Plan Review Details - Permit 11010508
| Plan Review Stops For Permit 11010508 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-03-16 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-16 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-10 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-02-10 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2011-02-10 14:15:48 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE STORM PANELS. SPECIFY SPANS, | | | SUBSTRATE, CONNECTION TYPE, ANCHOR TYPE, ANCHOR | | | FASTENER, ETC. | | | | | | 2) SUBMIT TWO COPIES OF THE CURRENT PRODUCT APPROVALS | | | FOR THE AWP SINGLE HUNG WINDOWS. THE NEW NOA IS | | | NO.10-0518.11. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-01-31 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-01-31 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-01-31 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-03-16 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-16 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2011-03-16 09:45:56 | TO R MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-02-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-11 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-01-21 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-03-16 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-03-16 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-10 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-02-10 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2011-02-10 14:25:07 | DENIED BY MECHANICAL | | | | | | 1) THE SCOPE OF WORK STATES SERVICE A/C AND ADD AN A/C | | | DUCT TO ONE OF THE BATHROOMS. THE PLANS INDICATE THAT | | | DUCTWORK IS BEING ADDED TO THE MASTER BEDROOM. PLEASE | | | CLARIFY. | | | | | | 2) IF THE EXISTING AIR HANDLER AND CONDENSING UNIT ARE | | | BEING REPLACED AS AN EXACT CHANGEOUT, FILL OUT THE | | | CONSTRUCTION SERVICES CHANGE OUT FORM. | | | | | | 3) IF A/C IS BEING INSTALLED FOR THE FIRST TIME, SUBMIT | | | EQUIPMENT SIZING CALCULATIONS AND PLANS SHOWING THE | | | LOCATION OF THE AIRHANDLER AND CONDENSING UNIT, THE | | | SIZE OF ALL DUCT WORK AND GRILLS, THE CFMS AT EACH | | | DROP, THE EQUIPMENT SIZES AND MODEL NUMBERS. SHOW | | | COMPLIANCE WITH FBCR M1602.4 FOR BALANCED RETURN AIR. | | | | | | 4) IF YOU ARE ADDING DUCTS TO AN EXISTING SYSTEM, | | | SPECIFY THE DUCT AND GRILL SIZES AND LOCATIONS AND THE | | | CFMS AT THE DROPS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2011-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2011-02-10 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-02-10 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2011-02-04 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2011-02-04 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2011-02-04 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2011-02-04 18:36:28 | PLANNING AND ZONING: *****ZONING REVIEW NOT REQUIRED: | | | INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES | | | NOT EXCEED 50% OF THE IMPROVEMENT VALUE. **** |
|
|
|