Plan Review Details - Permit 10120509
Plan Review Stops For Permit 10120509
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By jwitmer Date 2011-01-20 Time 10:37 Rev Time 0.55
Received By jwitmer Date 2011-01-20 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-04 Cont ID  
Sent By jwitmer Date 2011-01-04 Time 14:21 Rev Time 1.20
Received By jwitmer Date 2011-01-04 Time 14:21 Sent To  
Notes
2011-01-04 14:20:58BUILDING PLAN REVIEW
 PERMIT:10120509
 ADD: 250 S AUSTRALIAN AV# 800
 CONT: PAVARIN INT.
 TEL: (954)903-3700
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET LS1.0 PLANS INDICATE CARD READERS WITH IN THE
 STAIRS PLEASE REVIEWFBC-B 1020.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 2) ELEVATOR LOBBIES VERSES CARD READERS. PLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE CARD READERS AND
 COMPLIANCE WITH FBC-B 707.14.1 ELEVATOR LOBBIES SHALL
 HAVE AT LEAST ONE MEANS OF EGRESS COMPLYING WITH
 CHAPTER 10 AND OTHER PROVISIONS WITHIN THIS CODE.
  
 3A) SHEET A-1.2 THE SERVER ROOM # 806. THE PLANS
 INDICATE THE WALS TO BE EXISTING, BUT IS THIS A TRUE IT
 ROOM REQUIRING 1 HOUR RATED WALLS PER NEC 645.4(5) ? IF
 THE WALLS REQUIRE THE FIRE RATING DO THE WALLS EXTEND
 UP ALL THE WAY TO THE DECK ABOVE?
  
 3B) IS THE RAISED FLOOR EXISTING OR NEW? IF NEW PLEASE
 PROVIDE DESIGN CRITERIA IN REGARDS TO FLOOR LOADING,
 LIVE LOADS, TYPE OF FLOOR SYSTEM AND FIRE RESISTANCE,
 IS THIS A PLASTIC TYPE OR COMPOSITE MATERIAL?
  
 3C) IF THE RAISED FLOORING IS NEW PLEASE PROVIDE
 INFORMATION ON THTE ACCESSIBLE RAMP,FBC-B 707.14.1
 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND OTHER PROVISIONS
 WITHIN THIS CODE. 11-4.8.4.(2) LANDINGS. THE BOTTOM OF
 EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 4) SHEET A-1.4 IT APPEARS THAT THERE IS WORK BEING
 COMPLETED OUTSIDE OF THE TENANT AREA, BUT WITHIN THE
 COMMON AREAS?
  
 5) SHEET A-1.5 IT APPEARS THIS SHEET WAS MISTAKENLY
 APPLIED TO THIS PROJECT, PLANS INDICATE 18TH FLOOR
 EQUIPMENT PLAN.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-01-20 Cont ID  
Sent By rlecky Date 2011-01-20 Time 15:18 Rev Time 0.00
Received By rlecky Date 2011-01-20 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-06 Cont ID  
Sent By rlecky Date 2011-01-06 Time 12:19 Rev Time 0.00
Received By rlecky Date 2011-01-06 Time 12:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-21 Cont ID  
Sent By mcarsill Date 2011-01-21 Time 10:30 Rev Time 0.00
Received By mcarsill Date 2011-01-21 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-04 Cont ID  
Sent By mcarsill Date 2011-01-04 Time 15:39 Rev Time 0.00
Received By mcarsill Date 2011-01-04 Time 15:30 Sent To  
Notes
2011-01-04 15:39:22250 AUSTRALIAN AVENUE
 PERMIT NUMBER 10120509
  
  
 1. CARD READERS DISPLAYED IN ELEVATOR LOBBIES WITHIN
 EXISTING WEST STAIR, AND THE EXISTING VESTIBULE FOR THE
 EXISTING EAST STAIR. CARD READERS SHALL NOT INTERFERE
 WITH EXITING. ACCORDING TO BUILDING AND FIRE CODE
 REQUIREMENTS, AT LEAST ONE STAIR SHALL BE ACCESSIBLE
 FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA FIRE
 PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD
 READERS ARE NOT TO BE INSTALLED IN THE EXIT STAIRWELLS.
 PLEASE SEE FLORIDA FIRE PREVENTION CODE, NFPA 101,
 SECTION 7.2.1.6.1.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. PLEASE DESCRIBE LOCKING ARRANGEMENTS BEING USED
 WITHIN THIS SINGLE TENANT SPACE. ARE DOORS FAIL SAFE OR
 FAIL SECURE WHEN THE FIRE ALARM SYSTEM IS NOT
 ACTIVATED.
  
 4. ON SHEET E2.1 EXIT SIGNS ARE MISSING THAT WERE SHOWN
 ON THE LIFE SAFETY PLAN. THIS SHEET DOES NOT
 CORRESPOND.
  
 5. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 6. SHEET A1.5 INDICATES THE 18TH FLOOR. PLAN SHEET DOES
 NOT CORRESPOND.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR PRE-ACTION
 FIRE SPRINKLER SYSTEM.
  
 8. NOTE # 17 ON PAGE E0.1 IS INCORRECT. DUCT DETECTORS
 TO CAUSE AN ALARM NOT A SUPERVISORY SIGNAL.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-19 Cont ID  
Sent By rregueir Date 2011-01-19 Time 10:16 Rev Time 0.00
Received By rregueir Date 2011-01-19 Time 10:16 Sent To  
Notes
2011-01-19 10:16:40**DIGITAL PLANS** SEE PROJECTDOX AND C-43 ON THE
 SPREADSHEET.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-01-12 Time   Rev Time 0.00
Received By jwitmer Date 2010-12-21 Time 13:01 Sent To  
Notes
2010-12-22 10:52:09**DIGITAL PLANS** SEE PROJECTDOX AND C-43 ON THE
 SPREADSHEET.
2010-12-21 13:01:39PROJECT DOCS, INCOMING SEENT TO RON'S DESK. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-24 Cont ID  
Sent By rregueir Date 2011-01-24 Time 08:39 Rev Time 0.00
Received By rregueir Date 2011-01-24 Time 08:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-12 Cont ID  
Sent By rregueir Date 2011-01-12 Time 08:43 Rev Time 0.00
Received By rregueir Date 2011-01-12 Time 08:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-12-28 Cont ID  
Sent By lwagner Date 2010-12-28 Time 13:40 Rev Time 0.00
Received By lwagner Date 2010-12-28 Time 12:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-01-24 Cont ID  
Sent By rregueir Date 2011-01-24 Time 15:52 Rev Time 0.00
Received By rregueir Date 2011-01-24 Time 11:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-01-07 Cont ID  
Sent By aaponte Date 2011-01-07 Time 12:52 Rev Time 0.00
Received By aaponte Date 2011-01-07 Time 12:52 Sent To  
Notes
***NONE***