Plan Review Details - Permit 10120231
Plan Review Stops For Permit 10120231
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-12-21 Cont ID  
Sent By jwitmer Date 2010-12-21 Time 09:15 Rev Time 0.77
Received By jwitmer Date 2010-12-21 Time 09:15 Sent To  
Notes
2010-12-21 09:43:34 
 BUILDING PLAN REVIEW
 PERMIT: 10120231
 ADD: 477 S ROSEMARY #301
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISO: BUILDING APPROVED WITH EXCEPTION!
 1) THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE
 TO CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR
 TO INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND
 THE ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS
 REQUIRE ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 RESTROOM DOOR VERSES CLEAR FLOOR SPACE FOR LAVATORIES-
 11-4.19.3 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A LAVATORY TO ALLOW
 FORWARD APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN
 OR OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A
 MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY
 (SEE FIGURE 32).
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-01-07 Cont ID  
Sent By rlecky Date 2011-01-07 Time 13:19 Rev Time 0.00
Received By rlecky Date 2010-12-27 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-17 Cont ID  
Sent By mcarsill Date 2010-12-17 Time 14:37 Rev Time 0.00
Received By mcarsill Date 2010-12-17 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-01-10 Time   Rev Time 0.00
Received By rregueir Date 2010-12-09 Time 09:48 Sent To  
Notes
2010-12-22 09:49:46**DIGITAL PLANS** SEE PROJECTDOX AND B-30 ON
 SPREADSHEET

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-21 Cont ID  
Sent By rregueir Date 2010-12-21 Time 09:22 Rev Time 0.00
Received By rregueir Date 2010-12-20 Time 10:56 Sent To  
Notes
2011-01-10 09:17:22VENTILATION REQUIREMENTS PROVIDED ALONG WITH LOUVER
 PRODUCT APPROVAL. 1/10/11
 -----------------------------------
2010-12-21 09:22:44SPOKE WITH CHRIS AT FAE CONSULTING ENGINEERS. NO
 PROVISIONS HAVE BEEN MADE FOR VENTILATION OF THE
 RECONFIGURED SPACES, AS REQUIRED PER FBC-EB 709.1. THIS
 ISSUE MAY BE RE-ADDRESSED, AND A NEW MECHANICAL SHEET
 CAN BE SUBMITTED ADDRESSING THE VENTILATION
 REQUIREMENT, IF ALL OTHER TRADES PASS AND MECHANICAL IS
 THE ONLY STOP PREVENTING PERMIT ISSUANCE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-12-21 Cont ID  
Sent By lwagner Date 2010-12-21 Time 13:55 Rev Time 0.00
Received By lwagner Date 2010-12-21 Time 13:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-02-17 Cont ID  
Sent By spalmer Date 2011-02-17 Time 15:14 Rev Time 0.00
Received By spalmer Date 2011-02-17 Time 15:14 Sent To  
Notes
2011-02-17 15:14:57OKAY PER RON REGUEIRO

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-27 Cont ID  
Sent By eschneid Date 2010-12-27 Time 11:18 Rev Time 0.25
Received By eschneid Date 2010-12-27 Time 11:18 Sent To  
Notes
2010-12-27 11:19:59UPPER STORY INTERIOR RENOVATION. DOES NOT TRIGGER THE
 50% RULE.