Plan Review Details - Permit 10120502
Plan Review Stops For Permit 10120502
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-03-14 Cont ID  
Sent By shill Date 2011-03-14 Time 09:53 Rev Time 0.00
Received By shill Date 2011-03-14 Time 09:53 Sent To  
Notes
2011-03-14 09:54:24PROVISO - NO DOORS INCLUDED IN SCOPE
 (ASSEMBLY OCCUPANCY PER CONTRACTOR, SOUP KITCHEN)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-02-15 Cont ID  
Sent By shill Date 2011-02-15 Time 09:22 Rev Time 0.00
Received By shill Date 2011-02-15 Time 09:22 Sent To  
Notes
2011-02-15 09:50:00****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS REVIEWS:
  
 1. REVISE PLAN TO SHOW TYPE OF OPENING (DOOR OR
 WINDOW), FBC1003.6. IF YOU PROPOSE TO COVER REQUIRED
 EXIT DOORS WITH SHUTTERS, PROVIDE A LIFE SAFETY PLAN
 WHICH SHOWS THE FOLLOWING INFORMATION:
  
 OVERALL BUILDING DIMENSIONS
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3
 EXITING INFORMATION
  
 3RD REVIEW, PLEASE PROVIDE REQUESTED INFORMATION.
 OCCUPANCY CLASSIFICATION NOT PROVIDED, OVERALL
 DIMENSIONS NOT PROVIDED, THEREFORE OCCUPANT LOAD CANNOT
 BE DETERMINED. PLAN PROVIDED SHOWS TWO DOORS, ONE
 OUTSWING DOOR COVERED BY PANELS, NO OTHER INFORMATION.
 THIS DOES NOT APPEAR TO COMPLY WITH THE REQUIREMENTS OF
 FBC CHAPTER 10. EITHER REVISE PLAN TO SHOW COMPLIANCE
 WITH FBC CHAPTER 10 (MEANS OF EGRESS) OR REMOVE DOOR
 FROM SCOPE OF WORK.
  
 2. ADDRESSED.
  
 3. PLEASE SEE INSTALLATION SCHEDULE SUBMITTED, OPENING
 4 AND SHEET 4 OF THE PRODUCT APPROVAL. SPACING PROPOSED
 DOES NOT COMPLY FOR THIS PANEL SPAN. PLEASE REVISE AND
 CHECK ALL.
  
 4. ADDRESSED.
  
  
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-01-31 Cont ID  
Sent By shill Date 2011-01-31 Time 09:14 Rev Time 0.00
Received By shill Date 2011-01-31 Time 09:14 Sent To  
Notes
2011-01-31 09:14:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE PLAN TO SHOW TYPE OF OPENING (DOOR OR
 WINDOW), FBC1003.6. IF YOU PROPOSE TO COVER REQUIRED
 EXIT DOORS WITH SHUTTERS, PROVIDE A LIFE SAFETY PLAN
 WHICH SHOWS THE FOLLOWING INFORMATION:
  
 OVERALL BUILDING DIMENSIONS
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3
 EXITING INFORMATION
  
 2. ADDRESSED.
  
 3. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 4. ADDRESSED.
  
  
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-22 Cont ID  
Sent By shill Date 2010-12-22 Time 17:44 Rev Time 0.00
Received By shill Date 2010-12-22 Time 17:44 Sent To  
Notes
2010-12-22 18:04:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE PLAN TO SHOW TYPE OF OPENING (DOOR OR
 WINDOW), FBC1003.6. IF YOU PROPOSE TO COVER REQUIRED
 EXIT DOORS WITH SHUTTERS, PROVIDE A LIFE SAFETY PLAN
 WHICH SHOWS THE FOLLOWING INFORMATION:
  
 OVERALL BUILDING DIMENSIONS
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3
 EXITING INFORMATION
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQURIED,
 FAC9B72. THE PRODUCT APPROVALS SUBMITTED ARE EXPIRED.
  
 3. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 4. WHEN RESUBMITTING, PLEASE SUBMIT TWO COMPLETE SETS
 OF PERMIT DOCUMENTS.
  
  
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2011-03-14 Cont ID  
Sent By shill Date 2011-03-14 Time 09:54 Rev Time 0.00
Received By shill Date 2011-03-14 Time 09:54 Sent To  
Notes
2011-03-07 14:29:45SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-02-08 Cont ID  
Sent By rlecky Date 2011-02-08 Time 11:50 Rev Time 0.00
Received By rlecky Date 2011-02-08 Time 11:50 Sent To  
Notes
2011-02-08 11:51:07REVISIONS TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-19 Cont ID  
Sent By lmartine Date 2011-01-19 Time 10:25 Rev Time 0.00
Received By lmartine Date 2011-01-19 Time 10:25 Sent To  
Notes
2011-01-19 10:26:33GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By shill Date 2010-12-22 Time 18:04 Rev Time 0.00
Received By shill Date 2010-12-22 Time 10:03 Sent To  
Notes
***NONE***