Plan Review Details - Permit 10120325
Plan Review Stops For Permit 10120325
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-08 Cont ID  
Sent By jwitmer Date 2011-02-08 Time 10:09 Rev Time 2.22
Received By jwitmer Date 2011-02-08 Time 10:07 Sent To  
Notes
2011-02-08 10:11:59PERMIT: 10120325
 ADD: 4215 UP THE GROVE LN.
 CONT: ROYAL CONCRETE CONCEPTS
 TEL: (561)689-5395
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 FEB. 08/2011
  
 BUILDING PROVISO:
  
 THIS BUILDING IS LOCATED WITHIN A "A-8" FLLOOD ZONE.
 THE BASE ELEVATION IS TO BE AT 15'-0" PLUS AN ADDTIONAL
 6" A REQUIRED BY THE CITY CODE OF ORDINANCES SECTION
 94-546. THE FIRST FLOOR SLAB OF THE BUILDING IS
 ELEVATED ABOVE THE MINIMUM 15'-6" BUT THE GENERATOR
 SLAB ELEVATION IS NOT PROVIDED ON C3.1. PLEASE NOTE
 THAT NON-RESIDENTIAL CAN BE SET BELOW THIS HEIGHT BUT
 WOULD NEED TO
 DEMONSTRATE HOW THIS AREA WOULD BE FLOOD PROOFED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-29 Cont ID  
Sent By jwitmer Date 2010-12-29 Time 13:13 Rev Time 0.00
Received By jwitmer Date 2010-12-29 Time 13:13 Sent To  
Notes
2010-12-29 15:52:41PERMIT: 10120325
 ADD: 4215 UP THE GROVE LN.
 CONT: ROYAL CONCRETE CONCEPTS
 TEL: (561)689-5395
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)THIS JOB WILL NOT REQUIRE NEITHER A THRESHOLD OR
 RESIDENT INSPECTOR BUT WILL NEED THE CONTRACTOR OF
 RECORD TO CONTACT CHIEF BUILDING INSPECTOR KEN CONRAD
 IN REGARDS TO ALL INSPECTIONS FOR JOB SITE WELDING,
 QUALIFICATIONS FOR JOB SITE WELDERS & CERTIFICATES.
 KEN CONRAD- TELEPHONE NUMBER (561) 805-6666.
  
 2) PLEASE PROVIDE 2 ORIGINAL SOILS TEST REPORTS SIGNED
 & SEALED. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) THIS BUILDING IS LOCATED WITHIN A "A-8" FLLOOD ZONE.
 THE BASE ELEVATION IS TO BE AT 15'-0" PLUS AN ADDTIONAL
 6" A REQUIRED BY THE CITY CODE OF ORDINANCES SECTION
 94-546. THE FIRST FLOOR SLAB OF THE BUILDING IS
 ELEVATED ABOVE THE MINIMUM 15'-6" BUT THE GENERATOR
 SLAB ELEVATION IS NOT PROVIDED ON C3.1. PLEASE NOTE
 THAT NON-RESIDENTIAL CAN BE SET BELOW THIS HEIGHT BUT
 WOULD NEED TO
 DEMONSTRATE HOW THIS AREA WOULD BE FLOOD PROOFED.
  
 4) SHEET LS-000 INDICATES THIS BUILDING TO BE AN "A"
 ASSEMBLY OCCUPANCY WITHOUT PROVIDING A SUB GROUP A-1-
 A-5. THIS BUILDING BEING FPLCOMMAND CENTER IS TRUELY A
 BUSINESS OCCUPANCY, FBC-B 304.1 BUSINESS GROUP B.
 BUSINESS GROUP B OCCUPANCY INCLUDES, AMONG OTHERS, THE
 USE OF A BUILDING OR STRUCTURE, OR A PORTION THEREOF,
 FOR OFFICE, PROFESSIONAL OR SERVICE-TYPE TRANSACTIONS,
 INCLUDING STORAGE OF RECORDS AND ACCOUNTS.
  
 5) ADDITIONAL INFORMATION REQUIRED 106.1.2, DISCREPANCY
 IN THE PLANS. LS-201 EXIT DOORSINDICATE A 33 INCH WIDE
 DOOR, NOT CLEAR SPACE, THEN NEXT TO THIS STATEMENT THE
 GRAPHICS INDICATE A 34 INCH WIDE REQUIRED. A-201 DOORS
 110 & 121 INDICATE THEY ARE
 3'X7' ON THE DOOR SCHEDULE SHEET A-801.
  
 6) A-501 & A-801 THE PLANS INDICATE WHAT PRODUCT
 APPROVALS WILL BE INSTALLED ON THE JOBSITE BUT THE
 WHOLE APPROVAL HA NOT BEEN PROVIDED. BEFORE PERMIT
 ISSUANCE THEY WILL NEED TO BE PROVIDED FOR REVIEW.
 PLEASE NOTE ON MANY WINDOW AND DOOR APPROVALS THERE ARE
 MORE THAN ONE TYPE GLAZING SYSTEM THAT IS PART OF THE
 APPROVAL. PLEASE CIRCLE WHICH GLAZED SYSTEM WILL BE
 INSTALLED SINCE EFFECTS THE ASSOCIATED PRESSURES. RULE
 9N-3 (FORMERELY RULE 9B-72).
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 6A) IMPACT WINDOWS- STOREFRONT
 6B) IMPACT WINDOWS- SPANDREL (SHEET A-501)
 6C) GLAZED EXTERIOR DOORS
 6D) METAL EXTERIOR DOORS
 6E) EXTERIOR LOUVERS
 6F) ROOFING ASSEMBLIES- NO APPROVAL INFORMATION WAS
 SUBMITTED. PLEASE NOTE THERE MAY BE SEPERATE SUBSYSTEMS
 LISTED WITHIN THE PRODUCT APPROVAL REPORT, HIGHLIGHT
 THE INTENDED SUB-SYSTEM AND NOTE THE ASSOCIATED
 PRESSURES AND IF ENHANCED FASTENING IS LISTED OR IS
 THERE A SYSTEM LIMITATION ON THAT SUB-SYSTEM.
  
 7) SHEET F-1 THE WIND DESIGN IS FIGURED AT 191 MPH
 WHICH IS HIGH, BUT THE BUILDING CATEGORY IS NOT A I BUT
 A LV. POWER GENERATING STATIONS AND OTHER PUBLIC
 UTILITIES FACILITIES REQUIRED IN AN EMERGENCY. THE
 IMPORTANCE FACTOR WILL CHANGE FROM A 1.0 TO A 1.15.
 THIS WILL CHANGE THE PRESSURES INDICATED ON THE PLANS
 AND POSSIBLY THE PROPOSED PRODUCT APPROVALS..
  
 8) SHEET F2 FLOOR SLABS PLEASE PROVIDE COMPLIANCE WITH
 1816.1 TERMITE PROTECTION / 1910.1. NOTED THIS CODE
 SECTION DEALS WITH
 SLABS ON GROUND, THE FOAM MAY ACT AS A PARTIAL BARRIER
 BUT THE BEAM PORTION OF THE FLOOR SLAB WILL EITHER BE
 IN DIRECT CONTACT WITH EARTH OR DIRECTLY ABOVE THE
 EARTH, ALOWING MOISTURE, CONDENSATION TO ENTER THE
 CONCERTE BEAM PORTION OF THE FLOOR SYSTEM AND SPAWLLING
 WOULD OCCUR OVER A PERIOD OF TIME. ALSO APPENDIX E302.1
 RADON GASSES.
  
 9) THE SECOND ISSUE WITH FOAM INSULATION IS SHEET A-601
 & A-651:
 9A) INTERIOR WALLS, PLEASE PROVIDE SURFACE- BURNING
 CHARACTERISTICS FOR THE FOAM USED WITHIN THE POURED
 WALLS. FBC-B 2603.3
 9B) THE PLANS INDICATE THE INTERIOR WALLS TO BE GWB,
 GYPSUM WALL BOARD BUT NO THICKNESS INDICATED, PLEASE
 REVIEW SECTION
 FBC-B 2603.4.
 9C) IN DETAIL # 2 THE UPPER PORTION OF WALL HAS NO
 INSULATION WITH IN THE WALL DOES THIS MEET WITH THE
 ENERGY CALCULATIONS?
 9D) IN DETAIL # 2 THE CENTRAL CORE, THE CEILING
 INDICATES EXPOSED TO THE ROOF DECK BELOW WHICH WOULD
 ALLOW FOR EXPOSED FOAM INSULATION, FBC-B 2603.4.
 9E) THIS SAME CONDITION EXIST IN THE MECHANICAL/
 ELECTRICAL ROOM# 114 AND THE SERVER ROOM # 115.
 9F) IN MANY OF THE OTHER ROOMS THE FINISH SCHEDULE
 INDICATES THE USE OF DROPPED CEILINGS, PLEASE INDICATE
 HOW THE THERMAL BARRIER WILL BE MAINTAINED.
  
 10) SHEET A-601/ A-651 DETAIL# 3, GUTTERS AND DOWN
 SPOUTS, PLEASE PROVIDE THE SCHEDULE( THICKNESS) FOR THE
 PVC DOWNSPOUTS PER
 FBC-B 1503.4.1.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-02-10 Cont ID  
Sent By rlecky Date 2011-02-10 Time 12:43 Rev Time 0.00
Received By rlecky Date 2011-02-10 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-10 Cont ID  
Sent By rlecky Date 2011-01-10 Time 09:22 Rev Time 0.00
Received By rlecky Date 2011-01-07 Time 14:11 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-02-17 Cont ID  
Sent By mgonzale Date 2011-02-17 Time   Rev Time 1.00
Received By mgonzale Date 2011-02-17 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-01-19 Cont ID  
Sent By   Date 2011-01-19 Time   Rev Time 0.50
Received By   Date 2011-01-19 Time   Sent To  
Notes
2011-01-19 16:00:04 
 ENGINEERING DEPARTMENT SUBMITTAL REQUIRED
 PLEASE RESPOND TO COMMENTS IN WRITING OR REVISIONS.
  
 #1 METER AND WATER VALVE REQUIRES A UTILITY ESEMENT
 (LEGLAN AND SKETCH CAN BE RECORDED ONCE SERVICE IS IN
 BUT SHOW PROPOSED EASEMENT ON PLAN)
  
 #2 CLEAN OUT REQUIRED AT THE PROPERTY LINE ON CITY
 SIDE.
  
 #3 PROVIDE SURFACE WATER CALCULATIONS FOR STORM WATER
 SEWER.
  
 #4 PROVIDE WATER AND SEWER DEMANDS. (SIGNED AND SEALED
 BY EOR)
 SEWER
 HTTP://WWW.DOH.STATE.FL.US/ENVIRONMENT/COMMUNITY/GROUP/
 PDFS/64E-6.PDF
 PAGE 14
 FOR WATER
 HTTP://WWW.DOH.STATE.FL.US/ENVIRONMENT/COMMUNITY/GROUP/
 PDFS/64E-8.PDF
 HTTP://WWW.SRWMD.STATE.FL.US/PERMITTING/REGFILES/SRWMD/
 WWC/REGU/R64E8/TEXT.PDF
  
 OTHER COMMENTS WILL FOLLOW WHEN SUBMITTAL IS MADE TO
 ENGINEERING DEPARTMENT DIRECTLY.
 OTHER PERTINENT DOCUMENTS ARE REQUIRED UPON SUBMITTAL.
 SEE HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
 "DEVELOPMENT PERMIT PACKAGE 2010"
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-04-04 Cont ID  
Sent By mcarsill Date 2011-04-04 Time 15:31 Rev Time 0.00
Received By mcarsill Date 2011-04-04 Time 15:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-02-09 Cont ID  
Sent By mcarsill Date 2011-02-09 Time 17:02 Rev Time 0.00
Received By mcarsill Date 2011-02-09 Time 16:57 Sent To  
Notes
2011-02-09 17:02:224215 UP THE GROVE LANE
 FLORIDA POWER AND LIGHT COMMAND BUILDING
 PERMIT NUMBER 10120325
  
 1. ON SHEET A-101 TWO FIRE DEPARTMENT CONNECTIONS ARE
 SHOWN. ONLY ONE IS REQUIRED TO SUPPORT THE FIRE
 SPRINKLER SYSTEM.
  
 2. THE EVACUATION MESSAGE ON FA2.01 NEEDS A SLIGHT
 CHANGE. PLEASE CHANGE THE WORD FROM FIRE TO EMERGENCY.
  
 3. KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION SHOWN ON FS2.01.
  
 4. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE
 WITH EXITING.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-01-05 Cont ID  
Sent By mcarsill Date 2011-01-05 Time 11:16 Rev Time 0.00
Received By mcarsill Date 2010-12-20 Time 16:18 Sent To  
Notes
2010-12-20 16:36:14FLORIDA POWER AND LIGHT GENERAL OFFICE AND COMMAND
 CENTER
 4215 UP THE GROVE LANE
 PERMIT NUMBER 10120325
  
  
 1. SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER INSTALLATIONS.
  
 2. WORKROOMS 110 AND 121 CANNOT BE LOCKED AS THEY SERVE
 AS EXIT ACCESS TO TWO EXIT DOORS.
  
 3. ALL EXIT DOORS APPEAR TO BE PROVIDED WITH PANIC
 HARDWARE. CARE READERS SHALL NOT INTERFERE WITH ANY
 EXITING FROM THESE DOORS.
  
 4. KNOX-BOX AND FIRE DEPARTMENT CONNECTION KNOX LOCKING
 CAPS CAN BE ORDERED AT WWW.KNOXBOX.COM.
  
 5. ON SHEET LS-OOO SEVERAL CODE REFERENCES ARE LISTED
 THAT ARE NOT APPLICABLE TO THIS PROJECT, THEY INCLUDE
 NFPA 14, 45 AND 96. NFPA 241 SHOULD BE ADDED TO THE
 PLANS.
  
 6. TACTILE SIGNAGE LOCATIONS SHOULD BE DISPLAYED ON
 LS-201.
  
 7. PLEASE INDICATE PHYSICALLY CHALLENGED SEATING ON
 SHEET LS-201 WITHIN THE COMMAND CENTER.
  
 8. THE REQUIRED FIRE ALARM SYSTEM IS TO BE THIRD PARTY
 MONITORED BY A LICENSED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 9. THE FIRE ALARM SYSTEM SHALL BE PROVIDED WITH VOICE
 EVACUATION. PLEASE INDICATE WHAT THE VOICE EVACUATION
 MESSAGE WILL INDICATE.
  
 10. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 EMERGENCY GENERATOR.
  
 11. ON SHEET FA1.01 HORN STROBES ARE SHOWN. THESE
 SHOULD BE SPEAKER STROBES.
  
 12. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 13. WORKROOMS 110 AND 121 DO NOT APPEAR TO CONTAIN ANY
 EMERGENCY LIGHTING EQUIPMENT ON SHEET E2.01.
  
 14. EXIT SIGNS NOT SHOWN ON SHEET E2.01.
  
 15. ON SHEET A101 DISCREPANCIES EXIST RELATED TO THE
 FIRE SAFETY EQUIPMENT THAT ARE DISPLAYED ON THE CIVIL
 DRAWINGS.
  
 16. ON SHEET A101 THE "EMERGENCY VEHICLE ACCESS WITH
 HARDENED SUB-BASE " IF EXPECTED TO SUPPORT FIRE
 EQUIPMENT MUST BE CONSTRUCTED TO SUPPORT 32 TONS.
  
 17. ON SHEET A-501 THE BUILDING ADDRESS IS NOT SHOWN ON
 ANY ELEVATION DRAWINGS. THE BUILDING ADDRESS IS TO BE A
 MINIMUM OF 6" HIGH AND AT LEAST 1" WIDE.
  
 18. THE LOCATION OF THE BACKFLOW DEVICE ON SHEET FS1-01
 DOES NOT APPEAR TO CORRESPOND TO THE CIVIL SHEETS.
  
 19. IN THE SCOPE OF WORK SECTION ON SHEET FS-201 IT
 INDICATES A THREE STORY BUILDING. THE BUILDING IS ONLY
 ONE STORY.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-02-22 Time   Rev Time  
Received By   Date 2010-12-20 Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2011-02-22 Cont ID  
Sent By rregueir Date 2011-02-22 Time 13:42 Rev Time 0.00
Received By rregueir Date 2011-02-22 Time 13:42 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2011-02-15 Cont ID  
Sent By rkussner Date 2011-02-15 Time 09:45 Rev Time 0.00
Received By rkussner Date 2011-02-15 Time 09:45 Sent To  
Notes
2011-02-15 09:49:03***LANDSCAPE REVIEW APPROVED WITH PROVISO***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. UPON RESUBMITTAL OF REVISED PLANS, PLEASE APPLY FOR
 A SEPARATE LANDSCAPE PERMIT. SUBMIT AN APPLICATON AND
 TWO SETS OF LANDSCAPE PLANS, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT. ATTACH A CERTIFIED COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIRALS AND LABOR, BROKEN DOWN INTO UNIT COST.
  
 2. UPON RESUBMITTLA OF REVISED PLANS, PLEASE APPLY FOR
 A SEPARATE IRRIGATIN PERMIT. SUBMIT AN APPLICATION AND
 TWO SETS OF IRRIGATION PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-02-10 Cont ID  
Sent By rregueir Date 2011-02-10 Time 15:48 Rev Time 0.00
Received By rregueir Date 2011-02-10 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-01-12 Cont ID  
Sent By rregueir Date 2011-01-12 Time 16:49 Rev Time 0.00
Received By rregueir Date 2010-12-20 Time 10:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-17 Cont ID  
Sent By dwise Date 2011-02-17 Time 16:52 Rev Time 0.00
Received By dwise Date 2011-02-17 Time 16:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-12-22 Cont ID  
Sent By lwagner Date 2010-12-22 Time 12:32 Rev Time 0.00
Received By lwagner Date 2010-12-21 Time 13:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2011-02-15 Cont ID  
Sent By ajones Date 2011-02-15 Time 14:29 Rev Time 0.00
Received By ajones Date 2011-02-15 Time 14:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-01-11 Cont ID  
Sent By ajones Date 2011-01-11 Time 17:23 Rev Time 0.00
Received By ajones Date 2011-01-11 Time 17:23 Sent To  
Notes
2011-01-11 17:25:36PERMITS PLANS DO NOT MATCH INFORMAL SITE PLAN REVIEW
 APROVED PLANS. SUBMIT CORRECT VERSION OF APPROVED
 PLANS.
  
 ANGELLA VANN
 PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  