Plan Review Details - Permit 11010182
Plan Review Stops For Permit 11010182
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-11 Cont ID  
Sent By shill Date 2011-02-11 Time 18:12 Rev Time 0.00
Received By shill Date 2011-02-11 Time 18:12 Sent To  
Notes
2011-02-11 18:12:32PROVISO - DBPR APPROVAL TO BE SUBMITTED PRIOR TO PERMIT
 ISSUANCE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-19 Cont ID  
Sent By shill Date 2011-01-19 Time 19:24 Rev Time 0.00
Received By shill Date 2011-01-19 Time 18:37 Sent To  
Notes
2011-01-19 19:16:20****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. COVER LETTER STATES THAT THE SCOPE IS ENTIRELY NON
 STRUCTURAL, BUT THERE ARE NUMEROUS DETAILS FOR ROOF
 OPENINGS AND RTU DETAILS. PLEASE REMOVE OR REVISE
 LETTER TO CORRELATE WITH THE WORK PROPOSED.
  
 2. COVER LETTER, COVER SHEET, AND VARIOUS DETAILS REFER
 TO EXPOSURE CLASSIFICATION AS B, AND WIND SPEEDS OF
 120, 140, AN 146. THE CITY OF WEST PALM BEACH IS
 ENTIRELY IN THE 140MPH WIND ZONE, THIS PARCEL IS
 LOCATED IN EXPOSURE C BASED ON AERIALS. PLEASE REVISE
 AFFECTED DETAILS AND NOTES. FBC1609.
  
 3. THERE ARE NUMEROUS RTU DETAILS. PLEASE LABEL EACH
 DETAIL WHICH IS APPLICABLE TO THIS JOB AND INCLUDE A
 DETAIL MARKER ON THE FLOOR PLAN, OR OTHERWISE IDENTIFY
 INSTALLATION LOCATION AND PURPOSE OF THE VARIOUS
 DETAILS. REMOVE DETAILS WHICH ARE NOT APPLICABLE TO
 THIS JOB.
  
 4. COMPONENT & CLADDING PRESSURES ARE FOR 120 EXPOSURE
 B AND ARE TOO LOW FOR THIS PROJECT. EITHER REMOVE THE
 NON COMPLIANT PRESSURES OR REVISE TO COMPLY. C & C
 DESIGN PRESSURES DO NOT APPEAR TO BE APPLICABLE TO THIS
 JOB.
  
 5. "PROJECT DATA" ON COVER SHEET STATE THAT THIS IS A
 LEVEL 2 ALTERATION. THIS PROJECT ALSO APPEARS TO BE A
 CHANGE OF OCCUPANCY; BASED ON OUR RECORDS, THIS WAS A
 BUSINESS OCCUPANCY. PLEASE SEE FBC EXISTING BUILDING
 CHAPTER 9 (OR APPLICABLE SECTION BAED ON METHOD OF
 COMPLIANCE). SHOW COMPLIANCE WITH ALL REQUIREMENTS FOR
 A CHANGE OF OCCUPANCY. PLEASE ALSO SEE FBC 309,
 MERCANTILE OCCUPANCIES SHALL INCLUDE "RESTAURANTS AND
 DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF LESS
 THAN 50 PERSONS."
  
 6. PLEASE PROVIDE MORE INFORMATION TO SHOW COMPLIANCE
 WITH FBC TABLE 1004.1.1. DESIGNER HAS USED 15 SF PER
 PERSON; THIS IS FOR SEATING WITH TABLES AND CHAIRS.
 WILL NON FIXED SEATING BE PROVIDED? WAITING AREA SHOULD
 USE 5 SF PER OCCUPANT. OFFICE AREA WAS NOT INCLUDED IN
 CALCULATION. PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 7. COVER SHEET STATES THAT THIS IS A TYPE IIB BUILDING,
 BUT OUR RECORDS SHOW WOOD TRUSSES ON THE PITCHED
 SECTIONS OF THE ROOF, SEE FBC 602.2. PLEASE EITHER
 REVISE OR EXPLAIN TYPE IIB.
  
 8. FBC 11-7.2(1), COUNTER AT CASH REGISTER, SHOW
 LENGTH.
  
 9. FBC 11-4.32, PROVIDE A DETAIL FOR THE FIXED SEATING.
  
 10. FBC 11-5.5, PROVIDE A DETAIL FOR THE "SERVING
 AREA."
  
 11. FBC 11-5.5, 11-5.3, SHOW WIDTH OF FOOD SERVICE LINE
 AND ALSO SHOW ACCESS AISLE TO FIXED SEATING.
  
 12. FBC 11-5.6, WILL SELF SERVICE SHELVES OR DISPENSERS
 BE PROVIDED? PROVIDE A DETAIL IF REQUIRED.
  
 13. FBC 11-4.1(3), WORK AREAS ARE TO BE DESIGNED SO
 THAT EMPLOYEES CAN APPROACH, ENTER, AND EXIT. SEE THE
 "OFFICE," DOOR LACKS MANEUVERING CLEARANCE, SEE FBC 11
 FIGURE 25.
  
 14. DBPR APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE,
 FS509. PLEASE SEE HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/
 HR/FORMS/PLANREVIEWFORMS.HTML FOR MORE INFORMATION.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-14 Cont ID  
Sent By rlecky Date 2011-01-14 Time 14:57 Rev Time 0.00
Received By rlecky Date 2011-01-14 Time 14:25 Sent To  
Notes
2011-01-14 15:10:40THE FOLLOWING WAS NOTED ON THE SINGLE SET OF PLANS
 SUBMITTED.
 3/0 CONDUCTORS ARE REQUIRED FOR A 200 AMP ELECTRIC
 SERVICE. NEC 310.16
 ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-01-20 Cont ID  
Sent By wjolin Date 2011-01-20 Time 14:10 Rev Time 0.00
Received By wjolin Date 2011-01-20 Time 13:17 Sent To  
Notes
2011-01-20 14:10:401558 PALM BEACH LAKES BOULEVARD, SUITE #5
 PERMIT #11010182
 REVIEW COMMENTS - FIRE
  
 *****DRAWINGS REQUIRE FIRE DEPARTMENT STAMP ONCE
 BUILDING DEPT COMMENTS HAVE BEEN ADDRESSED*****
  
  
 PROVIDE THE OCCUPANCY TYPE OF THE PREVIOUS TENANT
 OCCUPYING THIS SUITE.
  
 RESTAURANTS WITH AN OCCUPANT LOAD LESS THAN 50 PERSONS
 ARE CLASSIFIED AS MERCANTILE OCCUPANCIES.
  
 PROVIDE K-TYPE PORTABLE FIRE EXTINGUISHER IN KITCHEN
 AREA. PROVIDE ABC-TYPE PORTABLE FIRE EXTINGUISHER IN
 NON-KITCHEN AREAS.
  
 PROVIDE MINIMUM 8-INCH STEEL/GLASS BAFFLE BETWEEN THE
 FRYERS AND SURFACE FLAMES OF THE WOK.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION/MODIFACTION OF THE FIRE SPRINKLER SYSTEM,
 FIRE ALARM SYSTEM AND KITCHEN HOOD SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2011-02-14 Cont ID  
Sent By lwagner Date 2011-02-14 Time 13:59 Rev Time 0.00
Received By lwagner Date 2011-02-14 Time 13:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2011-01-28 Cont ID  
Sent By lwagner Date 2011-01-28 Time 14:57 Rev Time 0.00
Received By lwagner Date 2011-01-28 Time 14:20 Sent To  
Notes
2011-01-28 14:57:00FBC FUEL GAS REVIEW #1
 DENIED:
  
 1. KITCHEN EQUIPMENT PLAN DOES NOT MATCH WITH THE
 APPLIANCES SHOWN ON P-1 GAS DRAWING.
  
 2. WATER HEATER IS LISTED AS GAS ON A-1, AND AS
 ELECTRIC ON E-2, AND MISSING ON P-1 GAS RISER.
  
 3. PLEASE LABEL AUTOMATIC GAS SHUTOFF AND SHOW THAT IT
 IS BELOW CEILING WITH A VALVE AND UNION UPSTREAM.
  
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-03 Cont ID  
Sent By lmartine Date 2011-02-03 Time 16:51 Rev Time 0.00
Received By lmartine Date 2011-02-03 Time 16:51 Sent To  
Notes
2011-02-03 17:01:38C--7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-02-03 Cont ID  
Sent By lmartine Date 2011-01-28 Time 16:50 Rev Time 0.00
Received By lmartine Date 2011-01-12 Time 11:29 Sent To  
Notes
2011-01-12 11:52:43***************EXPEDITED******************
 C--7

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-02-11 Cont ID  
Sent By shill Date 2011-02-11 Time 17:47 Rev Time 0.00
Received By shill Date 2011-02-11 Time 17:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-02-14 Cont ID  
Sent By shill Date 2011-02-14 Time 14:03 Rev Time 0.00
Received By rregueir Date 2011-02-14 Time 14:03 Sent To  
Notes
2011-02-14 14:03:28OK PER RR
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-20 Cont ID  
Sent By rregueir Date 2011-01-19 Time 10:47 Rev Time 0.00
Received By rregueir Date 2011-01-19 Time 10:47 Sent To  
Notes
2011-01-19 17:10:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. INCLUDE OCCUPANT LOAD IN THE FRESH AIR CALCULATION,
 SHEET M1, FBC M403.3.
  
 2. SHOW HOW BALANCED RETURN AIR WILL BE PROVIDED, FBC
 M601.4.
  
 3. SEPARATE PLANS, PERMITS, AND REVIEWS REQUIRED FOR
 THE HOOD, WALK IN COOLER, AND WALK IN FREEZER. PLEASE
 REMOVE APPLICABLE DETAILS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-14 Cont ID  
Sent By lwagner Date 2011-02-14 Time 13:38 Rev Time 0.00
Received By lwagner Date 2011-02-14 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-01-28 Cont ID  
Sent By lwagner Date 2011-01-28 Time 14:20 Rev Time 0.00
Received By lwagner Date 2011-01-27 Time 13:32 Sent To  
Notes
2011-01-27 13:59:18FBC PLUMBING REVIEW #1
 DENIED:
  
 1. PLUMBING 607.3.2 THERMAL EXPANSION CONTROL WILL BE
 REQUIRED.
  
 2. THE HOT WATER FOR THE RESTROOM AND WOK APPEARS TO BE
 SUPPLIED FROM 2 SEPERATE PLACES. IS THIS A HOT WATER
 CIRCULATING SYSTEM?
  
 3. THE DRAIN FOR THE SODA DISPENSER ON THE SANITARY
 RISER SHOULD BE A HUB DRAIN OR FLOOR SINK WITH TRAP.
  
 NOTES:
  
 2. PLEASE SPECIFY TOTAL SEATING. FBC PLUMBING 2007
 403.2(2) SEPERATE FACILITIES SHALL NOT BE REQUIRED FOR
 FOOD SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR
 LESS.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-02-14 Cont ID  
Sent By jroach Date 2011-02-14 Time 08:39 Rev Time 0.00
Received By jroach Date 2011-02-14 Time 08:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-01-21 Cont ID  
Sent By jroach Date 2011-01-21 Time 15:55 Rev Time 0.00
Received By jroach Date 2011-01-21 Time 15:55 Sent To  
Notes
***NONE***