Plan Review Details - Permit 10120485
Plan Review Stops For Permit 10120485
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-05-06 Cont ID  
Sent By rmcdouga Date 2011-05-06 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2011-05-06 Time 09:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 12:25 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 12:10 Sent To  
Notes
2011-04-27 12:31:24DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOW AS REQUIRED BY DCA RULE 9B-72.
  
 2) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS, IF
 THE NEW WINDOW IS NOT IMPACT RESISTANT.
  
 3) PLEASE CLARIFY WHETHER OR NOT THE DOUBLE OUTSWING
 ENTRY DOOR AND SIDELITES ARE BEING REPLACED. IF IT IS
 BEING REPLACED, SUBMIT PRODUCT APPROVALS FOR IT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-01-10 Time 10:46 Rev Time 0.00
Received By rmcdouga Date 2011-01-10 Time 08:27 Sent To  
Notes
2011-01-10 10:18:02DENIED BY BUILDING
 2007 FBC W/2009 REVISIONS
  
 1) AN IMPACT FEE PLAN REVIEW BY PALM BEACH COUNTY WILL
 BE REQUIRED. THE PLANS WILL BE STAMPED BY THE COUNTY.
 IF ANY FEES ARE DUE A COPY OF THE PAID RECEIPT ALONG
 WITH THE STAMPED PLANS SHALL BE SUBMITTED TO THE CITY
 OF WEST PALM CONSTRUCTION SERVICES DEPARTMENT.
  
 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND
 THE PLANS SPECIFY CATEGORY B. PLEASE REVISE AND
 INCREASE THE COMPONENT AND CLADDING PRESSURES
 ACCORDINGLY. SEE 2007 FBC RESIDENTIAL WITH 2009
 REVISIONS SECTION R301.2.1.4.3.
  
 3) THE WALL SECTION ON SHEET 2 DOES NOT SHOW THE
 FOUNDATION WEEP SCREED. ASTM C 1063 SECTION 7.11.5
 REQUIRES A FOUNDATION WEEP SCREED AT THE BOTTOM OF ALL
 STUCCO COVERED FRAMED EXTERIOR WALLS BELOW THE FLOOR
 LINE. FBC R703.6
  
 4) SUBMIT PRODUCT APPROVALS FOR THE NEW SINGLE HUNG
 WINDOW IN THE FAMILY ROOM. DCA RULE 9B-72.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE HURRICANE PANELS
 FOR THE NEW WINDOW (UNLESS IT IS A LARGE MISSILE IMPACT
 WINDOW). DCA RULE 9B-72.
  
 6) THE VALUE OF THE WORK APPEARS TO BE TOO LOW. THE
 VALUE IS TO INCLUDE THE COSTS OF ALL LABOR, MATERIALS,
 DESIGN COSTS, OVERHEAD AND PROFIT AS WOULD BE CHARGED
 BY A CONTRACTOR. PLEASE PROVIDE A COST BREAK DOWN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 11:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-01-10 Cont ID  
Sent By rmcdouga Date 2011-01-10 Time 10:54 Rev Time 0.00
Received By rmcdouga Date 2011-01-10 Time 10:46 Sent To  
Notes
2011-01-10 10:53:35DENIED BY ELECTRIC
 2008 NEC AND 2007 FBC W/2009 REVISIONS
  
 1) UPDATE THE ELECTRICAL DESIGN CRITERIA ON SHEET 2 TO
 REFERENCE THE 2007 FBC W/2009 REVISIONS AND THE 2008
 NEC.
  
 2) THE CODE SECTION FOR SMOKE ALARMS IN THE 2007 FBC
 RESIDENTIAL IS R313.2.1. PLEASE UPDATE THE CODE
 REFERENCE ON SHEET 2.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-05-06 Cont ID  
Sent By rmcdouga Date 2011-05-06 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2011-05-02 Time 17:41 Sent To  
Notes
2011-05-02 17:41:35TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-28 Cont ID  
Sent By rmcdouga Date 2011-04-28 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2011-04-21 Time 14:08 Sent To  
Notes
2011-04-21 14:08:59GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-01-10 Time 10:54 Rev Time 0.00
Received By rmcdouga Date 2011-01-10 Time 10:54 Sent To  
Notes
2011-01-10 10:55:03NEEDS PBC IMPACT FEE REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-04-27 Cont ID  
Sent By rmcdouga Date 2011-04-27 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2011-04-27 Time 10:57 Sent To  
Notes
2011-04-27 10:58:36MU-2011-003738-0000

Review Stop Z ZONING
Rev No 2 Status P Date 2011-04-28 Cont ID  
Sent By eschneid Date 2011-04-28 Time 09:11 Rev Time 0.25
Received By eschneid Date 2011-04-28 Time 09:11 Sent To  
Notes
2011-04-28 09:11:24RESTAMP

Review Stop Z ZONING
Rev No 1 Status P Date 2010-12-29 Cont ID  
Sent By eschneid Date 2010-12-28 Time 09:31 Rev Time 0.75
Received By eschneid Date 2010-12-28 Time 09:31 Sent To  
Notes
2010-12-29 12:02:31NO EXPANSION OF FOOTPRINT. LESS THAN 50% VALUE OF
 STRUCTURE.