Plan Review Details - Permit 10120252
Plan Review Stops For Permit 10120252
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-12-22 Cont ID  
Sent By shill Date 2010-12-22 Time 18:12 Rev Time 0.00
Received By shill Date 2010-12-22 Time 18:12 Sent To  
Notes
2010-12-22 18:13:54****PROVISO****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE INSTALLATION SCHEDULE AT INSPECTION.
 CONTRACTOR IS TO USE EXPOSURE C DESIGN PRESSURES PER
 TELEPHONE CONVERSATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-21 Cont ID  
Sent By shill Date 2010-12-21 Time 15:41 Rev Time 0.00
Received By shill Date 2010-12-21 Time 15:41 Sent To  
Notes
2010-12-21 15:47:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. R301.2.1.4 EXPOSURE CATEGORY. FOR EACH WIND
 DIRECTION CONSIDERED, AN EXPOSURE CATEGORY THAT
 ADEQUATELY REFLECTS THE CHARACTERISTICS OF GROUND
 SURFACE IRREGULARITIES SHALL BE DETERMINED FOR THE SITE
 AT WHICH THE BUILDING OR STRUCTURE IS TO BE
 CONSTRUCTED. FOR A SITE LOCATED IN THE TRANSITION ZONE
 BETWEEN CATEGORIES, THE CATEGORY RESULTING IN THE
 LARGEST WIND FORCES SHALL APPLY. ACCOUNT SHALL BE TAKEN
 OF VARIATIONS IN GROUND SURFACE ROUGHNESS THAT ARISE
 FROM NATURAL TOPOGRAPHY AND VEGETATION AS WELL AS FROM
 CONSTRUCTED FEATURES. FOR ANY GIVEN WIND DIRECTION, THE
 EXPOSURE IN WHICH A SPECIFIC BUILDING OR OTHER
 STRUCTURE IS SITED SHALL BE ASSESSED AS BEING ONE OF
 THE FOLLOWING CATEGORIES:
  
 EXCEPTION: AN INTERMEDIATE EXPOSURE BETWEEN THE
 EXPOSURE CATEGORIES DEFINED IS PERMITTED IN A
 TRANSITION ZONE PROVIDED THAT IT IS DETERMINED BY A
 RATIONAL ANALYSIS METHOD.
  
 PLANS HAVE A NOTE THAT THIS PARCEL IS CATEGORY B
 ROUGHNESS FOR 1500 FEET IN THE UPWIND DIRECTION. PLEASE
 SEE AERIALS, ROUGHNESS C OCCURS IN TWO DIFFERENT
 DIRECTIONS (ONE WITHIN 600 FEET). EITHER PROVIDE
 CALCULATIONS FOR DESIGN PRESSURES (SEE EXCEPTION) OR
 USE EXPOSURE C PRESSURES.
  
 2. PLEASE NOTE THAT THE WINDOWS COMPLY WITH EXPOSURE C
 DESIGN PRESSURES, BUT THE SHUTTER INSTALLATION PROPOSED
 MAY NOT COMPLY IF PRESSURES ARE INCREASED.
  
 3. PROPOSED INSTALLATION IS FOR ITW, PRODUCT APPROVAL
 HAS ELCO TESTED. MODIFICATIONS TO THE PRODUCT APPROVAL
 REQUIRES ENGINEERING.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-21 Cont ID  
Sent By shill Date 2010-12-21 Time 15:47 Rev Time 0.00
Received By shill Date 2010-12-13 Time 14:07 Sent To  
Notes
2010-12-13 14:07:50BLDG <$5K
  