Plan Review Details - Permit 11010337
Plan Review Stops For Permit 11010337
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-03-30 Cont ID  
Sent By jwitmer Date 2011-03-30 Time 07:50 Rev Time 0.77
Received By jwitmer Date 2011-03-29 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-03-15 Cont ID  
Sent By jwitmer Date 2011-03-15 Time 08:33 Rev Time 0.50
Received By jwitmer Date 2011-03-15 Time 07:59 Sent To  
Notes
2011-03-15 07:59:48BUILDING PLAN REVIEW
 PERMIT: 11010337
 ADD: 1001 N DIXIE HWY
 CONT: VINTAGE BUILDING & DESIGN
 TEL: (561)706-3987
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE
 INDICATES TWO SEPERATE PROPERTY CONTROL NUMBERS, ONE
 FOR LOT# 9 THE OTHER FOR LOT# 11. UNDER THE CURRENT
 CONFIGURATION OF LOT # 11 THE NORTH WALL WOULD BE A
 ZERO LOT LINE WALL, NO OPENINGS ALLOWWED, IF THE LOTS
 ARE UNIFIED UNDER A UNITY OF TITLE THIS SITUATION WOULD
 NOT OCCUR ALLOWING THE PROPOSED CHANGES. 2007/ 2009
 FBC-B TABLE 704.8.
  
 BUILDING PLANS ARCHITECTURAL & STRUCTURAL SHEETS OK/
 STAMPED!
  
  
 PROVISO:
 1) THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE
 TO CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR
 TO INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND
 THE ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS
 REQUIRE ADDITIONAL REVIEWS WITH ASSOCIATED FEES. SHEET
 A-4 THE CONCRETE EYEBROW, PLEASE INDICATE THE TYPE OF
 ANCHOR TO BE INSTALLED WITH DEPTH & SPACING.
  
 2) SHEET A-3 FRONT SIDEWALK DROPPED AREA FOR EGRESS
 FROM HANDICAPPED PARKING 11-4.29.5 DETECTABLE WARNING
 AT HAZARDOUS VEHICULAR AREAS.
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-31 Cont ID  
Sent By jwitmer Date 2011-01-31 Time 09:00 Rev Time 1.50
Received By jwitmer Date 2011-01-28 Time 14:28 Sent To  
Notes
2011-01-28 15:42:05BUILDING PLAN REVIEW
 PERMIT: 11010337
 ADD: 1001 N DIXIE HWY
 CONT: VINTAGE BUILDING & DESIGN
 TEL: (561)706-3987
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE
 INDICATES TWO SEPERATE PROPERTY CONTROL NUMBERS, ONE
 FOR LOT# 9 THE OTHER FOR LOT# 11. UNDER THE CURRENT
 CONFIGURATION OF LOT # 11 THE NORTH WALL WOULD BE A
 ZERO LOT LINE WALL, NO OPENINGS ALLOWWED, IF THE LOTS
 ARE UNIFIED UNDER A UNITY OF TITLE THIS SITUATION WOULD
 NOT OCCUR ALLOWING THE PROPOSED CHANGES. 2007/ 2009
 FBC-B TABLE 704.8.
  
 2) THERE WERE TWO SEPERATE MIAMI-DADE NOA'S SUBMITTED
 FOR OUTSWING ALUMINUM FRENCH DOORS W/ SIDE LITES, PGT
 FD-750, NOA 09-1028.10 AND PGT FD-101 OUTSWING ALUMINUM
 FRENCH DOORS W/ SIDE LITES, NOA 07-0629.10. IT APPEARS
 THAT THE NOA 07-0629.10 WILL HAVE PRESSURES TO LOW FOR
 THE "C" EXPOSURE WHEN THE MULTIPLIER 1.29 IS USED IN
 THE EQUATION.
  
 3) SHEET A-4 THE CONCRETE EYEBROW, PLEASE INDICATE THE
 TYPE OF SLEEPERS TO BE INSTALLED ONTO THE CONCRETE
 DECK, SIZE AND SPECIES OF WOOD, AND ANCHOR TO BE
 INSTALLED WITH DEPTH & SPACING. PLEASE ALSO PROVIDE THE
 TYPE OF PLYWOD TO BE INSTALLED TO CREATE THE RADIUS ON
 THE CONCRETE EYEBROW, REMEMBER MINIMUM THICKNESS WHICH
 WILL BE FOUND IN THE ROOFING NOA.
  
 4) BUILDING PROVISO: AT THIS TIME NO ROOFING CONTRACTOR
 IS SIGNED ON, NO ROOFING REPORT WILL BE REQUIRED AT
 THIS TIME BUT THE QUESTION IS WHAT TYPE OF METAL
 ROOFING WITH RAISED SEAM WILL BE INSTALLED ON THE
 RADIUS OF THE CONCRETE EYEBROW? 106.3.3 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-03-15 Cont ID  
Sent By rlecky Date 2011-03-15 Time 15:16 Rev Time 0.00
Received By rlecky Date 2011-03-15 Time 15:16 Sent To  
Notes
2011-03-15 15:26:51PROVISO:
  
 OCCUPANCY SENSORS REQUIRED IN ACCORDANCE WITH FBC
 13-415.ABC.1.2
  
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER. 561-805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-01-19 Cont ID  
Sent By rlecky Date 2011-01-19 Time 15:35 Rev Time 0.00
Received By rlecky Date 2011-01-19 Time 12:54 Sent To  
Notes
2011-01-19 15:37:24PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94
 PROVIDE AUTOMATIC LIGHTING CONTROL AND LIGHTING
 DENSITIES. FBC 13-415 ABC.1.2
 PROVIDE ELECTRIC FAULT CURRENT CALCULATION FOR SERVICE
 EQUIPMENT AND PANELBOARD. NEC 110.9, 110.10
 PROVIDE GFCI PROTECTED RECEPTACLE ON ROOF FOR SERVICING
 THE AIR-CONDITIONING EQUIPMENT. NEC 210.63
 PROVIDE A 1200 VA, 20 AMP, SIGN CIRCUIT. NEC 660.5,
 220.14(F)
 PROVIDE EMERGENCY LIGHTING. FBC 1006
 INCLUDE ALL LOADS AT 100% IN THE SERVICE CALCULATION.
 NEC 220 PART III
 ELECTRIC SERVICE REQUIRES 3/0 CONDUCTORS FOR 200 AMP.
 NEC T. 310.16
 INDICATE THE SIZE OF THE SERVICE FEEDERS AND LOCATION
 OF THE FEEDER. NEC. 310.8
 INDICATE THE MAIN DISCONNECT IS SUITABLE FOR A WET
 LOCATION. NEC 330.6
  
 NOTE:
 A SEPARATE PERMIT WITH A PLAN IS REQUIRED FOR VOICE AND
 DATA.
  
 ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-03-15 Cont ID  
Sent By wjolin Date 2011-03-15 Time 13:00 Rev Time 0.00
Received By wjolin Date 2011-03-15 Time 12:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-27 Cont ID  
Sent By wjolin Date 2011-01-27 Time 11:32 Rev Time 0.00
Received By wjolin Date 2011-01-27 Time 10:22 Sent To  
Notes
2011-01-27 11:30:101001 NORTH DIXIE HIGHWAY
 PERMIT #11010337
 REVIEW COMMENTS - FIRE
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS WITH A MINIMUM
 RATING OF 2A:10BC ALONG THE PATH OF EGRESS.
 EXTINGUISHERS SHALL HAVE A CURRENT SERVICE TAG PROVIDED
 BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 PROVIDE DOOR LOCK AND LATCH RELEASING MECHANISM
 INFORMATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-03-30 Cont ID  
Sent By jwitmer Date 2011-03-30 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2011-03-25 Time 08:37 Sent To  
Notes
2011-03-25 08:39:20******************EXPEDITED*****************
 C--9

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-22 Cont ID  
Sent By lmartine Date 2011-02-22 Time 17:13 Rev Time 0.00
Received By lmartine Date 2011-02-22 Time 17:12 Sent To  
Notes
2011-02-22 17:13:52C--9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-14 Cont ID  
Sent By hmoser Date 2011-02-14 Time 11:41 Rev Time 0.00
Received By hmoser Date 2011-01-18 Time 14:39 Sent To  
Notes
2011-01-18 14:40:03C9
  

Review Stop L LANDSCAPING
Rev No 3 Status N Date 2011-03-28 Cont ID  
Sent By rkussner Date 2011-03-28 Time 10:50 Rev Time 0.00
Received By rkussner Date 2011-03-28 Time 10:50 Sent To  
Notes
2011-03-28 10:51:02PLEASE REFER TO PERMIT #11020505 FOR LANDSCAPE PERMIT.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2011-03-03 Cont ID  
Sent By rkussner Date 2011-03-03 Time 13:15 Rev Time 0.00
Received By rkussner Date 2011-03-03 Time 13:15 Sent To  
Notes
2011-03-03 13:18:45***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1 PURSUANT TO SECTION 94-443 (C) (3) (A) EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN FIVE FEET IS WIDTH AND NOT
 LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL. THE
 LANDSCAPED ISLAND SHALL HAVE A MINIMUM RADIUS OF 2 1/2
 FEET AT ITS END SO AS TO ALLOW CAR MANEUVERING.. A
 LANDSCAPE ISLAND IS REQUIRED ALONG THE NORTH SIDE OF
 THE TWO PARKING STALLS THAT TAKE ACCESS FROM THE ALLEY.
 THE TWO SPACES WILL NEED TO BE SHIFTED TO THE SOUTH IN
 ORDER TO PROVIDE THE REQUIRED ISLAND.
  
 2. FOR ADDITIONAL LANDSCAPE COMMENTS, PLEASE REFER TO
 PERMIT #11020505.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2011-01-25 Cont ID  
Sent By rkussner Date 2011-01-25 Time 11:30 Rev Time 0.00
Received By rkussner Date 2011-01-25 Time 11:30 Sent To  
Notes
2011-01-25 12:21:55***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT
 AN APPLICATION AND TWO SETS OF LANDSCAPE PLANS, SIGNED
 AND SEALED BY A REGISTERED LANDSCAPE ARCHITECT. INCLUDE
 A CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR.
  
 2. PLEASE APPLY FOR A SEPARATE IRRIGATION PLAN. SUBMIT
 AN APPLICATION AND TWO SETS OF THE IRRIGATION PLAN.
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS. ALTHOUGH SOME OF THE
 TABULATION WAS PROVIDED OTHER INFORMATION WAS MISSING
 SUCH AS THE PERIMETER TREE REQUIREMENTS.
  
 4. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL INCLUDE ALL OF THE ELEMENTS ENUMERATED IN
 THIS SECTION. ALL UTILITIES, EASEMENTS, STREET LIGHTS,
 AND ANYTHING ELSE THAT MAY HAVE AN IMPACT UPON THE
 LANDSCAPING SHALL BE SHOWN ON THE PLAN. THERE ARE
 POTENTIAL CONFLICTS OBSERVED DURING A SITE VISIT. LIVE
 OAKS ARE PROPOSED ALONG THE WEST PERIMETER OF THE SITE
 IN THE SAME GENERAL AS OVER HEAD POWER LINES. YOU MUS
 ABIDE BY FPL'S "PLANT THE RIGHT TREE IN THE RIGHT
 PLACE" GUIDELINES WHICH LIMIT WHICH TREE SPECIES CAN BE
 PLANTED NEAR OR ADJACENT TO OVER HEAD POWER LINES.
  
 5. PURSUANT TO SECTION 94-443 (B) (1), FOR ALL
 NONRESIDENTIAL USES, THE LANDSCAPE BUFFER STRIP
 ADJACENT TO A PUBLIC RIGHT-OF-WAY AND OTHER
 NONRESIDENTIAL ZONING DISTRICTS SHALL BE A MINIMUM OF
 FIVE FEET IN WIDTH. THIS HAS NOT BEEN PROVIDED ALONG
 THE NORTH PERIMETER OF THE SITE AND A PORTION F THE
 WEST PERIMETER.
  
 6. PURSUANT TO SECTION 94-443 (B) (4), AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED
 BUFFER STRIP FOR EACH 30 LINEAR FEET OR PORTION
 THEREOF. ADDITIONAL TREES WILL BE REQUIRED ALONG THE
 WEST AND NORTH PERIMETER OF THE SITE.
  
 7. PURSUANT TO SECTION 94-444 (B), OUTDOOR GARBAGE OR
 TRASH RECEPTACLES AND OTHER MECHANICAL EQUIPMENT SHALL
 NOT BE PERMITTED UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE,OTHER DECORATIVE MASONRY, OR
 COMPARABLY DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS. A FOUR-SIDED ENCLOSURE WITH AN OBSCURING
 TATE IS ALSO REQUIRED. THE CONCRETE PAD WAS SHOWN ON
 THE SITE PLAN WITH NO PROPOSED WALLS, GATES OR
 SCREENING. THE PAD, ENCLOSURE AND SCREENING WAS NOT
 SHOWN ON THE LANDSCAPE PLAN.
  
 8. THE APPLICANT SHALL FILL IN THE MISSING PLANT
 MATERIAL IN THE LANDSCAPE NODE, LOCATED IN THE
 RIGHT-OF-WAY AT THE SOUTHEAST CORNER OF THE SITE. THE
 NODE AND THE STREET TREES SHALL BE SHOWN ON THE
 LANDSCAPE AND SITE PLANS.
  
 9. PURSUANT TO SECTION 94-446 (1), PLANTING AREAS ARE
 TO BE TOTALLY EXCAVATED WHENEVER PLANT MATERIALS ARE
 INSTALLED 24 OR LESS INCHES APART. PLANTING AREAS
 CONTAINING EXCESSIVE CALCAREOUS MATERIALS SHALL BE
 EXCAVATED TO A MINIMUM DEPTH OF TWO FEET. A MINIMUM OF
 THREE INCHES OF COMPACTED, ORGANIC MULCH SHALL BE
 PLACED AROUND ALL NEWLY INSTALLED TREES, SHRUBS AND
 GROUND COVER PLANTING AREAS. THE SPECIFICATIONS CALLED
 FOR TWO INCHES OF MULCH.
  
 10. ALL PROHIBITED TREE SPECIES SHALL BE REMOVED,
 INCLUDING THE SCHEFFLERA TREE ALONG THE NORTH SIDE OF
 THE BUILDING.
  
 11. PURSUANT TO SECTION 94-443 (C) (3), OFF-STREET
 PARKING LOTS CONTAINING AT LEAST 12 INTERIOR PARKING
 SPACES SHALL CONTAIN LANDSCAPE AREAS. THE TOTAL SIZE OF
 SUCH LANDSCAPED AREAS SHALL BE EQUAL TO TEN SQUARE FEET
 FOR EACH PARKING SPACE AND SHALL BE PROVIDED WITHIN THE
 INTERIOR OF AN OFF-STREET PARKING AREAS. LANDSCAPED
 AREAS SHALL CONTAIN AT LEAST ONE SHADE OR FLOWERING
 TREE FOR EACH 100 SQUARE FEET OF REQUIRED LANDSCAPED
 AREA.
  
 12. PURSUANT TO SECTION 94-443 (C) (3) (A), LANDSCAPED
 ISLANDS SHALL HAVE A MINIMUM RADIUS OF 2 1/2 FEET AT
 ITS END SO AS TO ALLOW CAR MANEUVERING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (5610 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-03-18 Cont ID  
Sent By hmoser Date 2011-03-18 Time 10:50 Rev Time 0.00
Received By hmoser Date 2011-03-18 Time 10:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-02-14 Cont ID  
Sent By hmoser Date 2011-02-14 Time 11:35 Rev Time 0.00
Received By hmoser Date 2011-02-14 Time 11:17 Sent To  
Notes
2011-02-14 11:40:48PLANS DENIED
 1) EQUIPMENT SCHEDULE SHOWS ONE A/C UNIT PLAN SHOWS
 TWO.
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 3) REFER TO SECTION 606.3.1 SUPPLY AIR AND SECTION
 606.3 INSTALLATION FBC (M) 2007 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-03-16 Cont ID  
Sent By lwagner Date 2011-03-16 Time 09:57 Rev Time 0.00
Received By lwagner Date 2011-03-16 Time 09:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-02-02 Cont ID  
Sent By lwagner Date 2011-02-02 Time 10:15 Rev Time 0.00
Received By lwagner Date 2011-02-01 Time 14:36 Sent To  
Notes
2011-02-02 10:04:36FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. PLUMBING 403.1 MINIMUN REQUIRED FIXTURES- BUSINESS:
 1 DRINKING FOUNTAIN IS REQUIRED PER 100 OCCUPANTS.
  
 2. PLUMBING 909.1 THE SINK IN ROOM 111 IS RUNNING
 THROUGH THE WET VENT FOR THE RESTROOMS. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 3. 106.3.5.1.3 PLUMBING (3) DRAWING REQUIRED FOR WATER
 PIPING.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2011-03-28 Cont ID  
Sent By aaponte Date 2011-03-28 Time 10:40 Rev Time 0.00
Received By aaponte Date 2011-03-28 Time 10:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2011-03-14 Cont ID  
Sent By aaponte Date 2011-03-14 Time 15:02 Rev Time 0.00
Received By aaponte Date 2011-03-14 Time 15:02 Sent To  
Notes
2011-03-14 15:15:561. PLEASE SUBMIT UNITY OF TITLE.
 2. PLEASE REVISE ELEVATION ACCORDING TO DAC APPROVAL.
 3. PARKING FROM ALLEY SHALL INCLUDE A 5 FOOT LANDSCAPE
 BUFFER ON THE NORTH SIDE.
 4. MECHANICAL EQUIPMENT ON THE ROOF SHALL BE ENCLOSED
 AND SCREENED. PLEASE INDICATE THE HEIGHT OF PROPOSED
 MECHANICAL UNITS TO DEMONSTRATE EXISTING PARAPET WALL
 WILL PROVIDE SUFFICIENT SCREENING.
 5. PLEASE INDICATE LOCATION OF EXISTING CURB CUT ON
 DIXIE HWAY. IF LARGER THAN REQUIRED FOR PROPOSED
 DRIVEWAY, A PERMIT FROM FDOT WILL BE REQUIRED TO MODIFY
 THE CURB CUT.
 6. TRASH RECEPTACLES SHALL BE SCREENED WITH A WALL,
 WOOD OR STEEL OPAQUE FENCE. LANDSCAPE SHALL BE PROVIDED
 AROUND THE SCREENING WITH SHRUBS AND HEDGES (SEC
 94-444(B)).
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-01-25 Cont ID  
Sent By aaponte Date 2011-01-25 Time 13:43 Rev Time 0.00
Received By aaponte Date 2011-01-25 Time 13:43 Sent To  
Notes
2011-01-25 16:30:121. PROPOSED PROJECT INCLUDES TWO SEPARATE PARCELS. A
 UNITY OF TITLE WILL BE REQUIRED. SURVEY SHALL INDICATE
 PROPERTY LINES, CURB CUTS, UNDERGROUND AND ABOVE GROUND
 UTILITY LINES.
 2. PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 3.. NEW MECHANICAL EQUIPMENT SHALL BE ENCLOSED AND
 SCREENED IN SUCH A MANNER THAT THE ENCLOSURE IS
 DESIGNED AS AN INTEGRAL PART OF THE OVERALL BUILDING
 DESIGN.
 4. A SEPARTE PERMIT IS REQUIRED FOR PAVING AND
 STRIPING.
 5. A FIVE FEET LANDSCAPE BUFFER IS REQUIRED ON THE
 NORTH PROPERTY LINE. PROPOSED PARKING LAYOUT DOES NOT
 ALLOW FOR REQUIRED LANDSCAPE BUFFER. PLEASE CONSIDER
 HAVING ANGLE PARKING AND ONE-WAY DRIVE WITH EXIT AT THE
 ALLEY.
 6. PLEASE INDICATE EXISTING STREETSCAPE IN SITE PLAN
 DRAWING.
 7. PROPOSED MAIN ENTRANCE DOOR IS ENCROACHING INTO THE
 TRAVEL LANE, CREATING AN UNSAFE SITUATION.
 8. PLEASE INDICATE ACCESS ROUTE TO THE PROPOSED
 CONCRETE PATH FOR ROLL OUT TRASH CANS. IF CONTAINERS
 ARE KEPT OUTSIDE, SCREENING SHALL BE PROVIDED.
 9. CURB PROVIDED WITHIN THE PARKING AREA SHALL BE BUILT
 WITH A 5 FEET RADIOUS.
 10. A MINIMUM OF 50% TRANSPARENCY IS REQUIRED ON THE
 BUILIDNG FACADE ALONG DIXIE HIGHWAY- ONLY 16.25%
 PROVIDED.
 11. A MINIMUM OF 30% TRANSPARENCY IS REQUIRED ALONG 9TH
 STREET- ONLY 8.3% PROVIDED.