Plan Review Details - Permit 10120443
| Plan Review Stops For Permit 10120443 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2010-12-17 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2010-12-17 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2010-12-17 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2010-12-17 15:40:45 | 1. APPROVED WITH THE FOLLOWING PROVISOS: | | | A. MUST PROVIDE EXECUTED CONTRACT WITH PBAU WHICH SHOWS | | | ENTIRE COST OF PROJECT. ESTIMATED VALUE SEEMS | | | SUBSTANTIALLY LOW GIVEN WORK REQURIRED INCLUDING NEW | | | CURBS, REMOVAL AND REPLACEMENT OF SHAFT WALL AND | | | INSULATION OF EXISTING DUCTS, ALONG WITH NEW EQUIPMENT, | | | ELECTRICAL AND INSTALLATION COSTS. | | | B. NO INCREASE IN VISIBILITY OF EQUIPMENT FROM ADJACENT | | | PUBLIC RIGHTS OF WAY IS AUTHORIZED OR ANTICIPATED WITH | | | THIS PERMIT. | | | C. REVISIONS REQUIRED TO ADDRESS BOTH MECHANICAL | | | COMMENTS AND TO FACILITATE THE ELECTRICAL WORK REQUIRED | | | FOR THIS PERMIT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2010-12-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-12-17 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2010-12-17 13:01:35 | TO R REGUEIRO |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2010-12-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-12-17 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2010-12-17 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2010-12-17 15:29:24 | ***PROVISO** | | | | | | 1. PROVIDE DETAIL FOR INSTALLATION AND ATTACHMENT OF | | | NEW ROOF CURB TO STRUCTURE AND NEW EQUIPMENT TO CURB | | | PER FBC-M 301.12. | | | 2. PROVIDE WIND RESISTANCE DATA, PRODUCT APPROVAL OR | | | CERTIFICATION FROM STRUCTURAL ENGINEER REGARDIN WIND | | | RESISTANCE OF THE NEWLY INSTALLED EQUIPMENT PER FBC-M | | | 301.12. | | | 3. CLEARANCE UNDER NEW EQUIPMENT SHALL BE IN ACCORDANCE | | | WITH FBC-B TABLE 1509.7 | | | 4. NEW ELECTRICAL CIRCUIT REQUIRED FOR NEW CONDENSING | | | UNITS. SEPARATE ELECTRICAL PLANS AND PERMIT REQUIRED. | | | 5. PROVIDE INFORMATION ON INSULATION TO BE USED ON | | | SUPPLY DUCT IN SHAFT PER FBC-M 604.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2010-12-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2010-12-17 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2010-12-17 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2010-12-17 15:43:23 | REPLACING EXISTING EXHAUST HOOD MAKEUP FAN WITH | | | COMBINATION MAKEUP FAN AND AIR CONDITIONING SYSTEM | | 2010-12-17 13:00:59 | NOT REQUIRED PER D WISE |
|
|
|