Plan Review Details - Permit 11010070
Plan Review Stops For Permit 11010070
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-01-19 Cont ID  
Sent By jwitmer Date 2011-01-19 Time 07:56 Rev Time 0.55
Received By jwitmer Date 2011-01-19 Time 07:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2011-01-11 Cont ID  
Sent By rlecky Date 2011-01-11 Time 14:33 Rev Time 0.00
Received By rlecky Date 2011-01-11 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-01-20 Cont ID  
Sent By wjolin Date 2011-01-20 Time 12:50 Rev Time 0.00
Received By wjolin Date 2011-01-20 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-02 Cont ID  
Sent By lmartine Date 2011-02-02 Time 11:57 Rev Time 0.00
Received By lmartine Date 2011-02-02 Time 11:57 Sent To  
Notes
2011-02-02 11:57:45UNDER 5 K PLUMBING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-26 Cont ID  
Sent By lmartine Date 2011-01-26 Time 09:08 Rev Time 0.00
Received By lmartine Date 2011-01-10 Time 09:42 Sent To  
Notes
2011-01-10 09:42:08B8
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-04 Cont ID  
Sent By lwagner Date 2011-02-04 Time 10:36 Rev Time 0.00
Received By lwagner Date 2011-02-04 Time 10:11 Sent To  
Notes
2011-02-04 10:37:12MED GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-01-13 Cont ID  
Sent By lwagner Date 2011-01-13 Time 10:02 Rev Time 0.00
Received By lwagner Date 2011-01-13 Time 08:53 Sent To  
Notes
2011-01-13 10:01:20FBC PLUMBING 2007
 NFPA 99C 2002
 REVISION REVIEW #1
 DENIED:
  
 1. PLEASE SUBMIT VACUUM PUMP MANUFACTURERS
 SPECIFICATIONS SHOWING THAT 3/4" MAIN AND 1/2" RISERS
 ARE SUGGESTED OR REQUIRED. RAMVAC VACUUM PUMPS REQUIRE
 2" MAINS BELOW FLOOR SLOPED AT 1/4" PER FOOT. VACSTAR'S
 SMALLEST PUMP VS 20 REQUIRES A MINIMUM OF 1" MAIN -
 ETC.
  
 2. SANITARY DRAWINGS APPEAR TO BE ELIMINATING THE
 DRAINS FOR THE CHAIRS IN TREATMENT ROOMS 1 & 3. ARE
 THESE CHAIRS EXISTING?
  
 3. NFPA 99C 2002 5.3.3.6.3 VACUUM DRAINS ARE TO BE
 DIRECTLY CONNECTED TO THE SANITARY, TRAPPED, AND
 VENTED.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  