| Plan Review Stops For Permit 10120203 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-12-14 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2010-12-14 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2010-12-14 |
Time |
10:29 |
Sent To |
M |
|
| Notes |
| 2010-12-14 11:08:27 | 901--45TH STREET (CATH LAB) | | | PERMIT #10120203 | | | REVIEW COMMENTS - FIRE | | | | | | PROVIDE TEMPORARY SPRINKLER COVERAGE FOR SMALL | | | TEMPORARY VESTIBULE CREATED WEST OF THE PROCEDURE ROOM. | | | | | | SYSTEM PRESSURES EXCEED 100 PSI. PROVIDE APPROPRIATE | | | HANGER RESTRICTIONS AND SPACING PER NFPA 13. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|
|