Plan Review Details - Permit 11010133
Plan Review Stops For Permit 11010133
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-02-01 Cont ID  
Sent By jgomez Date 2011-02-01 Time 10:31 Rev Time 0.00
Received By jgomez Date 2011-02-01 Time 09:05 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-01-11 Cont ID  
Sent By jgomez Date 2011-01-11 Time 16:45 Rev Time 0.00
Received By jgomez Date 2011-01-11 Time 15:58 Sent To  
Notes
2011-01-11 17:09:42RE-ROOF BUILDING REVIEW SECOND CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- MEMBRANE ATTACHMENT: ENGINEER SPECIFIES 4"O.C.
 FASTENER SPACING AT PERIMETER AND CORNER AREAS.
 CALCULATIONS ON SECOND PAGE SUBMITTED SHOWS FASTENER
 SPACING AT 3.6" AND 2.7" RESPECTIVELY. CALCULATIONS AND
 MEMBRANE ATTACHMENT SPECIFICATION DON'T MATCH. ON THE
 OTHER HAND ENGINEER TO SEE SEC. 4.2 OF RAS 137 FOR
 MINIMUM FASTENER SEPARATION REQUIRED. REVISE AS
 REQUIRED.
  
 2- INSULATION ATTACHMENT: ENGINEER SPECIFIES 6
 FASTENERS AT PERIMETER AND 8 FASTENERS AT CORNER AREAS.
 ACCORDING TO SEC. 9.1.2 OF RAS 117 ALL FRACTIONS SHALL
 BE ROUNDED UP TO THE NEXT WHOLE NUMBER. NOT ROUNDED
 DOWN. ALSO, REVISE EXPOSURE SHOWN ON SHEET 3. THIS
 BUILDING IS IN EXPOSURE "C" NOT "B". AND CLARIFY WHERE
 IS THE -45PSF MAXIMUM DESIGN PRESSURE FOR THE
 INSULATION ATTACHMENT TAKEN FROM?. REVISE AS REQUIRED.
  
  
 3- FASTENERS WITHDRAWAL RESISTANCE TEST (TAS 105) WILL
 BE REQUIRED FOR MECHANICALLY FASTENED ROOF COVERINGS.
 SEC. 4.3 OF RAS 137.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-07 Cont ID  
Sent By jgomez Date 2011-01-07 Time 16:50 Rev Time 0.00
Received By jgomez Date 2011-01-07 Time 16:35 Sent To  
Notes
2011-01-07 16:55:19RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PLEASE IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA
 09-0217.03 SUBMITTED IS GOING TO BE INSTALLED.
 ***NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE
 USED IN THIS BUILDING.
  
 2- PROVIDE RAS 117 AND RAS 137 CALCULATIONS AS REQUIRED
 BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA. (PROVIDE
 2 COPIES WITH ORIGINAL SEAL AND SIGNATURE).
 NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 REVISIONS THIS BUILDING IS LOCATED ON EXPOSURE 'C".
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-02-01 Cont ID  
Sent By jgomez Date 2011-02-01 Time 09:05 Rev Time 0.00
Received By jgomez Date 2011-02-01 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-11 Cont ID  
Sent By jgomez Date 2011-01-11 Time 15:58 Rev Time 0.00
Received By jgomez Date 2011-01-11 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-07 Cont ID  
Sent By jgomez Date 2011-01-07 Time 16:35 Rev Time 0.00
Received By jgomez Date 2011-01-07 Time 16:35 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved