| 2011-02-02 16:10:28 | ****PROVISO**** |
| | ****REVISION REQUIRED**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. SEE FEMA NFIP REQUIREMENTS, IF THE GARAGE IS NOT |
| | ELEVATED TO DFE, FLOOD OPENINGS REQUIRED FOR |
| | SUBSTANTIAL IMPROVEMENTS. SEE CFR TITLE 44, SEC. |
| | 60.3(5). THIS INFORMATION IS TO BE INCLUDED ON THE |
| | ELEVATION CERTIFICATE, A9. ALTERNATIVELY, FLOOR CAN BE |
| | RAISED TO DFE (7'?6"). SEE FEMA/NFIP WEBSITE FOR |
| | GUIDANCE. SUBMIT REVISED ELEVATION CERTIFICATE. |
| | |
| | 2. A SURVEY IS TO BE INCLUDED WITH THE ELEVATION |
| | CERTIFICATE, SEE ELEVATION CERTIFICATE, SECTION C. |
| | SUBMIT REVISED ELEVATION CERTIFICATE. |
| | |
| | 3. ELEVATION CERTIFICATE, C2 E, MECHANICAL EQUIPMENT |
| | REQUIRED TO BE ELEVATED TO 7'6", CFR TITLE 44, SECTION |
| | 60.3. MECHANICAL EQUIPMENT IS SHOWN AS 5.8'. THIS DOES |
| | NOT MEET THE NFIP REQUIREMENTS FOR SUBSTANTIAL |
| | IMPROVEMENTS. THE PERMIT WAS ISSUED WITH PROVISO THAT |
| | THE MECHANICAL PLANS INCLUDE PROPOSED ELEVATION OF |
| | EQUIPMENT, BUT I WAS UNABLE TO LOCATE THAT INFORMATION |
| | ON THE MECHANICAL PLANS SUBMITTED. PLEASE ADDRESS. |
| | SUBMIT REVISED ELEVATION CERTIFICATE. |
| | |
| | 4. ELEVATION CERTIFICATE TO INCLUDE AN ORIGINAL |
| | SIGNATURE, SEE ELEVATION CERTIFICATE INSTRUCTIONS. |
| | SUBMIT REVISED ELEVATION CERTIFICATE. |
| | |
| | 5. INCORPORATE REVISED ROOF TRUSS CONNECTOR SCHEDULE |
| | INTO APPROPRIATE STRUCTURAL SHEET (NOTED AS S6 ON |
| | ENGINEER'S LETTER). SUBMIT REVISED S6 |
| | |
| | 6. REVISE THE SITE PLAN TO SHOW PROPOSED CHANGES SO |
| | THAT SITE PLAN BUILDING FOOTPRINT WILL MATCH |
| | ARCHITECTURAL DRAWINGS. SUBMIT REVISED SITE PLAN. |
| | |
| | 7. PROVIDE PRODUCT APPROVALS FOR FRONT DOOR (UNLESS PGT |
| | FRENCH DOOR WAS INSTALLED), SIDING, FAC9B72. PRODUCT |
| | APPROVALS TO BE REVIEWED BY DOR PRIOR TO SUBMITTAL. |
| | SUBMIT PRIOR TO INSTALLATION. |
| | |
| | 8. SHEET A2 WAS NOT SUBMITTED WITH THIS REVISION, BUT |
| | IT APPEARS THAT THE FIRST FLOOR COVERED DECK IS |
| | AFFECTED BY THIS REVISION (CHANGE IN SIZE, LOCATION OF |
| | FOOTINGS). SUBMIT REVISED A2. |
| | |
| | |