| 2011-02-11 09:32:50 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- SCOPE OF WORK SHOWN ON THE PERMIT APPLICATION |
| | DOESN'T MATCH SCOPE OF WORK SHOWN ON PLANS SUBMITTED. |
| | PROPOSED FLOOR PLAN SHOWS NEW LAYOUT FOR THE MASTER |
| | BEDROOM, NEW KITCHEN, NEW FRAMED OPENINGS, NEW A/C, |
| | ETC. REVISE SCOPE OF WORK AND VALUATION ON PERMIT |
| | APPLICATION AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | *** NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL ( NEED 2 COPIES. ONLY ONE |
| | SUBMITTED) AS REQUIRED BY DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG IMPACT WINDOWS. NOA 03-1211.01 SUBMITTED |
| | EXPIRED ON APRIL 29, 2009. |
| | ***NOTE: CLARIFY IF USING IMPACT OR NON-IMPACT SINGLE |
| | HUNG WINDOWS. TWO DIFFERENT PRODUCT APPROVALS WERE |
| | SUBMITTED. |
| | B) SINGLE HUNG NON-IMPACT WINDOW. NOA 07-1029.08 WAS |
| | SUPERSEDED BY MIAMI-DADE WEBSITE. NEED CURRENT ONE. |
| | |
| | C) IMPACT HORIZONTAL SLIDING WINDOW. NOA 03-1203.02 |
| | SUBMITTED EXPIRED ON MARCH 04/ 2009. AND, CLARIFY WHERE |
| | IS THIS WINDOW GOING TO BE INSTALLED. PLANS DON'T |
| | SPECIFY ANY HORIZONTAL SLIDING WINDOWS. |
| | |
| | D) WINDOW MULLIONS: NOA 06-0905.11 SUBMITTED IS FOR |
| | IMPACT MULLIONS. SOMEBODY WROTE NON-IMPACT ON THE NOA. |
| | THIS INFORMATION IS MISLEADING. NEED TO COORDINATE IF |
| | USING IMPACT OR NON-IMPACT WINDOWS. |
| | |
| | E) HURRICANE SHUTTERS IF USING NON-IMPACT WINDOWS AND |
| | DOORS. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE, |
| | AND, CLEARLY MARK ON SHUTTERS DRAWINGS ANCHOR TYPE AND |
| | SPACING TO BE USED TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | F) ENTRY DOOR AND KITCHEN EXTERIOR DOOR. PROVIDE |
| | COMPLETE PRODUCT APPROVAL. MISSING THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PROVIDE 2 COPIES. |
| | |
| | G) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND |
| | SECTIONS. PROVIDE ONLY THE PRODUCT APRPOVAL COVER PAGE |
| | AND PAGE SHOWING THE CONNECTOR. THIS APPLIES TO |
| | STRUCTURAL CONNECTORS ONLY. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 5- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100 OF CHAPTER 13 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- PROVIDE SITE PLAN PLAN OR SURVEY TO SHOW DISTANCE |
| | FROM MASTER BEDROOM SIDE TO THE ADJACENT GARAGE. TO |
| | PROVIDE/VERIFY COMPLIANCE WITH THE SEPARATION |
| | REQUIREMENTS OF SEC. R309.2 AND EXTERIOR WALLS AND |
| | OPENINGS PROTECTION REQUIREMENTS OF TABLE R302.1. |
| | |
| | 7- SHEET A-1: |
| | A) DESIGN PRESSURES FOR WINDOWS DON'T CORRESPOND TO |
| | EXPOSURE "C" AS SPECIFIED ON THE WIND INFORMATION TABLE |
| | ON SAME SHEET. PROVIDE THE DESIGN PRESSURES BASED O THE |
| | WALL LOCATION (INTERIOR OR END) AND ACCORDING TO THE |
| | SIZE OF THE WINDOW. |
| | |
| | B) PROVIDE THE DESIGN PRESSURES FOR THE EXTERIOR DOORS. |
| | |
| | C) UPDATE WIND INFORMATION TABLE. REFERENCE CORRECT |
| | BUILDING CODE AND SECTION. REFER TO THE 2007 FLORIDA |
| | RESIDENTIAL CODE AND SEC. R301. IN ADDITION THERE ARE |
| | NO TABLES 1606.2A AND 1606.2B. |
| | |
| | D) CLARIFY WHAT'S 17PSF BEARING ON THE ROOF DEAD LOAD? |
| | |
| | E) CLARIFY WHAT'S 30PSF BEARING ON THE TOTAL ROOF LIVE |
| | LOAD? |
| | |
| | F) CLARIFY WHAT'S ROOF TRUSS LOAD PER TRUSS |
| | ENGINEERING. ENGINEER OF RECORD IS THE ONE WHO PERFORMS |
| | THE DESIGN OF THE STRUCTURE. TRUSSES ARE THEN DESIGNED |
| | PER THE ENGINEER OF RECORD DESIGN ASSUMPTIONS. |
| | |
| | G) REVISE AREA CALCULATIONS TO SHOW PROPOSED FLOOR |
| | PLAN. FLOOR PLANS DON'T SHOW ANY ENCLOSED PORCH. THIS |
| | WAS TAKEN FROM PAPA. INFORMATION NO LONGER MATCHES. |
| | |
| | H) UPDATE BUILDING NOTES TO REFLECT ACTUAL BUILDING |
| | CONDITIONS. THIS WAS TAKEN FROM PAPA. INFORMATION NO |
| | LONGER MATCHES. |
| | |
| | 8- PROPOSED FLOOR PLAN SHOWS NEW A/C. PROVIDE COMPLETE |
| | INFORMATION FOR A/C PERMIT UNDER A SEPARATE PERMIT. |
| | ALSO, PROPOSED FLOOR PLAN DOESN'T MATCH PROPOSED |
| | ELECTRICAL FLOOR PLAN. SEE LOCATION OF A/C AIR HANDLER |
| | UNIT AND COMPRESSOR UNIT. REVISE ELECTRICAL PLAN AS |
| | REQUIRED. |
| | |
| | 9- SHEET A-2: |
| | A) WALL SECTION: THERE ARE SPECIFICATIONS FOR 2X4'S AND |
| | 2X6'S ON SAME DRAWING. REVISE AS REQUIRED TO MATCH. |
| | ALSO, BASE PLATE IS ATTACHED TO 2X10 FLOOR JOIST OR |
| | CONCRETE SLAB. REVISE AS REQUIRED. BOTH ARE MENTIONED. |
| | |
| | B) TYPICAL WALL SECTION. REVISE SIZE OF WOOD STUDS TO |
| | MATCH. ARE 2X4'S OR 2X6'S. |
| | |
| | C) REVISE EAST ELEVATION TO MATCH FLOOR PLAN. CHECK |
| | WINDOW ON MASTER BEDROOM. |
| | |
| | 10- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |