Plan Review Details - Permit 10120529
Plan Review Stops For Permit 10120529
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By jwitmer Date 2011-01-20 Time 11:03 Rev Time 0.55
Received By jwitmer Date 2011-01-20 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-04 Cont ID  
Sent By jwitmer Date 2011-01-04 Time 14:12 Rev Time 0.77
Received By jwitmer Date 2011-01-04 Time 12:52 Sent To  
Notes
2011-01-04 14:11:31BUILDING PLAN REVIEW
 PERMIT:10120529
 ADD: 250 S AUSTRALIAN AV# 1700
 CONT: PAVARIN INT.
 TEL: (954)903-3700
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET LS1.0 PLANS INDICATE CARD READERS WITH IN THE
 STAIRS PLEASE REVIEWFBC-B 1020.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 2) ELEVATOR LOBBIES VERSES CARD READERS. PLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE CARD READERS AND
 COMPLIANCE WITH FBC-B 707.14.1 ELEVATOR LOBBIES SHALL
 HAVE AT LEAST ONE MEANS OF EGRESS COMPLYING WITH
 CHAPTER 10 AND OTHER PROVISIONS WITHIN THIS CODE.
  
 3) PLEASE PROVIDE DOCUMENTATION ON CARD READERS AND
 ELECTRIC LOCKS THAT THEY MEET TTHE REQUIREMENTS OF FBC
 1008.1.3.4.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By rlecky Date 2011-01-20 Time 15:05 Rev Time 0.00
Received By rlecky Date 2011-01-20 Time 14:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-04 Cont ID  
Sent By rlecky Date 2011-01-04 Time 15:44 Rev Time 0.00
Received By rlecky Date 2011-01-04 Time 15:15 Sent To  
Notes
2011-01-04 15:17:35PREVISO:
 PROVIDE ENGINEERED DETAIL FOR MOUNTING OF THE
 TRANSFORMER ABOVE THE CEILING.
  
 ROBERT LECKY, PLANS EXAMINER, 561-805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-25 Cont ID  
Sent By mcarsill Date 2011-01-25 Time 15:26 Rev Time 0.00
Received By mcarsill Date 2011-01-25 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-03 Cont ID  
Sent By mcarsill Date 2011-01-03 Time 16:15 Rev Time 0.00
Received By mcarsill Date 2011-01-03 Time 15:56 Sent To  
Notes
2011-01-03 16:15:37250 AUSTRALIAN AVENUE
 PERMIT NUMBER 10120529
  
  
 1. CARD READERS DISPLAYED IN ELEVATOR LOBBIES, WITHIN
 EXISTING WEST EXIT STAIR, AND THE EXISTING VESTIBULE
 FOR THE EXISTING EAST STAIR. CARD READERS SHALL NOT
 INTERFERE WITH EXITING. ACCORDING TO BUILDING AND FIRE
 CODE REQUIREMENTS, AT LEAST ONE EXIT STAIR SHALL BE
 ACCESSIBLE FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA
 FIRE PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD
 READERS ARE NOT ALLOWED TO BE INSTALLED IN EXIT
 STAIRWELLS. PLEASE SEE FLORIDA FIRE PREVENTION CODE,
 NFPA 101, SECTION 7.2.1.6.1 (6)
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. PLEASE DESCRIBE LOCKING ARRANGEMENTS BEING USED
 WITHIN THIS SINGLE TENANT SPACE. ARE THE DOORS FAIL
 SAFE OR FAIL SECURE WHEN THE FIRE ALARM SYSTEM IS NOT
 ACTIVATED.
  
 4. ON SHEET E-2.1 EXIT SIGNS ARE MISSING THAT WERE
 SHOWN ON THE LIFE SAFETY PLAN. THIS SHEET DOES NOT
 CORRESPOND.
  
 5. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 6. SHEET A1.5 INDICATES THE 18TH FLOOR. THIS SHEET IS
 FROM ANOTHER PROJECT.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR PRE-ACTION
 FIRE SPRINKLER SYSTEM.
  
 8. NOTE # 17 ON PAGE E0.1 IS INCORRECT. DUCT DETECTORS
 TO CAUSE AN ALARM NOT A SUPERVISORY SIGNAL.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-19 Cont ID  
Sent By rregueir Date 2011-01-19 Time 10:16 Rev Time 0.00
Received By rregueir Date 2011-01-19 Time 10:14 Sent To  
Notes
2011-01-19 10:15:39**DIGITAL PLANS** SEE PROJECTDOX AND C-44 ON THE
 SPREADSHEET.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-01-12 Time   Rev Time 0.00
Received By rregueir Date 2010-12-21 Time 10:53 Sent To  
Notes
2010-12-22 10:53:22**DIGITAL PLANS** SEE PROJECTDOX AND C-44 ON THE
 SPREADSHEET.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-12 Cont ID  
Sent By rregueir Date 2011-01-12 Time 08:54 Rev Time 0.00
Received By rregueir Date 2011-01-12 Time 08:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-01-12 Cont ID  
Sent By lwagner Date 2011-01-12 Time 10:14 Rev Time 0.00
Received By lwagner Date 2011-01-12 Time 10:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-01-07 Cont ID  
Sent By aaponte Date 2011-01-07 Time 12:51 Rev Time 0.00
Received By aaponte Date 2011-01-07 Time 12:51 Sent To  
Notes
***NONE***