Plan Review Details - Permit 10120470
Plan Review Stops For Permit 10120470
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-19 Cont ID  
Sent By shill Date 2011-01-19 Time 15:09 Rev Time 0.00
Received By shill Date 2011-01-19 Time 15:09 Sent To  
Notes
2011-01-19 15:11:14PROVISOS
 REVISION REQUIRED
  
 1. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 708.1,
 TENANT SEPARATION.
  
 2. SPECIFY DESIGN PRESSURE FOR SOFFIT GRILL AND SUBMIT
 PRODUCT APPROVAL
  
 3. BLOCKING TO BE FRT OR METAL
  
 4. AREA ABOVE CEILING IS NOT A RETURN AIR PLENUM FBC M
 601.5.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-27 Cont ID  
Sent By shill Date 2010-12-27 Time 09:53 Rev Time 0.00
Received By shill Date 2010-12-27 Time 09:53 Sent To  
Notes
2010-12-27 10:14:11****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A ROOM DESIGNATION FOR THE AREA ADJACENT TO
 THE PROPOSED NEW RESTROOM 100. SEE FBC 708.1(7), IT
 APPEARS THAT A FIRE PARTITION IS REQUIRED BUT WALL TYPE
 W1 IS NOT A RATED WALL.
  
 2. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE EXHAUST GRILL, FAC9B72.
  
 3. REVISE PLAN TO INCLUDE DESIGN PRESSURES FOR THE
 SOFFIT EXHAUST GRILL, FBC1609.1, ALL EXTERIOR SOFFITS
 SHALL BE CAPABLE OF RESISTING THE DESIGN PRESSURES
 SPECIFIED FOR COMPONENTS AND CLADDING LOADS.
  
 4. PROVIDE A BLOCKING DETAIL OR SPECIFICATION, SEE FBC
 602.2, 603. DESIGN INTENT IS NOT CLEAR; PLEASE NOTE
 THAT THIS IS A NONCOMBUSTIBLE BUILDING AND NO
 INFORMATION PROVIDED REGARDING THE BLOCKING REFERRED TO
 IN RESTROOM ACCESSORIES NOTE, SHEET A1.1.
  
 5. PLEASE NOTE THAT, IF ALL OTHER TRADES PASS REVIEW,
 THIS REVIEW CAN BE PASSED WITH PROVISO UPON DESIGNER'S
 REQUEST.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-03 Cont ID  
Sent By rlecky Date 2011-01-03 Time 11:29 Rev Time 0.00
Received By rlecky Date 2011-01-03 Time 09:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-29 Cont ID  
Sent By mcarsill Date 2010-12-29 Time 13:54 Rev Time 0.00
Received By mcarsill Date 2010-12-29 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-03 Cont ID  
Sent By lmartine Date 2011-01-03 Time 12:12 Rev Time 0.00
Received By lmartine Date 2010-12-20 Time 15:22 Sent To  
Notes
2010-12-20 15:26:58****************EXPEDITED*******************
 B--19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-06 Cont ID  
Sent By shill Date 2011-01-06 Time 10:42 Rev Time 0.00
Received By shill Date 2011-01-06 Time 10:42 Sent To  
Notes
2011-01-06 11:14:44***PROVISO***
  
 PER ARCHITECT, EXHAUST DUCT DOES NOT PASS THROUGH A
 RETURN AIR PLENUM. PER ARCHITECT, SERVICE CORRIDOR IS
 NOT CONDITIONED.
  
  
  
 OK PER HM
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-12-27 Cont ID  
Sent By hmoser Date 2010-12-27 Time 12:00 Rev Time 0.00
Received By hmoser Date 2010-12-27 Time 11:59 Sent To  
Notes
2010-12-27 11:51:19***CORRECTIONS***
  
 1. FBC MECHANICAL 601.5, EXHAUST DUCTS SHALL NOT PASS
 THROUGH PLENUMS. PLEASE ADVISE OR REVISE PLAN
 ACCORDINGLY.
  
 THIS REVIEW CAN BE PASSED WITH PROVISO UPON REQUEST
 FROM ENGINEER.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-12-27 Cont ID  
Sent By lwagner Date 2010-12-27 Time 10:01 Rev Time 0.00
Received By lwagner Date 2010-12-22 Time 08:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-27 Cont ID  
Sent By jroach Date 2010-12-27 Time 15:53 Rev Time 0.00
Received By jroach Date 2010-12-27 Time 15:53 Sent To  
Notes
***NONE***