Plan Review Details - Permit 10120530
Plan Review Stops For Permit 10120530
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By jwitmer Date 2011-01-20 Time 11:50 Rev Time 0.77
Received By jwitmer Date 2011-01-20 Time 11:45 Sent To  
Notes
2011-01-20 11:47:54 
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 DOOR 1815: REQUIRES 18" CLEAR LATCH SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-06 Cont ID  
Sent By jwitmer Date 2011-01-06 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2011-01-04 Time 14:36 Sent To  
Notes
2011-01-04 15:37:44BUILDING PLAN REVIEW
 PERMIT:10120530
 ADD: 250 S AUSTRALIAN AV# 1800
 CONT: PAVARIN INT.
 TEL: (954)903-3700
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET LS1.0 PLANS INDICATE CARD READERS WITH IN THE
 STAIRS PLEASE REVIEWFBC-B 1020.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 2) ELEVATOR LOBBIES VERSES CARD READERS. PLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE CARD READERS AND
 COMPLIANCE WITH FBC-B 707.14.1 ELEVATOR LOBBIES SHALL
 HAVE AT LEAST ONE MEANS OF EGRESS COMPLYING WITH
 CHAPTER 10 AND OTHER PROVISIONS WITHIN THIS CODE.
  
 3) PLEASE PROVIDE DOCUMENTATION ON CARD READERS AND
 ELECTRIC LOCKS THAT THEY MEET TTHE REQUIREMENTS OF FBC
 1008.1.3.4.
  
 4) PLEASE REVIEW LS-1.0 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITHIN
 THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 5) SHEET A-1.1 GLAZED OPENINGS WITHIN WALLS: 2406.3
 HAZARDOUS LOCATIONS. THE FOLLOWING SHALL BE CONSIDERED
 SPECIFIC HAZARDOUS LOCATIONS REQUIRING SAFETY GLAZING
 MATERIALS: 6.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE
 PANEL ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE
 OF THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF
 EITHER VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION
 AND WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS
 LESS THAN 60 INCHES (1524 MM) ABOVE THE WALKING
 SURFACE.
  
 6) SHEET A-4.0 RECEPTION DESK SECTION TO COMPLY WITH
 ACCESSIBILITY REQUIREMENTS:
  
 11-7.2 (2) AT TICKETING COUNTERS, TELLER STATIONS IN A
 BANK, REGISTRATION COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS, AND OTHER COUNTERS THAT MAY NOT
 HAVE A CASH REGISTER BUT AT WHICH GOODS OR SERVICES ARE
 SOLD OR DISTRIBUTED, EITHER:
  
 (I) A PORTION OF THE MAIN COUNTER WHICH IS A MINIMUM OF
 36 INCHES (915 MM) IN LENGTH SHALL BE PROVIDED WITH A
 MAXIMUM HEIGHT OF 36 INCHES (915 MM); OR
  
 (II) AN AUXILIARY COUNTER WITH A MAXIMUM HEIGHT OF 36
 IN (915 MM) IN CLOSE PROXIMITY TO THE MAIN COUNTER
 SHALL BE PROVIDED; OR
  
 (III) EQUIVALENT FACILITATION SHALL BE PROVIDED (E.G.,
 AT A HOTEL REGISTRATION COUNTER, EQUIVALENT
 FACILITATION MIGHT CONSIST OF:
  
 (1) PROVISION OF A FOLDING SHELF ATTACHED TO THE MAIN
 COUNTER ON WHICH AN INDIVIDUAL WITH DISABILITIES CAN
 WRITE, AND
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By rlecky Date 2011-01-20 Time 14:52 Rev Time 0.00
Received By rlecky Date 2011-01-20 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-07 Cont ID  
Sent By rlecky Date 2011-01-07 Time 14:08 Rev Time 0.00
Received By rlecky Date 2011-01-07 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-27 Cont ID  
Sent By mcarsill Date 2011-01-27 Time 13:36 Rev Time 0.00
Received By mcarsill Date 2011-01-27 Time 13:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-05 Cont ID  
Sent By mcarsill Date 2011-01-05 Time 10:54 Rev Time 0.00
Received By mcarsill Date 2011-01-05 Time 10:46 Sent To  
Notes
2011-01-05 10:54:34250 AUSTRALIAN AVENUE
 PERMIT NUMBER 10120530
  
  
 1. CARD READERS NOTED IN ELEVATORS, EXISTING WEST
 STAIR, AND EXISTING EAST VESTIBULE FOR EXIT STAIR. CARD
 READERS ARE NOT TO INTERFERE WITH EXITING. ACCORDING TO
 BUILDING AND FIRE CODES AT LEAST ONE EXIT IS TO BE
 ACCESSIBLE FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA
 FIRE PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD
 READERS ARE NOT ALLOWED IN STAIRWELLS. PLEASE SEE
 FLORIDA FIRE PREVENTION CODE, NFPA 101, SECTION
 7.2.1.6.1 (6)
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. NOTE # 17 IS INCORRECT ON PAGE E0.1. DUCT DETECTORS
 WHEN ACTIVATED SHALL CAUSE AN ALARM NOT A SUPERVISORY
 SIGNAL.
  
 4. EXIT SIGNS APPEAR TO BE MISSING FROM SHEET E3.1.
  
 5. IT APPEARS THAT ADDITIONAL FIRE ALARM DEVICES ARE
 NEEDED ON SHEET E3.1.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-19 Cont ID  
Sent By rregueir Date 2011-01-19 Time 10:17 Rev Time 0.00
Received By rregueir Date 2011-01-19 Time 10:13 Sent To  
Notes
2011-01-19 10:13:40**DIGITAL PLANS** SEE PROJECTDOX AND C-45 ON THE
 SPREADSHEET.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-01-12 Time   Rev Time 0.00
Received By rregueir Date 2010-12-21 Time 10:53 Sent To  
Notes
2010-12-22 10:54:15**DIGITAL PLANS** SEE PROJECTDOX AND C-45 ON THE
 SPREADSHEET.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-24 Cont ID  
Sent By rregueir Date 2011-01-21 Time 11:43 Rev Time 0.00
Received By rregueir Date 2011-01-21 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-12 Cont ID  
Sent By rregueir Date 2011-01-12 Time 09:03 Rev Time 0.00
Received By rregueir Date 2011-01-12 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-01-25 Cont ID  
Sent By lwagner Date 2011-01-25 Time 08:02 Rev Time 0.00
Received By lwagner Date 2011-01-25 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-01-12 Cont ID  
Sent By lwagner Date 2011-01-12 Time 10:59 Rev Time 0.00
Received By lwagner Date 2011-01-12 Time 10:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2011-01-24 Time 11:44 Sent To  
Notes
2011-01-28 11:20:44OK TO PASS PER R REGUEIRO (SIGNATURE DOCUMENTS
 SUBMITTED)

Review Stop Z ZONING
Rev No 1 Status N Date 2011-01-04 Cont ID  
Sent By aaponte Date 2011-01-04 Time 11:13 Rev Time 0.00
Received By aaponte Date 2011-01-04 Time 11:13 Sent To  
Notes
***NONE***