Plan Review Details - Permit 10120594
Plan Review Stops For Permit 10120594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-27 Cont ID  
Sent By jgomez Date 2010-12-27 Time 15:54 Rev Time 0.00
Received By jgomez Date 2010-12-27 Time 15:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-27 Cont ID  
Sent By jgomez Date 2010-12-27 Time 13:32 Rev Time 0.00
Received By jgomez Date 2010-12-27 Time 13:32 Sent To  
Notes
2010-12-27 13:41:18RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 09-0323.18 SUBMITTED.
  
 3- SPECIFY SQUARE FOOT OF FLAT ROOF TO BE INSTALLED.
 PERMIT FEE VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. REVISE AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-27 Cont ID  
Sent By jgomez Date 2010-12-27 Time 13:32 Rev Time 0.00
Received By jgomez Date 2010-12-27 Time 13:32 Sent To  
Notes
***NONE***