| 2010-12-30 11:57:36 | RESIDENTIAL (R3) ALTERATION/REPAIRS BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- A) SCOPE OF WORK ON PERMIT APPLICATION CALLS FOR |
| | REPAIRS & ALTERATION DUE TO TERMITE DAMAGE. PLANS |
| | SUBMITTED DON'T SHOW ANY REPAIRS. ARCHITECT NEED TO |
| | SPECIFY REPAIRS AND PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS TO SHOW COMPLIANCE WITH THE PROTECTION |
| | AGAINST DECAY AS REQUIRED BY SEC. R319 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 2- ARCHITECT TO SPECIFY ON PLANS TYPE OF ALTERATION AS |
| | REQUIRED BY SEC. 401.4 OF 2007 FBC- EXISTING BUILDING |
| | CODE. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 4- ARCHITECT TO SPECIFY ON PROPOSED FLOOR PLAN HOW |
| | COMPLYING WITH THE EGRESS REQUIREMENTS OF SEC. R311 AND |
| | SEC. R310. |
| | |
| | 5- ARCHITECT TO SPECIFY: |
| | A) ALL DESIGN LOADS WIND, DEAD AND LIVE LOADS, |
| | INCLUDING ATTIC LIVE LOADS AS REQUIRED BY SEC. R301 AND |
| | TABLE R301.5. |
| | |
| | B) ALL EXTERIOR OPENINGS DESIGN PRESSURES AS REQUIRED |
| | BY SEC. R301. |
| | ***NOTE: ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 |
| | THIS BUILDIG IS LOCATED ON EXPOSURE "C". TAKE THIS INTO |
| | CONSIDERATION FOR THE DESIGN PRESSURES CALCULATIONS. |
| | |
| | 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. REVISE |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| | PROFESSIONAL ARCHITECT FEES. |
| | |
| | 7- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ALL EXTERIOR DOORS AS SHOWN ON PLANS (DOOR LEADING |
| | TO PORCH FROM BEDROOM AND BATHROOM EXTERIOR DOOR). |
| | PRODUCT APPROVAL SUBMITTED (FL4809-R3) IS MISSING THE |
| | DRAWINGS SHOWING THE DOORS TO BE USED. |
| | |
| | B) ALL WINDOWS AS SHOWN ON PLANS. PRODUCT APPROVAL |
| | SUBMITTED (FL4765-R3) SUBMITTED IS MISSING THE DRAWINGS |
| | FOR SPECIFIC WINDOWS TO BE USED. |
| | |
| | C) IF DOOR AND WINDOWS TO BE INSTALLED DON'T HAVE |
| | IMPACT GLASS, THEN SHUTTERS ARE REQUIRED. SEC. |
| | R301.2.1.2. PROVIDE PRODUCT APPROVALS AND COMPLETE |
| | INSTALLATION SCHEDULE. |
| | ***NOTE: EXISTING SHUTTERS CAN'T BE USED IF THEY WERE |
| | INSTALLED WITHOUT PERMIT. PROVIDE PROOF THAT EXISTING |
| | SHUTTERS WERE INSTALLED WITH PERMIT UNDER THE FLORIDA |
| | BUILDING CODE. |
| | |
| | D) METAL ROOF AS SHOWN ON PLANS. |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | 8- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 9- ARCHITECT TO PROVIDE COMPLETE FRAMING PLANS AND |
| | SPECIFICATIONS FOR THE CONSTRUCTION OF THE SCREENED |
| | PORCH. SPECIFY ALL COLUMNS, BEAMS, STRUCTURAL |
| | CONNECTORS TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301. |
| | |
| | 10 - ARCHITECT TO PROVIDE COMPLETE FRAMING DETAILS AND |
| | SPECIFICATIONS FOR THE CONVERSION OF PORCH TO NEW |
| | BATHROOM. SPECIFY FOOTINGS, PROVIDE COMPLETE FRAMING |
| | DETAILS AND SPECIFICATIONS TO VERIFY COMPLIANCE WITH |
| | THE DESIGN PRESSURES OF SEC. R301. SPECIFY ALL |
| | STRUCTURAL CONNECTORS. PROVIDE COMPLETE WALL SECTION |
| | PROVIDING ALL THE SPECIFICATIONS TO INTERIOR AND |
| | EXTERIOR SIDE. |
| | |
| | 11- ARCHITECT TO PROVIDE IN ALL PLANS ALL THE |
| | INFORMATION REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 481 OF FLORIDA STATUTE. |
| | MISSING THE FIRM LICENSE NUMBER, NAME OF ARCHITECT |
| | SIGNING THE PLANS, LICENSE NUMBER OF ARCHITECT AND DATE |
| | WHEN PLANS WERE SEALED. |
| | |
| | 12- PROVIDE ROOF FRAMING PLAN WITH COMPLETE |
| | SPECIFICATIONS FOR NEW ROOF OVER THE PROPOSED PORCH. |
| | SEE SEC. R803.2.3.1 FOR MIN. NAIL TYPE AND SPACING TO |
| | BE USED FOR THE ROOF SHEATHING IN ALL ROOF ZONES. |
| | |
| | 13- SPECIFY SAFETY GLASS ON BATHROOM WINDOWS AS |
| | REQUIRED BY SEC. R308.4. |
| | |
| | 14- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806. |
| | |
| | 15- SPECIFY ATTIC ACCESS SIZE AND LOCATION TO COMPLY |
| | WITH SEC. R807. |
| | |
| | 16- REVISE ROOF PITCH SHOWN ON NORTH ELEVATION ON SHEET |
| | A-2.1. |
| | |
| | 17- SPECIFY ALL DOORS AND WINDOWS TYPES AND SIZES. SEC. |
| | 106.1.1 CITY AMENDMENTS TO FBC. |
| | |
| | 18- ENERGY CALCULATIONS SHOW CEILING FAN CREDIT. |
| | SPECIFY ON PLANS CEILING FAN SIZE TO COMPLY WITH TABLE |
| | C4.2.1.1 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 19- PROVIDE COMPLETE FRAMING DETAILS FOR THE |
| | INSTALLATION THE THE BEDROOM FRENCH DOORS AND SLIDERS |
| | AS SHOWN ON PLANS TO VERIFY COMPLIANCE WITH SEC. R301. |
| | |
| | 20- SHEET C-1.0: UPDATE CODE REFERENCED ON THE GENERAL |
| | NOTES. CURRENT CODE IS THE 2007 FLORIDA RESIDENTIAL |
| | CODE WITH 2009 REVISIONS. |
| | |
| | 21: ENERGY CALCULATIONS SUBMITTED: |
| | A) REVISE FLOOR TYPE. THIS BUILDING DOESN'T HAVE A SLAB |
| | ON GRADE. SEE PLANS. REVISE FRONT PAGE AND PAGE 2 OF 5. |
| | |
| | B) REVISE THE ROOF TYPE SHOWN ON SHEET 2 OF 5. SEE |
| | PLANS. |
| | |
| | C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | D) FILL ALL THE INFORMATION ON TOP OF THE FORM. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |