Plan Review Details - Permit 11010403
Plan Review Stops For Permit 11010403
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-01-20 Time   Rev Time 0.00
Received By shill Date 2011-01-18 Time 12:08 Sent To  
Notes
2011-01-18 12:09:05TO MECHANICAL < $5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-31 Cont ID  
Sent By rregueir Date 2011-01-31 Time 16:18 Rev Time 0.00
Received By rregueir Date 2011-01-31 Time 16:18 Sent To  
Notes
2011-01-31 16:19:24MATCHING AIR HANDLER ADDED TO SCOPE OF WORK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-20 Cont ID  
Sent By rregueir Date 2011-01-18 Time 10:55 Rev Time 0.00
Received By rregueir Date 2011-01-18 Time 10:54 Sent To  
Notes
2011-01-20 10:03:09REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. APPLICATION SCOPE OF WORK IS FOR CONDENSING UNIT
 REPLACEMENT. PLEASE SEE FBC 13-101.6, EXCEPTIONS (1):
  
 MATCHED SYSTEMS ARE REQUIRED; THIS MATCH MAY BE
 VERIFIED BY ANY ONE OF THE FOLLOWING MEANS:
  
 1. ARI (AHRI) DATA
 2. ACCREDITED LABORATORY (EXAMPLE ARL LABS)
 3. MANUFACTURER'S LETTER
 4. LETTER FROM REGISTERED P.E. STATE OF FLORIDA
  
 AS DISCUSSED, PLEASE PROVIDE DOCUMENTATION TO SHOW
 COMPLIANCE WITH FBC 13-101.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  