Plan Review Details - Permit 10120284
Plan Review Stops For Permit 10120284
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-16 Cont ID  
Sent By wjolin Date 2010-12-16 Time 15:56 Rev Time 0.00
Received By wjolin Date 2010-12-15 Time 16:17 Sent To  
Notes
2010-12-15 16:20:26505 SOUTH FLAGLER DRIVE, SUITE #700
 PERMIT #10120284
 REVIEW COMMENTS - FIRE
  
  
 FIRE ALARM NOTIFICATION APPLIANCES WILL BE ADDED TO THE
 RESTROOMS AS PART OF THE BASE-BUILDING FIRE ALARM
 UPGRADE (UNDER A SEPARATE DRAWING AND PERMIT).
  
 PLANS SHOW FIRE ALARM SPEAKER/STROBE DEVICES. SUBMITTED
 PRODUCT DATA SHOWS FIRE ALARM HORN/STROBE DEVICES. FIRE
 ALARM SYSTEM HAS VOICE EVACUATION CAPABILITIES
 REQUIRING SPEAKER/STROBE NOTIFICATION APPLIANCES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-16 Cont ID  
Sent By wjolin Date 2010-12-16 Time 15:56 Rev Time 0.00
Received By wjolin Date 2010-12-14 Time 13:20 Sent To  
Notes