE PLAN. COORDINATE THE LOCATION OF THE AC
 UNITS, SEE SHEET E-1 AND M- 1.
 ATTIC
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-03-25 Cont ID  
Sent By mgonzale Date 2011-03-25 Time   Rev Time 0.50
Received By mgonzale Date 2011-03-25 Time   Sent To  
Notes
2011-03-25 08:58:20PASSED WITH PROVISO
  
 IF USING PAVERS, DRIVEWAY AGREEMENT MUST BE SUPPLIED
 BEFORE C.O.
 I HAVE ATTACHED ONE TO THE PLANS FOR YOUR INFORMATION.
 ANY QUESTIONS CONTACT ME AT YOUR CONVENIENCE.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-02-14 Cont ID  
Sent By mgonzale Date 2011-02-14 Time 07:40 Rev Time 1.00
Received By mgonzale Date 2011-02-14 Time 07:40 Sent To  
Notes
2011-02-14 07:58:06RESPOND TO ALL COMMENTS IN WRITING:
  
 #1 PROVIDE PLAN SHOWING STREET R.O.W. AND REMOVAL OF
 EXSITING CONCRETE APRONS.
 YOU ARE ONLY ALLOWED (2) TEN FOOT WIDE APRONS.
 SEPARATE DRIVEWAY PERMIT IS REQUIRED. THIS WOULD
 INCLUDE DEMOLITION.
  
 #2 PROVIDE SITE CALCULATION AS FOLLOWS:
 TOTAL PERVIOUS
 TOTAL IMPERVIOUS
 TOTAL SITE
 IN S.F. AND IN AC.
  
 #3 MUNICIPAL CODE 94-482 - REQUIRED PARKING MAY BE
 LOCATED IN A FRONT YARD; HOWEVER, THE LESSER OF 1,000
 SQUARE FEET OR 75 PERCENT OF THE FRONT YARD AREA MUST
 BE LANDSCAPED.
 PROVIDE CALCULATION BASED ON YOUR SETBACK AREA.
  
 #4 FOR NEW APRONS PLEASE USE CITY STANDARD APRONS:
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/PDF/STANDARDS/GC-6
 .PDF
 OR
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/PDF/STANDARDS/GC-7
 .PDF
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_STANDARDS.HTM
  
 THANK YOU FOR YOUR ATTENTION. FEEL FREE TO CALL IF ANY
 QUESTIONS.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-30 Cont ID  
Sent By lmartine Date 2011-03-24 Time 12:07 Rev Time 0.00
Received By lmartine Date 2011-03-11 Time 16:44 Sent To  
Notes
2011-03-11 16:44:47SENT TO R19.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-14 Cont ID  
Sent By lmartine Date 2011-02-14 Time 17:12 Rev Time 0.00
Received By lmartine Date 2011-01-27 Time 12:23 Sent To  
Notes
2011-01-27 12:27:15****************EXPEDITED****************
 R--11
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-03-21 Cont ID  
Sent By shill Date 2011-03-21 Time 17:16 Rev Time 0.00
Received By shill Date 2011-03-21 Time 17:16 Sent To  
Notes
2011-03-21 17:16:25MU 2011 4279

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-02-03 Cont ID  
Sent By shill Date 2011-02-03 Time 17:28 Rev Time 0.00
Received By shill Date 2011-02-03 Time 17:28 Sent To  
Notes
2011-02-03 17:29:06233-5025

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-03-17 Cont ID  
Sent By rmcdouga Date 2011-03-17 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2011-03-17 Time 07:52 Sent To  
Notes
2011-03-17 09:30:13MECHANICAL PROVISO
  
 1) THE AIR HANDLERS LOCATED IN THE ATTIC SHALL BE
 LOCATED WITHIN 6 FEET OF AN ACCESS OPENING AND COMPLY
 WITH FBC M1305.1.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-02-04 Cont ID  
Sent By rmcdouga Date 2011-02-04 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2011-02-04 Time 15:59 Sent To  
Notes
2011-02-04 16:16:05DENIED BY MECHANICAL
  
 1) ON SHEET M-1 THE WALL AT LAUNDRY ROOM #1 ON THE
 FIRST FLOOR IS SHOWN IN A DIFFERENT LOCATION THAN ON
 A-1 OF THE ARCHITECTURAL PLAN. IF THE WALL IS LOCATED
 AS SHOWN ON A-1 THE RETURN LOCATED IN THE LAUNDRY ROOM
 WILL VIOLATE CODE SECTION M1602.2(3) OF THE 2007 FBC
 RESIDENTIAL CODE. PLEASE CORRECT.
  
 2) SHOW COMPLIANCE WITH FBCR M1305.1.3 FOR ACCESS TO
 THE AIR HANDLER UNITS LOCATED IN THE ATTIC.
  
 3) ON SHEET M-1 THE TRANSFER DUCT FROM THE GUEST
 BEDROOM IS TOO SMALL. FBCR M1602.4 REQUIRES THE
 TRANSFER DUCT TO BE 1.5 TIMES THE CROSS SECTIONAL AREA
 OF THE SUPPLY DUCTS ENTERING THE SPACE IT'S SERVING.
 PLEASE CORRECT.
  
 4) THE FLOOR PLAN FOR THE MASTER BATH ON SHEET M-2 DOES
 NOT CORRESPOND WITH THE ONE ON A-2. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-03-17 Cont ID  
Sent By rmcdouga Date 2011-03-17 Time 07:42 Rev Time 0.00
Received By rmcdouga Date 2011-03-17 Time 07:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-02-04 Cont ID  
Sent By rmcdouga Date 2011-02-04 Time 09:49 Rev Time 0.00
Received By rmcdouga Date 2011-02-04 Time 09:49 Sent To  
Notes
2011-02-04 11:54:10DENIED BY PLUMBING
  
 1) THE WASHING MACHINE ON THE SECOND FLOOR IS NOT SHOWN
 ON THE PLUMBING ISOMETRIC DRAWING ON SHEET E-3. PLEASE
 SHOW ON DRAWINGS.
  
 2) THE TWO WATER CLOSETS IN HIS AND HER BATH ARE NOT
 VENTED ON THE ISOMETRIC DRAWING. PLEASE CORRECT PER FBC
 R P3101.2.1.
  
 3) THE WET VENT FOR THE FIRST FLOOR GUEST BATHROOM IS
 DOWNSTREAM OF THE TWO FIXTURES IT IS VENTING. PLEASE
 CORRECT PER FBC R P3108.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-03-22 Cont ID  
Sent By eschneid Date 2011-03-22 Time 13:29 Rev Time 1.50
Received By eschneid Date 2011-03-22 Time 13:29 Sent To  
Notes
2011-03-22 12:04:10PASSED
  
 POOL, FENCES AND GATES REQUIRE SEPARATE PERMITS.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-02-07 Cont ID  
Sent By eschneid Date 2011-02-07 Time 10:32 Rev Time 2.00
Received By eschneid Date 2011-02-07 Time 10:32 Sent To  
Notes
2011-02-07 12:10:57FAILED
  
 1) PROVIDE A COPY OF THE RECORDED UNITY OF TITLE.
 PLEASE NOTE THAT THE UNITY OF TITLE SHALL BE SUBMITTED
 TO VINCE NOEL, CITY SURVEYOR, FOR REVIEW AND APPROVAL
 PRIOR TO RECORDATION.
  
 2) SUBMITTAL OF A LANDSCAPE PERMIT AND AN IRRIGATION
 PERMIT ARE REQUIRED PRIOR TO ZONING APPROVAL OF THIS
 PERMIT.
  
 3) THE SURVEY AND THE SITE PLAN SHOW DIFFERENT SITE
 LAYOUTS. IF THE SURVEY IS TO SHOW THE PROPOSED SITE
 LAYOUT, THEN IT SHALL SHOW IT ACCURATELY.
  
 4) TWO COPIES OF A SURVEY SHOWING EXISTING CONDITIONS,
 INCLUDING THE CURRENT DRIVEWAY LOCATIONS, SHALL BE
 PROVIDED.
  
 5) THE A/C UNITS SHALL BE SHOWN ON THE SITE PLAN.
  
 6) PROVIDE THE DIMENSIONS OF THE PROPOSED DRIVEWAY
 CONNECTIONS TO FOREST HILL BLVD. PLEASE NOTE THAT
 NEITHER CONNECTION MAY BE WIDER THAN 10 FEET (PLAN
 SCALES AT 10 FEET) NOR MAY THERE BE MORE THAN 2
 CONNECTIONS.
  
 7) PROVIDE THE MATERIAL OF THE DRIVEWAY.
  
 8) PROVIDE THE FRONT YARD LANDSCAPE CALCULATIONS. THERE
 SHALL BE AT LEAST 1,000 SQUARE FEET TO LANDSCAPE AREA
 IN THE FRONT YARD.
  
 9) PER SECTION 94-611 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE DEFINITION OF DWELLING
 UNIT REQUIRES THAT ALL ROOMS BE ACCESSIBLE FROM THE
 INTERIOR OF THE UNIT. THE MEDIA ROOM, SUMMER KITCHEN
 AND CABANA BATH ARE NOT ACCESSIBLE FROM THE INTERIOR OF
 THE HOUSE, BUT RATHER REQUIRE LEAVING THE HOUSE AND
 CROSSING THE LOGGIA TO ENTER.
  
 10) THE ELEVATIONS ARE MISLABELED AS 1/8" SCALE WHEN
 THEY ARE ACTUALLY 1/4" SCALE. PLEASE REVISE.
  
 11) PLEASE PROVIDE THE BUILDING HEIGHT AS DEFINED BY
 THE CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS - BUILDING, HEIGHT OF, MEANS THE VERTICAL
 DISTANCE FROM THE MEAN GRADE OF A LOT AT THE FRONTAGE
 OF THE BUILDING TO THE HIGHEST POINT OF THE TOP OF THE
 STRUCTURE OF A FLAT ROOF, OR TO THE DECK LINE OF A
 MANSARD ROOF, OR TO THE MID-HEIGHT LEVEL BETWEEN EAVES
 AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS. THE
 BUILDING HEIGHT DIMENSIONS THAT HAVE BEEN PROVIDED ARE
 FROM THE FINISHED 1ST FLOOR NOT THE MEAN GRADE AS
 REQUIRED, NOR DO THEY SHOW THE MID-HEIGHT LEVEL. PLEASE
 NOTE THAT PER SECTION 94-72 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE HEIGHT ALLOWANCE IN THE
 SINGLE FAMILY 7 ZONING DISTRICT IS 30 FEET.
  
 12) THE TALLER CHIMNEYS EXCEED THE ALLOWED HEIGHT
 WITHIN THE SINGLE FAMILY 7 ZONING DISTRICT. THE ALLOWED
 BUILDING HEIGHT OF 30 FEET PLUS THE ADDITIONAL 10%
 HEIGHT EXCEPTION ALLOWED BY SECTION 94-306 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS PERMIT A
 CHIMNEY TO MEASURE 33 FEET TO THE HIGHEST POINT. PLEASE
 NOTE THAT THIS INCLUDES THE CHIMNEY CAP. THE ELEVATION
 DRAWINGS DO NOT MEASURE THE HEIGHT OF THE CHIMNEYS
 CORRECTLY. THE MEAN GRADE (SEE PREVIOUS COMMENT) SHALL
 BE THE STARTING POINT AND THE CHIMNEY CAP SHALL BE THE
 ENDING POINT. THE 35'10" DIMENSION, WHILE NOT MEASURED
 CORRECTLY, EXCEEDS THE DISTRICT HEIGHT ALLOWANCE.
  
 13) PLEASE NOTE THAT THE POOL, SPA, ANY NEW
 FENCES/WALLS, AND GATES WILL REQUIRE SEPARATE PERMITS.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  