Plan Review Details - Permit 10120447
Plan Review Stops For Permit 10120447
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-01-05 Cont ID  
Sent By jwitmer Date 2011-01-05 Time 08:43 Rev Time 1.22
Received By jwitmer Date 2011-01-04 Time 15:54 Sent To  
Notes
2011-01-05 08:51:48BUILDING PLAN REVIEW
 PERMIT: 10120447
 ADD: 10130 NORTHLAKE BLVD SUITE 100& 102
 CONT: S.W.KAPER
 TEL: (561)847-6648
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
 1008.1.9 PANIC AND FIRE EXIT HARDWARE. WHERE PANIC AND
 FIRE EXIT HARDWARE IS INSTALLED, IT SHALL COMPLY WITH
 THE FOLLOWING:
 1. THE ACTUATING PORTION OF THE RELEASING DEVICE SHALL
 EXTEND AT LEAST ONE-HALF OF THE DOOR LEAF WIDTH.
 2. THE MAXIMUM UNLATCHING FORCE SHALL NOT EXCEED 15
 POUNDS (67 N).
 EACH DOOR IN A MEANS OF EGRESS FROM A GROUP A OR E
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 50 OR MORE AND ANY
 GROUP H OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR
 LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-03 Cont ID  
Sent By rlecky Date 2011-01-03 Time 15:00 Rev Time 0.00
Received By rlecky Date 2011-01-03 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-01-10 Cont ID  
Sent By ddaniels Date 2011-01-10 Time 14:06 Rev Time 0.00
Received By ddaniels Date 2011-01-10 Time 14:06 Sent To  
Notes
2011-01-10 14:08:591/10/11 PLANS REVIEWED BY CAPTAIN DANIELS PASSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-21 Cont ID  
Sent By mcarsill Date 2010-12-21 Time 15:09 Rev Time 0.00
Received By mcarsill Date 2010-12-21 Time 15:01 Sent To  
Notes
2010-12-21 15:08:57MIJAS TEX MEX RESTAURANT
 10130 NORTHLAKE BOULEVARD, SUITE 102
 PERMIT NUMBER 10120447
  
  
 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEM.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL. PLEASE ENSURE FIRE SPRINKLER
 PROTECTION IN EXISTING WALK-IN COOLER.
  
 5. NEW GAS LINE TO BE INSTALLED IN ACCORDANCE WITH
 APPLICABLE STANDARDS AND IN A SAFE RELIABLE MANNER.
  
 6. PLEASE ENSURE THAT ALL EXIT SIGNS AND EMERGENCY
 LIGHTS ARE IN GOOD WORKING ORDER.
  
 7. ON SEVERAL SHEETS THE BACKS OF THE SEATS APPEAR TOO
 CLOSE TOGETHER IN EXISTING DINING AREA 103.
  
 8. ALL EXIT DOORS SUBJECT TO AN OCCUPANCY LOAD OF 100
 OR MORE PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 9. IS THE EXISTING OUTDOOR DINING AREA 104 HAVE A ROOF
 OR IS IT OPEN TO THE SKY?
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2010-12-28 Cont ID  
Sent By lwagner Date 2010-12-28 Time 08:45 Rev Time 0.00
Received By lwagner Date 2010-12-27 Time 14:21 Sent To  
Notes
2010-12-27 14:22:22*****PROVISO*****
  
 404.11 PIPING UNDERGROUND BENEATH BUILDINGS.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS
 IS PROHIBITED EXCEPT WHERE THE PIPING IS
 ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC
 PIPE, OR STEEL PIPE DESIGNED TO WITHSTAND THE
 SUPERIMPOSED LOADS. SUCH CONDUIT SHALL EXTEND
 INTO AN OCCUPIABLE PORTION OF THE BUILDING AND,
 AT THE POINT WHERE THE CONDUIT TERMINATES IN
 THE BUILDING, THE SPACE BETWEEN THE CONDUIT
 AND THE GAS PIPING SHALL BE SEALED TO PREVENT
 THE POSSIBLE ENTRANCE OF ANY GAS LEAKAGE.
 WHERE THE END SEALING IS CAPABLE OF
 WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE,
 THE CONDUIT SHALL BE DESIGNED FOR THE SAME
 PRESSURE AS THE PIPE. SUCH CONDUIT SHALL EXTEND
 NOT LESS THAN 4 INCHES (102 MM) OUTSIDE THE
 BUILDING, SHALL BE VENTED ABOVE GRADE TO THE
 OUTDOORS, AND SHALL BE INSTALLED SO AS TO PREVENT
 THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT
 SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE
 WITH SECTION 404.8.
  
 PLUMBING PERMIT REQUIRED
 GAS PERMIT REQUIRED
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-10 Cont ID  
Sent By ddaniels Date 2011-01-10 Time 14:07 Rev Time 0.00
Received By ddaniels Date 2011-01-07 Time 15:20 Sent To  
Notes
2011-01-07 15:22:27INCOMING SENT SUBMITTAL AND PLANS TO FIRE BOX. JW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-06 Cont ID  
Sent By hmoser Date 2011-01-06 Time 14:52 Rev Time 0.00
Received By hmoser Date 2010-12-16 Time 16:39 Sent To  
Notes
2010-12-16 16:43:06B--6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-06 Cont ID  
Sent By hmoser Date 2011-01-06 Time 14:52 Rev Time 0.00
Received By hmoser Date 2011-01-06 Time 14:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-12-27 Cont ID  
Sent By lwagner Date 2010-12-27 Time 14:21 Rev Time 0.00
Received By lwagner Date 2010-12-27 Time 12:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-12-30 Cont ID  
Sent By lfranco Date 2010-12-30 Time 11:40 Rev Time 0.00
Received By lfranco Date 2010-12-30 Time 11:40 Sent To  
Notes
2010-12-30 11:40:59PLANNING AND ZONING: **** ZONING REVIEW NOT REQUIRED:
 INTERIOR WORK ONLY AND THE VALUE OF PROPOSED WORK DOES
 NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****