Plan Review Details - Permit 10120466
Plan Review Stops For Permit 10120466
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-29 Cont ID  
Sent By jwitmer Date 2010-12-29 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2010-12-29 Time 11:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-22 Cont ID  
Sent By jwitmer Date 2010-12-22 Time 11:54 Rev Time 0.50
Received By jwitmer Date 2010-12-22 Time 11:54 Sent To  
Notes
2010-12-22 11:56:38BUILDING PLAN APPEAR TO BE CODE COMPLIANT, EACH OF THE
 TRADES NEED THE QUALIFIER TO SIGN AND APPLY THEIR
 LICENSE NUMBER TO THE PLANS. JW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-12-29 Cont ID  
Sent By rlecky Date 2010-12-29 Time 10:54 Rev Time 0.00
Received By rlecky Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-12-20 Cont ID  
Sent By rlecky Date 2010-12-20 Time 09:14 Rev Time 0.00
Received By rlecky Date 2010-12-20 Time 08:35 Sent To  
Notes
2010-12-20 09:14:33LOCATE SMOKE DETECTORS ON THE PLAN. INDICATE THEY ARE
 TO BE INTERCONNECTED. FBC 907.2.10
 SHOW LOCATION OF EXISTING PANEL BOARD. PROVIDE SIZE AND
 RATING OF THE NEW PANEL BOARD. SHOW EXISTING SERVICE
 WIRE SIZE AND OVERCURRENT PROTECTION PROVIDED AT THE
 MAIN SERVICE DISTRIBUTION. PROVIDE A PANEL SCHEDULE
 SHOWING ALL CIRCUITS NEW AND EXISTING WITH CIRCUIT
 BREAKERS AND WIRE SIZES. NEC 210.2, 230.3, 240.4
  
 ROBERT LECKY, PLANS EXAMINER, 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-29 Cont ID  
Sent By mcarsill Date 2010-12-29 Time 14:39 Rev Time 0.00
Received By mcarsill Date 2010-12-29 Time 14:38 Sent To  
Notes
2010-12-29 14:40:47SMOKE ALARMS ARE TO BE TESTED TO ENSURE PROPER
 OPERATION. THEY SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. PLANS
 INDICATE THEY WILL BE INTERCONNECTED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-06 Cont ID  
Sent By shill Date 2011-01-06 Time 08:58 Rev Time 0.00
Received By shill Date 2010-12-20 Time 11:39 Sent To  
Notes
2010-12-20 11:39:54B18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-01-10 Cont ID  
Sent By shill Date 2011-01-10 Time 08:07 Rev Time 0.00
Received By shill Date 2011-01-10 Time 08:07 Sent To  
Notes
2011-01-10 08:07:14OK PER HM
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-06 Cont ID  
Sent By hmoser Date 2011-01-06 Time 11:10 Rev Time 0.00
Received By hmoser Date 2011-01-06 Time 11:10 Sent To  
Notes
2011-01-06 08:58:161. THE NAME OF THE DESIGNER OF THE PLAN, DAVID
 HUTCHISON, DOES NOT MATCH THE LICENSE NUMBER OF THE
 PLAN (CAC1814987). PLANS ARE TO BE PREPARED BY AN
 INDIVIDUAL LICENSED TO DESIGN THIS SCOPE OF WORK,
 FLORIDA STATUTE 471, FS481, FS489.
  
 2. COMBUSTIBLES NOT PERMITTED IN A RETURN AIR PLENUM,
 FBC MECHANICAL 602.2.1.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-12-30 Cont ID  
Sent By lwagner Date 2010-12-30 Time 14:15 Rev Time 0.00
Received By lwagner Date 2010-12-30 Time 14:15 Sent To  
Notes
2010-12-30 14:16:01ISO ADDED TO PLANS

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-27 Cont ID  
Sent By lwagner Date 2010-12-27 Time 10:21 Rev Time 0.00
Received By lwagner Date 2010-12-27 Time 08:39 Sent To  
Notes
2010-12-27 10:21:35FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 PAGE 5 OF SCOPE INDICATES RUNNING A 3" WASTE LINE AND
 WATER LINES.
 FBC 106.3.5.1.3 MINIMUM CRITERIA PLUMBING RISER DIAGRAM
 REQUIRED.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-20 Cont ID  
Sent By jroach Date 2010-12-20 Time 13:09 Rev Time 0.00
Received By jroach Date 2010-12-20 Time 13:09 Sent To  
Notes
***NONE***