Plan Review Details - Permit 10120477
Plan Review Stops For Permit 10120477
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-19 Cont ID  
Sent By jwitmer Date 2011-01-19 Time 10:40 Rev Time 1.33
Received By jwitmer Date 2011-01-19 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-28 Cont ID  
Sent By jwitmer Date 2010-12-28 Time 14:41 Rev Time 0.77
Received By jwitmer Date 2010-12-28 Time 14:23 Sent To  
Notes
2010-12-28 14:41:45BUILDING PLAN REVIEW
 PERMIT: 10120477
 ADD: 505 38TH ST
 CONT: MARK STEFFAN GROUP
 TEL: (954)479-0171
 FL BLD CODE= 2007 FLORIDA BUILDING CODE- RESIDENTIAL
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE CORRECT COVERSHEET EXPOSURE TO "C":
 R301.2.1.4(3) EXPOSURE C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER
 IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M)
 FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE
 SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN
 EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN
 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF
 EXPOSURE C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET
 (182.9 M) AND WIDTH GREATER THAN 150 FEET IN THE UPWIND
 DIRECTION.
  
 2) PLEASE PROVIDE WIND PRESSURES FOR NEW WINDOWS AND
 DOORS INCLUDE ADJUSTMENT FACTORS FOR EXPOSURE "C". 2007
 FBC-R TABLE R301.2(2) & TABLE R301.2(3).
  
 3) PLEASE PROVIDE PRODUCT APPROVALS REQUIRED BY RULE
 9N-3 (FORMERLY RULE 9B-72) COMPONENTS AND CLADDING &
 PROTECTION OF ALL OPENINGS:
 3A) WINDOWS
 3B) STORM SHUTTERS IF NEW WINDOWS DO NOT HAVE LARGE
 MISSILE TESTING
 3C) EXTERIOR DOORS
  
 4) IF STORM SHUTTERS ARE ELECTED TO BE INSTALLED
 INSTEAD OF MISSILE IMPACT WINDOWS THEN PLEASE PROVIDE
 STORM PANEL INFORMATION WITH INSTALLATION SCHEDULE AND
 KEY PLAN WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING. FBC 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-01-24 Cont ID  
Sent By rlecky Date 2011-01-24 Time 13:05 Rev Time 0.00
Received By rlecky Date 2011-01-24 Time 12:53 Sent To  
Notes
2011-01-24 13:04:01PROVISO:
  
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-12-27 Cont ID  
Sent By rlecky Date 2010-12-27 Time 14:53 Rev Time 0.00
Received By rlecky Date 2010-12-27 Time 12:42 Sent To B
Notes
2010-12-27 14:53:00BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC
 210.12
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
 TAMPER -RESISTANCE RECEPTACLES REQUIRED. NEC 406.11,
 210.52
 PROVIDE A RISER DIAGRAM. INDICATE THE SIZE OF THE
 EXISTING SERVICE, FEEDERS AND MAIN DISCONNECT.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-01-18 Cont ID  
Sent By jpapa Date 2011-01-18 Time 11:40 Rev Time 0.00
Received By jpapa Date 2011-01-18 Time 11:40 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2010-12-20 Cont ID  
Sent By jpapa Date 2010-12-20 Time 10:52 Rev Time 0.00
Received By jpapa Date 2010-12-20 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-12 Cont ID  
Sent By jgomez Date 2011-01-12 Time 14:53 Rev Time 0.00
Received By jgomez Date 2011-01-12 Time 14:53 Sent To  
Notes
2011-01-12 14:53:41SENT TO R4.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-28 Cont ID  
Sent By jwitmer Date 2010-12-28 Time 14:42 Rev Time 0.00
Received By jwitmer Date 2010-12-20 Time 07:48 Sent To  
Notes
2010-12-21 07:51:23TO ELECTRIC BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2010-12-20 Cont ID  
Sent By jpapa Date 2010-12-20 Time 10:53 Rev Time 0.00
Received By jpapa Date 2010-12-20 Time 10:53 Sent To  
Notes
***NONE***