Plan Review Details - Permit 10120450
Plan Review Stops For Permit 10120450
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-04-21 Cont ID  
Sent By jwitmer Date 2011-04-21 Time 08:24 Rev Time 1.20
Received By jwitmer Date 2011-04-21 Time 08:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-04-18 Cont ID  
Sent By jwitmer Date 2011-04-18 Time 14:05 Rev Time 0.77
Received By jwitmer Date 2011-04-18 Time 14:03 Sent To  
Notes
2011-04-18 14:05:06PLANS APPEAR TO BE CODE COMPLIANT WILL BE STAMPED ONCE
 A CONTRACTOR HAS SUBMITTED A PERMIT APPLICATION AND
 CONTRACTOR LICENSURE HAS BEEN VERIFIED. J WITMER
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-10 Cont ID  
Sent By jwitmer Date 2011-01-10 Time 14:19 Rev Time 0.77
Received By jwitmer Date 2011-01-10 Time 13:00 Sent To  
Notes
2011-01-10 14:50:10BUILDING PLAN REVIEW
 PERMIT: 10120450
 ADD: 1800 CENTREPARK DRIVE EAST/ GROUND FLOOR
 CONT: TO BE DETERMINED
 TEL: (954)914-9848
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COVER SHEET CS INDICATES THE MINIMUM BUILDING TYPE
 AS A TYPE V NO CHANGE, PLEASE REVIEW FBC-B TABLE 503,
 THE MINIMUM BUILDING TYPE CAN BE A TYPE IIA WITH A
 HEIGHT INCREASE OF ONE STORY IF INSTALLED IN ACCORDANCE
 WITH 903.3.1.1, NFPA 13, NOT A 13-R.
  
 2) NEITHER THE LIFE SAFETY PLAN NOR A-111 LOBBY FLOOR
 PLAN PROVIDE PLANS WITH RATED WALLS AND IDENTIFYING
 DOORS AND REQUIRED RATINGS
 THE BUILDING CODE THIS BUILDING WAS BUILT UNDER AS WELL
 AS TODAY'S CODE REQUIRES THE CORRIDORS TO BE ONE HOUR
 FIRE RATING THROUGH THE LOBBY TO THE EXIT DISCHARGE
 (FRONT DOORS). PLEASE SEE FBC-B TABLE 1017.1 REQUIRING
 A 1 HOUR CORRIDOR FOR A-2, A-3 AND R-1 OCCUPANCIES.
 SECTION 1014.2 DOES ALLOW FOR EGRESS THROUGH
 INTERVENING ROOMS PROVIDED SUCH ADJOINING ROOMS OR
 AREAS ARE NOT A HIGHER HAZARD OCCUPANCY AND PROVIDE A
 DISCERNIBLE PATH OF EGRESS TRAVEL TO AN EXIT. PLEASE
 PROVIDE WHERE THE FIRE RATED WALLS WILL BE LOCATED,
 FIRE DAMPERS FOR RATED WALLS AND OPENING PROTECTIVES
 (RATED DOORS). PLEASE REVIEW EXCEPTION FOR KITHEN
 AREAS.
  
 3) PLEASE PROVIDE ADDITIONAL WORDING FOR FIRE RATED
 WALLS, FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 4) A-602 DOOR PLAN IDENTIFIES A FEW OF THE DOORS WITHIN
 THE FIRST FLOOR NOT ALL DOORS NOR DOES THE DOOR
 SCHEDULE INDICATE FIRE RATINGS.
 FBC-B TABLE 715.4 FOR REQUIRED OPENING PROTECTION
 RATINGS.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-04-06 Cont ID  
Sent By rlecky Date 2011-04-06 Time 12:49 Rev Time 0.00
Received By rlecky Date 2011-04-06 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-18 Cont ID  
Sent By rlecky Date 2011-01-18 Time 08:41 Rev Time 0.00
Received By rlecky Date 2011-01-14 Time 15:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-04-12 Cont ID  
Sent By wjolin Date 2011-04-12 Time 11:55 Rev Time 0.00
Received By wjolin Date 2011-04-12 Time 11:12 Sent To  
Notes
2011-04-12 11:50:561800 CENTREPARK DRIVE EAST
 PERMIT #10120450
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 PROVIDE TACTILE SIGNAGE AT EXITS.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE SPRINKLER,
 FIRE ALARM AND KITCHEN HOOD SUPPRESSION MODIFICATIONS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-28 Cont ID  
Sent By wjolin Date 2010-12-28 Time 13:32 Rev Time 0.00
Received By wjolin Date 2010-12-28 Time 10:18 Sent To  
Notes
2010-12-28 13:16:471800 CENTREPARK DRIVE EAST - GROUND FLOO
 PERMIT #10120450
 REVIEW COMMENTS - FIRE
  
 COVER SHEET
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 SHEET A-001
 THE REFERENCES TO THE INTERNATIONAL BUILDING CODE DO
 NOT APPLY TO THIS PROJECT.
  
 COMMON PATH OF TRAVEL AND EXIT ACCESS DISTANCES SHALL
 COMPLY WITH DISTANCES LISTED IN THE FLORIDA FIRE
 PREVENTION CODE.
  
 FIRE-RATED WALLS NOT SHOWN ON PLAN.
  
 EXIT SIGNAGE NOT SHOWN ON LIFE SAFETY PLAN.
  
 PROVIDE TACTILE SIGNAGE AT EXITS.
  
 SHOW PROPOSED LOCATIONS OF PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC.
  
 SHEET A-101
 DEMOLITION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA
 241.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 WORK.
  
 SHEET A-601
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER--PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. (REFERENCE: SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ??? NFPA 101)
  
 SHEET A-602
 DOOR SCHEDULE REFERENCES DETAILS THAT DO NOT EXIST ON
 SHEET A-601.
  
 SHEET E-111
 DEMOLITION WORK (WALL REMOVAL) MAY AFFECT FIRE ALARM
 DEVICE LOCATIONS. SEPARATE PLANS AND PERMIT REQUIRED
 FOR FIRE ALARM WORK.
  
 SHEET E-112
 NO EMERGENCY LIGHTING SHOWN.
  
 SHEET FS-1
 SEPARATE PLANS AND PERMIT REQUIRED FOR KITCHEN HOOD
 SUPPRESSION SYSTEM MODIFICATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-04-22 Cont ID  
Sent By lmartine Date 2011-04-21 Time 15:21 Rev Time 0.00
Received By lmartine Date 2011-04-05 Time 09:01 Sent To  
Notes
2011-04-06 09:01:55C28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-18 Cont ID  
Sent By rlecky Date 2011-01-18 Time 08:43 Rev Time 0.00
Received By rlecky Date 2010-12-20 Time 16:33 Sent To  
Notes
2010-12-20 16:33:35C24
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-04-21 Cont ID  
Sent By hmoser Date 2011-04-21 Time 07:36 Rev Time 0.00
Received By hmoser Date 2011-04-21 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-12 Cont ID  
Sent By rregueir Date 2011-01-12 Time 13:47 Rev Time 0.00
Received By rregueir Date 2011-01-12 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-04-19 Cont ID  
Sent By lwagner Date 2011-04-19 Time 09:09 Rev Time 0.00
Received By lwagner Date 2011-04-19 Time 09:09 Sent To  
Notes
2011-04-19 08:59:06GAS NOT INCLUDED IN THIS REVIEW. GAS PLAN,APPLICATION,
 PERMIT, AND FEES REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-12-29 Cont ID  
Sent By lwagner Date 2010-12-29 Time 13:37 Rev Time 0.00
Received By lwagner Date 2010-12-28 Time 13:47 Sent To  
Notes
2010-12-29 13:29:35SEPERATE GAS PLAN, APPLICATION, AND PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2010-12-30 Cont ID  
Sent By jroach Date 2010-12-30 Time 21:52 Rev Time 0.00
Received By jroach Date 2010-12-30 Time 21:51 Sent To  
Notes
***NONE***