Plan Review Details - Permit 10120637
Plan Review Stops For Permit 10120637
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-10 Cont ID  
Sent By shill Date 2011-02-10 Time 17:38 Rev Time 0.00
Received By shill Date 2011-02-10 Time 17:38 Sent To  
Notes
2011-02-10 17:39:16***PROVISO***
 ***REVISION REQUIRED***
  
 THE CENTER PANEL OF THE ARCHED FIXED WINDOW, FAMILY
 ROOM, EXCEEDS THE PRODUCT APPROVAL LIMITATION. EITHER
 SUBMIT NEW PRODUCT APPROVAL, REVISE THE WINDOW PANEL
 SIZE, OR SUBMIT SITE SPECIFIC ENGINEERING.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-04 Cont ID  
Sent By shill Date 2011-01-04 Time 16:13 Rev Time 0.00
Received By shill Date 2011-01-04 Time 11:40 Sent To  
Notes
2011-01-04 16:58:58****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SITE PLAN AND MECHANICAL PLAN SHOW THE MECHANICAL
 EQUIPMENT AND SLAB ENCROACHING THE PROPERTY LINE. OTHER
 SHEETS SHOW THE MECHANICAL EQUIPMENT IN ANOTHER
 LOCATION. PLEASE CORRELATE.
  
 2. PROVIDE OVERALL AND UNIT SIZE FOR THE ARCHED FIXED
 WINDOW, FAMILY ROOM. THE HEIGHT IS PROVIDED, NO WIDTH
 SHOWN FOR EITHER THE OVERALL OPENING OR FOR THE UNITS
 SEPARATED BY MULLIONS. FBC301.
  
 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE ANCHORS SPECIFIED FOR THE MECHANICAL UNITS,
 FAC9B72. WIND RESISTANCE TO SLIDING AND OVERTURNING TO
 BE SHOWN AS WELL AS UPLIFT.
  
 4. 1" AND 2" MULLION PRODUCT APPROVALS WERE SUBMITTED.
 PLEASE SPECIFY PROPOSED LOCATIONS.
  
 5. SEE FBC R 1104.A.2, WALLS CONSIDERED CEILINGS.
 COFFERED CEILINGS NOT SHOWN ON CEILING SQUARE FOOT AREA
 ON ENERGY CALCS.
  
 7. ENERGY CALC SHOWS TWO DIFFERENT TYPES OF FRAME WOOD
 ADJACENT WALLS (R11 AND R4.1), PLEASE SPECIFY ON PLAN.
  
 8. PLEASE CHECK ALL ENERGY CALC ITEMS FOR CONSISTENCY
 WITH THE PLAN SUBMITTED. FOR INSTANCE, ROOF ON ENERGY
 CALC IS SHINGLE, PLAN SHOWS TILE. GARAGE CEILING HEIGHT
 ON PLAN IS 10', ENERGY CALC SHOWS 8'. ENERGY CALC SHOWS
 TWO EXTERIOR DOORS, EAST ORIENTATION. PLAN SHOWS ONE
 DOOR, WEST ORIENTATION.
  
 9. SEE PREVIOUS COMMENT, AND ALSO NOTE THAT GARAGE
 FRAME WALL FACES WEST, ENERGY CALC SHOWS EAST
 ORIENTATION. PLEASE NOTE THAT ALTHOUGH THE SITE PLAN
 SHOWS "NORTH" ORIENTED TOWARDS THE TOP OF THE PAGE,
 ARCHITECTURAL SHEETS ARE REVERSED. NO "NORTH"
 DESIGNATION PROVIDED ON A SHEETS, BUT BASED ON THE SITE
 PLAN, "NORTH" WOULD BE THE BOTTOM OF THE PLAN. PLEASE
 CONFIRM ORIENTATION OF ALL ITEMS AND REVISE AS
 NECESSARY.
  
  
  
 PLAN SHOWS GARAGE FRAME WALL FACING WEST, ENERGY CALC
 SHOWS EAST.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-07 Cont ID  
Sent By rlecky Date 2011-02-07 Time 10:21 Rev Time 0.00
Received By rlecky Date 2011-02-07 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-01-05 Cont ID  
Sent By rlecky Date 2011-01-05 Time 14:58 Rev Time 0.00
Received By rlecky Date 2011-01-05 Time 14:01 Sent To  
Notes
2011-01-05 15:01:37PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94
 NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT
 RECEPTACLES. NEC 406.11
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
 GFCI PROTECTED RECEPTACLE REQUIRED AT THE MECHANICAL
 EQUIPMENT. NEC 210.63
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-02-23 Cont ID  
Sent By lfranco Date 2011-02-23 Time 16:23 Rev Time 1.00
Received By mgonzale Date 2011-02-23 Time   Sent To  
Notes
2011-02-23 09:40:04PASSED

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2011-01-24 Cont ID  
Sent By shill Date 2011-01-24 Time 13:55 Rev Time 0.00
Received By shill Date 2011-01-24 Time 13:55 Sent To  
Notes
2011-01-24 13:56:06PASSED UNDER 10120639
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 2011-02-23 Cont ID  
Sent By mgonzale Date 2011-02-23 Time   Rev Time 0.00
Received By mgonzale Date 2011-02-23 Time 09:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2011-02-08 Cont ID  
Sent By rmcdouga Date 2011-02-08 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2011-02-08 Time 07:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2011-01-07 Cont ID  
Sent By rmcdouga Date 2011-01-07 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2011-01-07 Time 10:57 Sent To  
Notes
2011-01-07 10:50:12GAS REVIEW IS DENIED
  
 1) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE AND SECTION OF PIPE.
  
 2) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 THE REQUIREMENTS FOR GAS PERMITS CAN BE FOUND AT THIS
 LINK. HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/GAS%20P
 ERMIT%20APPLICATION%20REQUIREMENTS.PDF
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-02-24 Cont ID  
Sent By rmcdouga Date 2011-02-24 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2011-02-07 Time 08:04 Sent To  
Notes
2011-02-07 08:06:11R8 "EXPEDITED" 2ND RUN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-24 Cont ID  
Sent By shill Date 2011-01-24 Time 13:55 Rev Time 0.00
Received By shill Date 2010-12-28 Time 15:49 Sent To  
Notes
2010-12-28 15:50:23R--12
 ****************EXPEDITED******************

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-01-04 Cont ID  
Sent By shill Date 2011-01-04 Time 11:39 Rev Time 0.00
Received By shill Date 2011-01-04 Time 11:39 Sent To  
Notes
2011-01-04 11:40:09RECEIPT # MU-2010-017829-0000
 4168 SF
  

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-02-17 Cont ID  
Sent By rkussner Date 2011-02-17 Time 09:28 Rev Time 0.00
Received By rkussner Date 2011-02-17 Time 09:28 Sent To  
Notes
2011-02-17 09:30:17***LANDSCAPE REVIEW NOT REQUIRED***
  
 PLEASE REFER TO PERMIT # 10120635 FOR THE LANDSCAPE
 PERMIT AND PLANS.--RAK

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2010-12-30 Cont ID  
Sent By rkussner Date 2010-12-30 Time 16:29 Rev Time 0.00
Received By rkussner Date 2010-12-30 Time 16:29 Sent To  
Notes
2010-12-30 16:30:53***LANDSCAPE REVIEW NOT REQUIRED***
  
 PLEASE REFER TO PERMIT #10120635 FOR LANDSCAPE PERMIT
 AND PLANS---RAK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-02-14 Cont ID  
Sent By shill Date 2011-02-11 Time 16:14 Rev Time 0.00
Received By hmoser Date 2011-02-11 Time 16:14 Sent To  
Notes
2011-02-11 16:14:51OK PER HM
  
 PROVISO - PROVIDE LEGIBLE ENGINEERING FOR A/C TIE DOWN
 AT INSPECTION
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-04 Cont ID  
Sent By hmoser Date 2011-01-04 Time 14:31 Rev Time 0.00
Received By hmoser Date 2011-01-04 Time 14:31 Sent To  
Notes
2011-01-04 11:28:14****CORRECTIONS****
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FS489.105, FS471, THE INDIVIDUAL RESPONSIBLE FOR THE
 MECHANICAL DESIGN (DONALD O'BRYON) IS NOT THE PERSON
 LISTED ON THE DBPR WEBSITE FOR THE LICENSE NUMBER ON
 THE PLAN, CAC032382. PLEASE ADDRESS.
  
 2. THE SITE PLAN S1 AND MECHANICAL PLAN SUBMITTED SHOW
 THE EQUIPMENT ENCROACHING THE PROPERTY LINE (OUTISDE OF
 THE GARAGE). THE SITE PLAN PREPARED BY THE SURVEYOR AND
 ARCHITECTURAL SHEETS SHOW THE MECHANICAL EQUIPMENT
 OUTSIDE THE KITCHEN. PLEASE ADDRESS.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-08 Cont ID  
Sent By rmcdouga Date 2011-02-08 Time 08:23 Rev Time 0.00
Received By rmcdouga Date 2011-02-08 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-01-07 Cont ID  
Sent By rmcdouga Date 2011-01-07 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2011-01-07 Time 10:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-02-17 Cont ID  
Sent By lfranco Date 2011-02-16 Time 17:11 Rev Time 0.00
Received By lfranco Date 2011-02-15 Time 10:52 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-01-13 Cont ID  
Sent By lfranco Date 2011-01-13 Time 15:12 Rev Time 0.00
Received By lfranco Date 2011-01-11 Time 17:03 Sent To  
Notes
2011-01-11 17:02:58PLANNING AND ZONING: *** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
  
 2. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE
 SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT
 BUILDING FACADE).
 SHOW ALL INFORMATION ON THE SURVEY AND PLANS.
  
 3. THE SETBACKS WITHIN THIS PROPERTY SHALL BE A MINIMUM
 OF THE FOLLOWING:
  
 3'-1" ONE SIDE AND 4'-11" THE OTHER SIDE. A MINIMUM OF
 8' SHALL BE MAINTAINED BETWEEN HOUSES. THE APPLICANT
 SHALL PROVIDE THE LOCATION AND DIMENSION OF THE HOME(S)
 ADJACENT TO THE SUBJECT PROPERTY. SHOW DIMENSIONS IN
 FEET AND INCHES (I.E. 3'-6"). SINCE PROPERTY IS
 SOMEWHAT ANGLED, SHOW DIMENSIONS WITHIN THE FRONT, MID
 AND REAR OF THE LOT AREAS THAT COMPLY WITH THE SETBACK
 REQUIREMENTS ABOVE. THIS COMMENT IS FOR THE SURVEY. THE
 SITE PLAN SHOWS THE CORRECT DIMENSIONS.
  
 4, INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION
 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 THERE ARE DISCREPANCIES BETWEEN THE SURVEY AND THE SITE
 PLAN. THE PLANS SHOW THE EQUIPMENT ENCROACHING INTO THE
 ADJACENT PROPERTY AND IN A DIFFERENT LOCATION THAN THE
 SURVEY.
  
 5. REVISE DISCREPANCIES FOR THE LOCATION OF THE HOME
 REGARDING THE FRONT SETBACK. THE SITE PLAN SHOWS THE
 BUILDING'S GARAGE AT 20'11" AND THE SURVEY SHOWS THE
 BUILDING'S FRONTAGE AT 24.3'. THE DIMENSION OF THE
 STRUCTURE SHALL BE FROM THE CLOSEST STRUCTURE INCLUDING
 THE ARCHITECTURAL FEATURES BY THE GARAGE'S SIDE FACADE
 AS SHOWN ON THE SITE PLAN.
  
 6. PROVIDE THE TOTAL HEIGHT OF THE BUILDING'S HEIGHT ON
 SHEET A05.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  