Plan Review Details - Permit 11010541
Plan Review Stops For Permit 11010541
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2011-03-07 Cont ID  
Sent By lmartine Date 2011-03-07 Time 10:31 Rev Time 0.00
Received By lmartine Date 2011-03-07 Time 10:31 Sent To  
Notes
2011-03-07 10:32:48BUILDING REVIEW NOT REQUIRED, NO STRUCTUAL WORK ON
 PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-03-07 Cont ID  
Sent By lmartine Date 2011-03-07 Time 10:17 Rev Time 0.00
Received By lmartine Date 2011-03-07 Time 10:30 Sent To  
Notes
2011-03-07 10:25:21SEE SHEET M-1 FOR HAROLD MOSER'S SIGNATURE

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-02-11 Cont ID  
Sent By rlecky Date 2011-02-11 Time 12:37 Rev Time 0.00
Received By rlecky Date 2011-02-11 Time 12:08 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-02-01 Cont ID  
Sent By mgonzale Date 2011-02-01 Time 17:28 Rev Time 1.00
Received By mgonzale Date 2011-02-01 Time 17:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-03-16 Cont ID  
Sent By ddaniels Date 2011-03-16 Time 09:22 Rev Time 0.00
Received By ddaniels Date 2011-03-16 Time 09:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-02-17 Cont ID  
Sent By mcarsill Date 2011-02-17 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2011-02-17 Time 13:16 Sent To  
Notes
2011-02-17 13:35:421009 BANYAN BOULEVARD
 PERMIT NUMBER 11010541
 REPLACEMENT OF EXISTING FLUORIDE SYSTEM WITH A NEW
 FLUORIDE STORAGE AND FEED SYSTEM.
  
  
 1. SITE ADDRESS NOT LISTED ON THE PLANS.
  
 2. ALL STORAGE VESSELS ARE TO BE PROPERLY IDENTIFIED
 WITH PRODUCT NAME AND QUANTITY.
  
 3. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 4. ALL HAZARDOUS MATERIALS ARE TO BE PROPERLY STORED,
 HANDLED, AND TRANSFERRED DURING THE PROPOSED
 RENOVATIONS.
  
 5. ACCORDING TO THE MATERIAL SAFETY DATA SHEETS (MSDS)
 THAT WERE PROVIDED THE HYDROFLUOROSILICIC ACID
 SIGNIFICANT HEALTH HAZARDS EXIST SHOULD EYE, SKIN,
 INHALATION OR INGESTION OCCURS. THIS MATERIAL HAS A
 HEALTH HAZARD OF A 3 ON THE NFPA 704 IDENTIFICATION
 PLACARD. ALSO THE SULFURIC ACID IS ALSO LISTED AS A 3
 ON THE NFPA 704 IDENTIFICATION PLACARD.
  
 6. MORE DETAILS NEEDED FOR CONDUIT PENETRATION AT NEW
 WALL OR SLAB DETAIL SHOWN ON SHEET E-9. THE TYPE OF
 FIRE RATING MATERIAL, THICKNESS OF APPLICATION, AND
 INSTALLATION METHODS SHOULD BE PROVIDED.
  
 7. WRONG CODE INFORMATION PROVIDED ON SHEET E-2. SHOULD
 READ THE 2006 EDITION OF THE LIFE SAFETY CODE, NFPA 101
 NOT THE 2003 EDITION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-03-16 Cont ID  
Sent By ddaniels Date 2011-03-16 Time 09:22 Rev Time 0.00
Received By ddaniels Date 2011-03-14 Time 09:29 Sent To  
Notes
2011-03-14 09:31:33SENT TO FIRE BOX FOR MIKE CARSILLO REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-25 Cont ID  
Sent By jwitmer Date 2011-01-25 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2011-01-25 Time 08:02 Sent To  
Notes
2011-01-25 08:02:38INCOMING SENT TO C-15 JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-03-07 Cont ID  
Sent By hmoser Date 2011-02-11 Time 13:05 Rev Time 0.00
Received By lmartine Date 2011-02-11 Time 13:05 Sent To  
Notes
2011-03-07 10:30:28SEE SHEET M-1 FOR HAROLD MOSER'S SIGNATURE

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-02-22 Cont ID  
Sent By lwagner Date 2011-02-22 Time 10:10 Rev Time 0.00
Received By lwagner Date 2011-02-22 Time 09:55 Sent To  
Notes
2011-02-22 10:10:36PLUMBING PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2011-02-14 Cont ID  
Sent By astelly Date 2011-02-14 Time 11:55 Rev Time 0.00
Received By astelly Date 2011-02-14 Time 11:55 Sent To  
Notes
***NONE***