Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-01-03 Cont ID  
Sent By jwitmer Date 2010-12-27 Time 12:47 Rev Time 0.77
Received By jwitmer Date 2010-12-27 Time 12:47 Sent To  
Notes
2011-01-03 14:30:53BUILDING PLAN REVIEW
 PERMIT: 10120293
 ADD: 2240 P B LAKES #302
 CONT: TYDAN CONSTRUCTION
 TEL: (561)339-3717
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 01/03/2011
 1ST REVIEW: SPOKE WITH ARCHITECT STEVE YECKES ANSWERED
 CONCERNS:
 ACTION: PROVISO
  
 1) PLEASE INDICATE COMPLIANCE WITH: FBC-B 712.6 FIRE
 WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS
 AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 2) PROVIDE COMPLIANCE WITH: FBC-B 712.3
 FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO OR
 THROUGH FIRE WALLS, FIRE-BARRIER WALLS, SMOKE-BARRIER
 WALLS AND FIRE PARTITIONS SHALL COMPLY WITH SECTIONS
 712.3.1 THROUGH 712.3.4.
  
 3) DISSPROPORTIONATE COST REQUIRES 20% ABOVE CONTRACT
 VALUE (11-4.1.6(2)(1)(2)(A) CHOOSING WHICH ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT PROVIDE THE GREATEST ACCESS IN THE FOLLOWING
 ORDER(I) AN ACCESSIBLE ENTRANCE.
 THE NEW EXIT DOOR SHEET A-1 IS MISSING THE REQUIRED 18
 INCHES LATCH SIDE OF INSWING DOOR, FBC-B 11-4.13.6.
 JAMES A. WITMER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
2010-12-27 14:34:30BUILDING PLAN REVIEW
 PERMIT: 10120293
 ADD: 2240 P B LAKES #302
 CONT: TYDAN CONSTRUCTION
 TEL: (561)339-3717
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED. IT APPEARS THERE
 MAY BE EITHER 3 OR 4 TENANTS WITHIN THE 3RD FLOOR, THE
 PLANS DO INDICATE UP TO 14 OFFICES ON THIS FLOOR,
 TENANT SEPERATION WALLS ARE NOT CLEARLY DEFINED. 2007
 FBC-B 708.1 EXCEPTION #1 DOES ALLOW FOR TENAT
 SEPERATION WALLS NOT REQUIRING A 1-HOUR FIRE
 -RESISTANCE WHEN THEY DO NOT EXCEED 3,000 SQ FT.
  
 2) SHEET A-1 OFFICE SPACE 1 AND OFFICE SPACE 2
 INDICATES A NEW DOOR OPENING BEING CUT INTO THIS WALL,
 THE COMMON WALL TO CONFERENCE ROOM #1 AND KITCHEN #2.
 IS THIS A COMMUNICATING DOOR WITHIN A SINGLE TENANT OR
 A COMMUNICATING DOOR BETWEEN
 TWO SEPERATE TENANTS? AGAIN PROVIDE SQUARE FOOTAGE TO
 SEE IF FBC-B 708.1 EXCEPTION #1 IS ALLOWED IN THIS
 INSTANCE. BOTH THE PERMIT APPLICATION AND PLAN SHOULD
 INCLUDE THIS WORK TO BE WITHIN THE DESCRIPTION OF WORK
 TO BE COMPLETED UNDER THIS PERMIT.
  
 3) PLEASE INDICATE COMPLIANCE WITH: FBC-B 712.6 FIRE
 WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS
 AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
 PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 4) PROVIDE COMPLIANCE WITH: FBC-B 712.3
 FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO OR
 THROUGH FIRE WALLS, FIRE-BARRIER WALLS, SMOKE-BARRIER
 WALLS AND FIRE PARTITIONS SHALL COMPLY WITH SECTIONS
 712.3.1 THROUGH 712.3.4.
  
 5) THE NEW EXIT DOOR SHEET A-1 IS MISSING THE REQUIRED
 18 INCHES LATCH SIDE OF INSWING DOOR, FBC-B 11-4.13.6.
  
 JAMES A. WITMER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2011-01-13 Time   Rev Time 0.00
Received By rlecky Date 2011-01-13 Time 09:23 Sent To  
Notes
2011-01-13 09:23:03PROVISO:
 ELECTRIC SUB PERMIT REQUIRED FOR THE NEW ELECTRIC WORK.
 ELECTRICAL BOXES INSTALLED WITHIN FIRE RATED WALLS MUST
 BE FIRE STOPPED, PROTECTED, LISTED, OR INSTALLED TO
 MAINTAIN THE FIRE RESISTANCE RATING. PROVIDE A DETAIL
 OR SPECIFICATION FOR THE INSTALLATION. NEC 300.21
 ROBERT LECKY, ELECTRICAL PLANS EXAMINER, 561-805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-01-25 Cont ID  
Sent By wjolin Date 2010-12-21 Time 12:42 Rev Time 0.00
Received By wjolin Date 2010-12-21 Time 09:45 Sent To  
Notes
2010-12-21 12:42:132240 PALM BEACH LAKES BOULEVARD, SUITE 302
 PERMIT #10120293
 REVIEW COMMENTS - FIRE
  
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION.
  
 NEW OR EXISTING LIFE SAFETY EQUIPMENT (FIRE ALARM, FIRE
 SPRINKLERS, PORTABLE FIRE EXTINGUISHERS) NOT SHOWN ON
 PLANS FOR ANY OF THE OFFICE SPACES.
  
 SECTION 708 OF THE FLORIDA BUILDING CODE REQUIRES A
 1-HOUR FIRE RATED PARTITION BETWEEN INDIVIDUAL TENANT
 SPACES EXCEPT FOR BUSINESS OCCUPANCIES, PROVIDED NO
 AREA BETWEEN FIRE-RATED PARTITIONS EXCEEDS 3,000 SQUARE
 FEET. THE NEW WALLS RESULT IN FIVE SEPARATE TENANT
 SPACES. PLEASE INDICATE WHICH EXISTING WALLS HAVE A
 FIRE RATING.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER???PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. (REFERENCE: SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ??? NFPA 101)
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
 (REFERENCE: SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION
 CODE ??? NFPA 101)
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-01-13 Cont ID  
Sent By rlecky Date 2011-01-13 Time 10:04 Rev Time 0.00
Received By rlecky Date 2010-12-13 Time 15:53 Sent To  
Notes
2010-12-14 15:54:11B4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-12-28 Cont ID  
Sent By hmoser Date 2010-12-28 Time 13:10 Rev Time 0.00
Received By hmoser Date 2010-12-28 Time 13:07 Sent To  
Notes
2010-12-28 13:14:34NO MECHANICAL PERMIT REQUIRED AT THIS TIME. IF
 MECHANICAL WORK IS TO BE DONE PLEASE HAVE MECHANICAL
 CONTRACTOR PROVIDE PLANS AT THE TIME OF APPLICATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By jroach Date 2010-12-22 Time 10:14 Rev Time 0.00
Received By jroach Date 2010-12-22 Time 10:14 Sent To  
Notes
***NONE***