Plan Review Details - Permit 10120674
| Plan Review Stops For Permit 10120674 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2011-01-26 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2011-01-26 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-01-26 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2011-01-11 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-01-11 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-01-11 |
Time |
11:30 |
Sent To |
B |
|
| Notes |
| 2011-01-11 11:45:57 | 1221 ANDREWS ROAD | | | PERMIT #10120674 | | | EXPIRED PERMIT #09060576 | | | REVIEW COMMENTS - FIRE | | | | | | PLANS ARE DATED 02/12/09 WITH REVISIONS DATED 12/20/10. | | | SEVERAL PLAN SHEETS APPEAR TO BE MISSING. | | | | | | NO INFORMATION GIVEN ON CURRENT BUILDING USE, EXIT | | | LOCATIONS, PORTABLE FIRE EXTINGUISHER LOCATIONS ETC. | | | | | | WOODWORKING OPERATIONS SHALL COMPLY CHAPTER 31 - FOREST | | | PRODUCTS OF THE FLORIDA FIRE PREVENTION CODE 2007 | | | EDITION (NFPA 1). | | | | | | NO SMOKING SIGNS SHALL BE POSTED IN ANY LOCATIONS | | | SUBJECT TO SAWDUST GENERATION. | | | | | | PLEASE INDICATE HOW THE DUST COLLECTION SYSTEM IS | | | INTERLOCKED WITH THE MACHINERY PRODUCING SAWDUST. | | | | | | PLEASE INDICATE (MICRONS) THE SIZE OF DUST PARTICLES | | | THAT WILL BE GENERATED. | | | | | | DRAWINGS DO NOT SHOW FLOOR PLANS, ONLY SITE PLAN TYPE | | | DRAWINGS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-01-11 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-01-03 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2011-01-03 10:24:19 | INCOMING SENT TO <$5,000.00 MECHANICAL BOX. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-01-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-01-05 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-01-05 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2011-01-05 14:40:33 | PLANS DENIED | | | PLEASE PROVIDE A LISTING OF THE DUST COLLECTOR PER | | | SECTION 301.5.1 FBC (M) 2007 AND 510.2.2 COMBUSTIBLE | | | FIBERS. | | | PLEASE PROVIDE THE MATERIALS USED FOR THE DUCTWORK PER | | | SECTION 510.8 AND TABLE 510.8 2007 FBC (M) | | | REFER TO SECTION 511.1.1 COLLECTORS AND SEPARATORS . | | | PLEASE REFER TO NFPA 664 SECTION 5.1.1 APPROVED | | | QUALIFICATIONS . | | | PLEASE REFER TO SECTION 301.12 WIND RESISTANCE. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | | | | |
|
|
|