| 2011-01-11 11:06:09 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM |
| | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) |
| | |
| | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, |
| | PROVIDE CALCULATIONS. |
| | |
| | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG (WINDOWS). PLEASE |
| | PRINT COVER SHEET; EVALUATION REPORT WAS PROVIDED BUT |
| | THE COVER SHEET SHOWING PRODUCT APPROVAL NUMBER AND |
| | "APPROVED" STATUS IS ALSO REQUIRED. |
| | |
| | 3. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. INCLUDE THE PROPOSED |
| | DOOR ON THE FLOOR PLAN. |
| | |
| | 4. PLAN SHOULD SHOW ALL PROPOSED WORK. A RED TAG WAS |
| | ISSUED FOR "INTERIOR RENOVATIONS." APPLICATION |
| | SUBMITTED WAS FOR WINDOW AND DOOR REPLACEMENT ONLY. |
| | PERMIT DESCRIPTION HAS BEEN REVISED TO BE CONSISTENT |
| | WITH THE APPLICATION AND PERMIT DOCUMENTS SUBMITTED. IF |
| | ADDITIONAL WORK SUCH AS "MISC REPAIRS" ARE TO BE |
| | INCLUDED IN THIS PERMIT, PROVIDE A PLAN SHOWING |
| | PROPOSED WORK AND INCLUDE IN THE PERMIT DESCRIPTION. IT |
| | IS NOT CLEAR WHETHER OR NOT THIS PERMIT WILL ENTIRELY |
| | ADDRESS THE STOP WORK ORDER. |
| | |
| | |
| | |