Plan Review Details - Permit 11010405
| Plan Review Stops For Permit 11010405 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2011-02-10 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-10 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-09 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2011-02-10 10:31:48 | PLAN RESUBMITALL IS INCOMPLETE AND INADEQUATELY | | | DETAILED. PLEASE ADD ADDITIONAL INFORMATION OR SCHEDULE | | | A MEETING TO DISCUSS. | | | | | | 3/0 WIRE IS REQUIRED TO FEED THE 200 AMP PANEL. | | | WHAT SIZE WIRE IS FEEDING THE 400 AMP PANEL? | | | WHAT SIZE WIRE IS FEEDING THE GUTTER. THE PLANS SHOW | | | TWO DIFFERENT SIZES. | | | SHOW THE GROUNDING WIRE SIZE FOR ALL CONDUITS. | | | WHAT IS THE INSULATION RATING FOR THE WIRE? | | | WHAT TYPE OF CONDUIT IS PROPOSED? | | | WHAT IS THE VOLTAGE OF THE SERVICE? | | | PROVIDE A SERVICE GROUNDING DETAIL. | | | | | | | | | | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-01-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-01-20 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-01-19 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2011-01-20 11:58:17 | PLANS ARE INCOMPLETE AND INADEQUATELY DETAILED. PLEASE | | | REDRAW WITH ADDITIONAL INFORMATION OR SCHEDULE A | | | MEETING TO DISCUSS. | | | | | | 2/0 WIRE IS RATED FOR 175 AMPS. NEC 301.16. | | | THE ???NEW??? PANEL APPEARS TO BE FED FROM A METER? | | | WHICH PANEL BOARDS ARE FOR THE I-HOP? | | | ARE THE MAIN SERVICE DISCONNECTS GROUPED? | | | IS THERE ADEQUATE CLEARANCE FOR THE NEW EQUIPMENT? | | | HOW IS THE NEW SERVICE AND DISCONNECT BEING FED? | | | IS THIS PLAN AN " AS BUILT" OR A NEW INSTALLATION? | | | PROVIDE A LOAD CALCULATION TO SUPPORT THE PROPOSED | | | SERVICE SIZE. | | | WHAT IS THE INSULATION RATING FOR THE WIRE? | | | WHAT TYPE OF CONDUIT IS PROPOSED? | | | WHAT IS THE VOLTAGE? | | | WHAT IS THE FAULT CURRENT RATING REQUIRED FOR THE | | | SERVICE? | | | | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-02-10 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-02-10 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-02-09 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2011-02-09 08:56:49 | TO ELECTRIC |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-01-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-01-20 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-01-18 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2011-01-18 14:42:38 | IN ELECTRIC BOX |
|
|
|