Plan Review Details - Permit 10120323
Plan Review Stops For Permit 10120323
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-02-02 Cont ID  
Sent By jwitmer Date 2011-02-02 Time 14:15 Rev Time 1.25
Received By jwitmer Date 2011-02-02 Time 13:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-01-04 Cont ID  
Sent By jwitmer Date 2011-01-04 Time 11:23 Rev Time 1.22
Received By jwitmer Date 2011-01-04 Time 11:23 Sent To  
Notes
2011-01-04 12:13:44BUILDING PLAN REVIEW
 PERMIT: 10120323
 ADD: 4700 N CONGRESS 103/105
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-2 INDICATES THE SQ. FOOTAGE OF THE BUSSINESS
 AND 1 HOUR TENANT SEPERATION WALLS AS WELL AS EGRESS
 DOORS 1 & 28. THE
 DOOR SCHEDULE DOESN'T INDICATE ANY FIRE RATING FOR
 THESE DOORS OR LOCKING MECHANISM PLEASE PROVIE
 ADDTIONAL INFORMATION, PLEASE.
 FBC-B TABLE 715.4. & 1008.1.8.1.
  
 2) SHEET A-2 INDICATES AN ELECRIC ROOM AND DOOR# 21,
 THE PLANS DO NOT IDENTIFY IF THIS IS THE MAIN ELECTRIC
 ROOM THAT WOULD REQUIRE
 RATED WALLS AND OPENING PROTECTIVES, PLEASE PROVIDE
 ADDITIONAL INFORMATION, NFPA 13.8.14.10.
  
 3) SHEET A-2 PLEASE PROVIDE ADDITIONAL INFORMATION ON
 PUMP ROOM AND DOOR# 6, IF THIS ROOM IS A FIRE PUMP ROOM
 THEN THE WALS SHOULD BE IDENTIFIED AS A TWO HOUR RATED
 WAALL WITH 1 1/2 HOUR OPENING PROTECTIVES, NFPA
 20.5.12.1.1.
  
 4) SHEET A-2 LEGEND NOTE B INDICATES THE 1 HOUR TENAT
 SEPERATION WALLS PLEASE INCLUDE REQUIRED SIGNAGE BY
 SEECTION FBC-B 712.6 "FIRE & SMOKE BARRIER PROTECT ALL
 OPENINGS". PLEASE PROVIDE THROUGH PENETRATION DETAILS
 FOR ALL FIRE RATED WALLS,
 FBC-B 708.7 PENETRATIONS.
  
 5) PLEASE PROVIDE DOCUMENTATION THAT ALL REQUIREMENTS
 OF FBC-B 435.5 ARE BEING MET. IT APPEARS THAT ONE OF
 THE WALLS OF THE X-RAY ROOM IS NOT LEAD LINED WHERE AS
 DOOR 36 IN THE SAME WALL IS LEAD LINED?
  
 6) PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE
 MECHANICAL CURB DETAIL SHEET M-1, ATTACHMENT OF CURB TO
 ROOF SLAB. PLANS INDICATE THE ATTACHMENT OF THE A/C
 ROOF TOP UNIT TO CURB BUT MISSING SIZE AND SPACING OF
 ANCHOR FOR CURB ATTACHMENT. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-21 Cont ID  
Sent By rlecky Date 2010-12-21 Time 08:54 Rev Time 0.00
Received By rlecky Date 2010-12-20 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2011-02-24 Cont ID  
Sent By ddaniels Date 2011-02-24 Time 11:53 Rev Time 0.00
Received By ddaniels Date 2011-02-24 Time 11:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2011-02-16 Cont ID  
Sent By ddaniels Date 2011-02-16 Time 12:52 Rev Time 0.00
Received By ddaniels Date 2011-02-16 Time 12:52 Sent To  
Notes
2011-02-16 12:56:3602/16/11 PLANS REVIEWED BY FIRE **DENIED**
  
 1. PROVIDE EXIT SIGNS FOR ALL EXIT DOORS IN SUITE 103
 AND 105.
  
 CAPTAIN DERRICK DANIELS
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-02-10 Cont ID  
Sent By wjolin Date 2011-02-10 Time 09:35 Rev Time 0.00
Received By wjolin Date 2011-02-10 Time 09:16 Sent To  
Notes
2011-02-10 09:35:254700 NORTH CONGRESS AVENUE, SUITES 103 AND 105
 PERMIT #10120323
 REVIEW COMMENTS - FIRE
 2ND REVIEW
  
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION 106
 AND 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN
 OR ALTERATION OF FIRE SUPPRESSION SYSTEMS AND FIRE
 ALARM SYSTEMS. SECTION 106.1.1.1 OF THE FBC REQUIRES
 FIRE PROTECTION SHOP DRAWINGS TO BE SUBMITTED, UNDER A
 SEPARATE PERMIT, AND THESE SHOP DRAWINGS SHALL BE IN
 CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
  
 A ONE-HOUR FIRE-RATED TENANT SEPARATION IS REQUIRED
 BETWEEN INDIVIDUAL TENANT SPACES WHEN THE AREA EXCEEDS
 3,000 SQUARE FEET BETWEEN FIRE-RATED PARTITIONS. THE
 DOOR AND WALL BETWEEN BUSINESS OFFICE 127 AND HALL 120
 ARE REQUIRED TO BE FIRE RATED.
  
 ELECTRICAL SHEET E-2 ONLY SHOWS TWO EXIT SIGNS IN SUITE
 103.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-27 Cont ID  
Sent By wjolin Date 2010-12-27 Time 16:33 Rev Time 0.00
Received By wjolin Date 2010-12-27 Time 15:39 Sent To  
Notes
2010-12-27 16:33:354700 NORTH CONGRESS AVENUE, SUITES 103 AND 105
 PERMIT #10120323
 REVIEW COMMENTS - FIRE
  
  
 INDICATE WHAT TYPE OF OCCUPANCY EXISTS EAST AND WEST OF
 SUITE 105.
  
 PROVIDE PERTINENT LIFE SAFETY INFORMATION (EXIT SIGNS,
 FIRE EXTINGUISHER LOCATIONS ETC.) ON PLAN.
  
 FOR A BUILDING PERMIT, FIRE PROTECTION CONSTRUCTION
 DOCUMENTS ARE REQUIRED SHOWING/DESCRIBING THE SCOPE OF
 THE FIRE ALARM AND FIRE SPRINKLER WORK.
  
 SEPARATE PLANS (SHOP DRAWINGS) AND PERMITS REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM
 INSTALLATION/MODIFICATION.
  
 A ONE-HOUR FIRE-RATED TENANT SEPARATION IS REQUIRED
 BETWEEN INDIVIDUAL TENANT SPACES WHEN THE AREA EXCEEDS
 3,000 SQUARE FEET BETWEEN FIRE-RATED PARTITIONS.
  
 DOES THE LARGE EXISTING ELECTRICAL ROOM HAVE A
 FIRE-RATING?
  
 DOOR RELEASING MECHANISMS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE OPERATION. PROVIDE NEW/EXISTING DOOR
 HARDWARE, LOCKS, AND FIRE-RATING INFORMATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-02-16 Cont ID  
Sent By lmartine Date 2011-02-16 Time 10:53 Rev Time 0.00
Received By lmartine Date 2011-02-16 Time 10:53 Sent To  
Notes
2011-02-16 10:54:10IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-01-28 Cont ID  
Sent By jgomez Date 2011-01-28 Time 09:20 Rev Time 0.00
Received By jgomez Date 2011-01-28 Time 09:03 Sent To  
Notes
2011-02-02 12:57:48*************EXPEDITED*************
 2/2/11
2011-01-28 09:20:25SENT TO C16.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-04 Cont ID  
Sent By jwitmer Date 2011-01-04 Time 11:24 Rev Time 0.00
Received By jwitmer Date 2010-12-15 Time 07:06 Sent To  
Notes
2010-12-15 07:07:28C13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-02-08 Cont ID  
Sent By hmoser Date 2011-02-08 Time 07:09 Rev Time 0.00
Received By hmoser Date 2011-02-08 Time 07:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-01-03 Cont ID  
Sent By hmoser Date 2011-01-03 Time 09:18 Rev Time 0.00
Received By hmoser Date 2010-12-30 Time 06:47 Sent To  
Notes
2011-01-03 09:43:19PLAN DENIED
 OFFICE 127 HAS NO RETURN AIR ON THE PLANS. PLEASE
 PROVIDE RETURN PER SECTION 601.4 2007 FBC (M) BALANCED
 RETURN AIR.
 REFER TO SECTION 601.4 2007 FBC(M) FOR EXAM ROOMS 110
 THROUGH 116 AND 116 .
 PLEASE PROVIDE THE SIZE AND SPACING OF THE WEDGE
 ANCHORS ON THE DETAIL FOR CURB TO ROOF TIE DOWN.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-02-07 Cont ID  
Sent By lwagner Date 2011-02-07 Time 14:19 Rev Time 0.00
Received By lwagner Date 2011-02-07 Time 14:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-12-20 Cont ID  
Sent By lwagner Date 2010-12-20 Time 11:00 Rev Time 0.00
Received By lwagner Date 2010-12-20 Time 10:27 Sent To  
Notes
2010-12-20 11:00:47FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. 403.1 BUSINESS OCCUPANCIES REQUIRE DRINKING
 FOUNTAINS AT 1 PER 100
 410.1 ...WHERE DRINKING FOUNTAINS ARE REQUIRED, WATER
 COOLERS OR BOTTLED WATER DISPENSERS SHALL BE PERMITTED
 TO BE SUBSTITUTED FOR NOT MORE THAN 50 PERCENT OF THE
 REQUIRED DRINKING FOUNTAINS.
  
 2. FBC 106.3.5.1.3 RISER DIAGRAM IS REQUIRED FOR
 SANITARY AND WATER PIPEING.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-21 Cont ID  
Sent By astelly Date 2010-12-21 Time 16:10 Rev Time 0.00
Received By astelly Date 2010-12-21 Time 16:09 Sent To  
Notes
***NONE***