| 2010-12-28 14:41:45 | BUILDING PLAN REVIEW |
| | PERMIT: 10120477 |
| | ADD: 505 38TH ST |
| | CONT: MARK STEFFAN GROUP |
| | TEL: (954)479-0171 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE- RESIDENTIAL |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE CORRECT COVERSHEET EXPOSURE TO "C": |
| | R301.2.1.4(3) EXPOSURE C. OPEN TERRAIN WITH SCATTERED |
| | OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS OR OTHER |
| | IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS THAN 30 |
| | FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET (457.2 M) |
| | FROM THE BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE |
| | SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN |
| | EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| | 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF |
| | EXPOSURE C-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET |
| | (182.9 M) AND WIDTH GREATER THAN 150 FEET IN THE UPWIND |
| | DIRECTION. |
| | |
| | 2) PLEASE PROVIDE WIND PRESSURES FOR NEW WINDOWS AND |
| | DOORS INCLUDE ADJUSTMENT FACTORS FOR EXPOSURE "C". 2007 |
| | FBC-R TABLE R301.2(2) & TABLE R301.2(3). |
| | |
| | 3) PLEASE PROVIDE PRODUCT APPROVALS REQUIRED BY RULE |
| | 9N-3 (FORMERLY RULE 9B-72) COMPONENTS AND CLADDING & |
| | PROTECTION OF ALL OPENINGS: |
| | 3A) WINDOWS |
| | 3B) STORM SHUTTERS IF NEW WINDOWS DO NOT HAVE LARGE |
| | MISSILE TESTING |
| | 3C) EXTERIOR DOORS |
| | |
| | 4) IF STORM SHUTTERS ARE ELECTED TO BE INSTALLED |
| | INSTEAD OF MISSILE IMPACT WINDOWS THEN PLEASE PROVIDE |
| | STORM PANEL INFORMATION WITH INSTALLATION SCHEDULE AND |
| | KEY PLAN WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. FBC 1609.1.4. |
| | |
| | FL BLD CODE 2004 SECTION 106.3.3, |
| | 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY |
| | HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT |
| | STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT |
| | TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT |
| | APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. |
| | |