Plan Review Details - Permit 10120584
Plan Review Stops For Permit 10120584
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-25 Cont ID  
Sent By jgomez Date 2011-01-25 Time 11:09 Rev Time 0.00
Received By jgomez Date 2011-01-25 Time 08:53 Sent To PC
Notes
2011-01-25 11:16:27BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. N1100.0
 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11.
  
 2- REVISE ALL THE DESIGN PRESSURES ON SHEETS S2.0 AND
 S3.0 TO REFLECT THE REVISED BUILDING EXPOSURE "C".
  
 3- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS. PROVIDE
 COMPLETE PRODUCT NOA. ONLY COVER PAGE WAS SUBMITTED AT
 THIS TIME.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC. NEED APPROVAL FOR FRENCH DOORS AND
 SINGLE HUNG WINDOWS NOA'S SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-10 Cont ID  
Sent By jgomez Date 2011-01-10 Time 16:04 Rev Time 0.00
Received By jgomez Date 2011-01-10 Time 15:57 Sent To  
Notes
2011-01-10 16:31:38RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. N1100.0
 OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11. PLEASE
 MAKE SURE THE FORM IS COMPLETELY FILLED AND
 CORRESPONDING SIGNATURES AT BOTTOM OF FORM ARE
 PROVIDED.
  
 2- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". REVISE
 INFORMATION ON SHEETS C1, S2.0 AND S3.0 AS REQUIRED.
 REVISE THE DESIGN PRESSURES ACCORDINGLY.
  
 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) METAL ROOF AS SPECIFIED ON PLANS.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 6- SPECIFY CARBON MONOXIDE ALARMS BY ALL BEDROOMS AS
 REQUIRED BY SEC. R313.4 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-01-24 Cont ID  
Sent By rmcdouga Date 2011-01-24 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2011-01-24 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-11 Cont ID  
Sent By rmcdouga Date 2011-01-11 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2011-01-11 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-24 Cont ID  
Sent By rmcdouga Date 2011-01-24 Time 11:13 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2011-01-24 11:14:23TO JULIO GOMEZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-24 Cont ID  
Sent By rmcdouga Date 2011-01-24 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2011-01-03 Time 14:37 Sent To  
Notes
2011-01-03 14:38:07R--9
2011-01-03 14:37:28PLANS DELIVERED TODAY
  
2010-12-28 14:06:07SENT TO DENIED FILE UNDER "C". THERE ARE NO PLANS
 SUBMITTED. LUIS MARTINEZ LEFT MESSAGE ON CONTRACTOR'S
 VOICE MAIL. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-01-25 Cont ID  
Sent By jgomez Date 2011-01-25 Time 11:22 Rev Time 0.00
Received By jgomez Date 2011-01-25 Time 11:22 Sent To  
Notes
2011-01-25 11:24:31PLANS WERE NO STAMPED, BUT CALLED THE COUNTY TO VERIFY
 IF FEES WERE PAID BASED ON RECEIPT WITH TRACKING NO
 MU-2011-000957-0000 SUBMITTED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-01-10 Cont ID  
Sent By jgomez Date 2011-01-10 Time 16:00 Rev Time 0.00
Received By jgomez Date 2011-01-10 Time 16:00 Sent To  
Notes
2011-01-10 16:01:43BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-25 Cont ID  
Sent By jgomez Date 2011-01-25 Time 11:08 Rev Time 0.00
Received By jgomez Date 2011-01-25 Time 11:08 Sent To  
Notes
2011-01-25 11:08:53NEED SEPARATE A/C PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-10 Cont ID  
Sent By jgomez Date 2011-01-10 Time 16:03 Rev Time 0.00
Received By jgomez Date 2011-01-10 Time 16:02 Sent To  
Notes
2011-01-10 16:03:49NEED A/C CONTRACTOR TO APPLY FOR PERMIT.

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-01-10 Cont ID  
Sent By jgomez Date 2011-01-10 Time 16:04 Rev Time 0.00
Received By jgomez Date 2011-01-10 Time 16:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-01-13 Cont ID  
Sent By astelly Date 2011-01-13 Time 16:54 Rev Time 0.00
Received By astelly Date 2011-01-13 Time 16:54 Sent To  
Notes
***NONE***