|
 |
 |
 |
 |
 |
Plan Review Details - Permit 10120311
| Plan Review Stops For Permit 10120311 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-01-03 |
|
|
Cont ID |
|
| Sent By |
ddaniels |
Date |
2011-01-04 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2011-01-04 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2011-01-04 12:06:36 | UPON CALLING IN FOR FIRE FINAL #131 A MICHANICAL #603 | | | FINAL IS REQUIRED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-12-22 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-12-22 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-12-22 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2010-12-22 09:09:57 | 2223 PALM BEACH LAKES BOULEVARD, SUITE #102 | | | PERMIT #10120311 | | | MASTER #08010251 | | | REVIEW COMMENTS - FIRE | | | | | | | | | THE SUITE NUMBER ON THE PERMIT APPLICATION AND THE | | | SUITE NUMBER ON THE PLANS ARE CONFLICTING (SUITE | | | 101/102). | | | | | | INSUFFICIENT NUMBER OF NOTIFICATION APPLIANCES SHOWN IN | | | CORRIDORS. | | | | | | NOTIFICATION APPLIANCES NOT PROVIDED IN KITCHENETTE OR | | | PREP ROOM. | | | | | | THE STROBE DEVICE CANNOT BE SEEN FROM THE | | | ADA-ACCESSIBLE TOILET AREA IN THE WOMEN'S BATHROOM. | | | | | | DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM CONDITION. | | | | | | INDICATE THE CLASS AND STYLE OF WIRING. | | | | | | INDICATE THE SIZE OF THE BATTERY TO BE INSTALLED. | | | | | | VOICE EVACUATION MESSAGE TO ANNOUNCE AN EMERGENCY HAS | | | BEEN REPORTED IN THE BUILDING, PERSONS ARE TO LOCATE | | | THE NEAREST EXIT AND EXIT THE BUILDING IMMEDIATELY. | | | | | | DEVICES LABELED AS AAL DO NOT INDICATE THE NOTIFICATION | | | APPLIANCES ARE SPEAKER/STROBES. | | | | | | INDICATE IF ANY TAMPER SWITCHES OR FLOW SWITCHES FROM | | | THE FIRE SPRINKLER SYSTEM WILL BE MONITORED BY THE FIRE | | | ALARM SYSTEM. | | | | | | FIRE ALARM SYSTEM TO BE MONITORED BY UL LISTED CENTRAL | | | STATION MONITORING COMPANY. | | | | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-01-03 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2011-01-03 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-01-03 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2011-01-03 14:04:44 | IN FIRE BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-12-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-12-22 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-12-14 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2010-12-14 13:19:44 | TO FIRE BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |