| 2011-01-06 08:07:45 | BUILDING PLAN REVIEW |
| | PERMIT: 11010034 |
| | ADD: 222 PICADILLY STREET |
| | CONT: LCI |
| | TEL: (561)307-4951 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1 DETAIL# 3 /A1.3 THE BREAK ROOM SINK, THE |
| | SINK IS LOCATED AT 34" ABOVE FLOOR LEVEL BUT DOEN'T |
| | APPEAR TO HAVE A FRONTAL APPROACH. 11-4.24.3 KNEE |
| | CLEARANCE THAT IS AT LEAST 27" HIGH 30" WIDE, AND 19" |
| | DEEP SHALL BE PROVIDED UNDERNEATH SINKS. 11-4.24.5 |
| | CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT LEAST 30 |
| | INCHES BY 48 INCHES (760 MM BY 1219 MM) COMPLYING WITH |
| | SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK |
| | TO ALLOW FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL |
| | BE ON AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF |
| | 19 INCHES (485 MM) UNDERNEATH THE SINK. |
| | |
| | 2) SHEET A1.1 DETAIL# 6/ A1.3 THE RECEPTIONIST WALL |
| | SECTION INDICATES A COUNTER ON THE RECEPTIONIST SIDE OF |
| | THE WALL BUT NO COUNTER FOR HANDICAPPED PERSONS TO BE |
| | ABLE TO TRANSACT BUSINESS. 11-7.2 SALES AND SERVICE |
| | COUNTERS, TELLER WINDOWS, INFORMATION COUNTERS. |
| | (2) AT TICKETING COUNTERS, TELLER STATIONS IN A BANK, |
| | REGISTRATION COUNTERS IN HOTELS AND MOTELS, BOX OFFICE |
| | TICKET COUNTERS, AND |
| | OTHER COUNTERS THAT MAY NOT HAVE A CASH REGISTER BUT AT |
| | WHICH GOODS OR SERVICES ARE SOLD OR DISTRIBUTED, |
| | EITHER: |
| | (I) A PORTION OF THE MAIN COUNTER WHICH IS A MINIMUM OF |
| | 36 INCHES (915 MM) IN LENGTH SHALL BE PROVIDED WITH A |
| | MAXIMUM HEIGHT |
| | OF 36 INCHES (915 MM); OR |
| | (II) AN AUXILIARY COUNTER WITH A MAXIMUM HEIGHT OF 36 |
| | IN (915 MM) IN CLOSE PROXIMITY TO THE MAIN COUNTER |
| | SHALL BE PROVIDED; OR |
| | (III) EQUIVALENT FACILITATION SHALL BE PROVIDED (E.G., |
| | AT A HOTEL REGISTRATION COUNTER, EQUIVALENT |
| | FACILITATION MIGHT CONSIST OF: |
| | (1) PROVISION OF A FOLDING SHELF ATTACHED TO THE MAIN |
| | COUNTER ON WHICH AN INDIVIDUAL WITH DISABILITIES CAN |
| | WRITE, AND |
| | (2) USE OF THE SPACE ON THE SIDE OF THE COUNTER OR AT |
| | THE CONCIERGE DESK, FOR HANDING MATERIALS BACK AND |
| | FORTH). |
| | |
| | 3) PLEASE REVIEW DOORS IN THE NEWLY CONSTRUCTED WALLS, |
| | 1-101/2, & 1-121/1 IN BOTH THESE CASES FROM THE IN |
| | SWING POSITION THEY ARE MISSING THE REQUIRED 18" ON THE |
| | LATCH SIDE OFTHE DOOR. FBC-B 11-413.6 MANEUVERING |
| | CLEARENCES AT DOORS. |
| | |
| | 4) PLEASE REVIEW THE EXISTING DOORS, 1-103/1, 1-104/1, |
| | 1-106/1 & 1-115/1 THEY TO ARE MISSING THE REQUIRED 18" |
| | MANEUVERING CLEARENCES AT DOORS. PLEASE REVIEW |
| | 11-4.1.6(2)(A) DISPROPORTIONATE COST AND LIST WHERE 20% |
| | OF THE CONTRACT VALUE TO UPGRADE |
| | TENANT SPACE TO COMPLY WITH THE ACCESSIBILITY CODE. |
| | |
| | 5) SHEET A1.1PLANS DO NOT INDICATE IF THE EXTERIOR |
| | DOORS (1-105/ 1 & 2) HAVE DOOR CLOSERS IF THEY DO THEN |
| | THESE DOORS WOULD ALSO NEED TO HAVE 12" CLEAR ON THE |
| | LATCH SIDE OF THE DOOR. |
| | |
| | 6) ROOMS 116, 117 & 118 1WHEN THE COST OF ALTERATIONS |
| | NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED |
| | AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST |
| | OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE |
| | MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE |
| | ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. |
| | 2007 EXISTING BUILDING CODE LEVEL II 706.1 GENERAL. |
| | A BUILDING, FACILITY, OR ELEMENT THAT IS ALTERED SHALL |
| | COMPLY WITH CHAPTER |
| | 11 OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, |
| | BUILDING. |
| | |
| | 2007/2009 FBC- CHAPTER 11 ACCESSIBILITY SECTION |
| | 11-4.1.3 (11) TOILET FACILITIES. |
| | IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND |
| | COMMON USE TOILET ROOM SHALL COMPLY |
| | WITH SECTION 11-4.22. OTHER TOILET ROOMS PROVIDED FOR |
| | THE USE OF OCCUPANTS OF SPECIFIC |
| | SPACES (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF |
| | A PRIVATE OFFICE) SHALL BE ADAPTABLE. |
| | |
| | IF THE TOILET ROOMS ARE EXISTING, THEN FBC-B |
| | 11-4.1.6(2) DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE |
| | EVENT OF DISPROPORTIONALITY. |
| | |
| | 1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE |
| | PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. |
| | |
| | (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| | PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| | THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| | ORDER: |
| | |
| | (I) AN ACCESSIBLE ENTRANCE; |
| | |
| | (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA: |
| | |
| | (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| | A SINGLE UNISEX RESTROOM: |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |