Plan Review Details - Permit 10120590
Plan Review Stops For Permit 10120590
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-10 Cont ID  
Sent By ddaniels Date 2011-01-10 Time 13:35 Rev Time 0.00
Received By ddaniels Date 2011-01-10 Time 13:34 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-29 Cont ID  
Sent By wjolin Date 2010-12-29 Time 15:23 Rev Time 0.00
Received By wjolin Date 2010-12-29 Time 14:08 Sent To M
Notes
2010-12-29 15:23:44600 VILLAGE BOULEVARD
 REVISION #10120590
 PERMIT #10090787
 MASTER #10070434
 REVIEW COMMENTS - FIRE
  
  
 THE UPRIGHT EXTENDED COVERAGE SPRINKLERS (TY6137) WITH
 A K-FACTOR OF 14.0 ARE ONLY UL LISTED FOR STANDARD
 RESPONSE IN THIS APPLICATION; HOWEVER, THE HYDRAULIC
 CALCULATION AREA USES THE AREA REDUCTION METHOD FOR
 QUICK RESPONSE SPRINKLERS.
  
 SUBMITTED DRAWINGS HAVE NOT BEEN SIGNED AND SEALED BY
 AN ENGINEER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-12 Cont ID  
Sent By hmoser Date 2011-01-12 Time 10:01 Rev Time 0.00
Received By hmoser Date 2011-01-06 Time 14:33 Sent To  
Notes
2011-01-06 14:33:49TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-03 Cont ID  
Sent By hmoser Date 2011-01-03 Time 13:55 Rev Time 0.00
Received By hmoser Date 2010-12-28 Time 09:32 Sent To  
Notes
2010-12-28 09:33:00SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-12 Cont ID  
Sent By hmoser Date 2011-01-12 Time 10:01 Rev Time 0.00
Received By hmoser Date 2011-01-12 Time 10:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-03 Cont ID  
Sent By hmoser Date 2011-01-03 Time 13:52 Rev Time 0.00
Received By hmoser Date 2011-01-03 Time 13:52 Sent To  
Notes
2011-01-03 13:55:39PLANS DENIED
 PLANS NOT SEALED OR STAMPED BY ENGINEER.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved