Plan Review Details - Permit 10120203
Plan Review Stops For Permit 10120203
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-14 Cont ID  
Sent By wjolin Date 2010-12-14 Time 11:08 Rev Time 0.00
Received By wjolin Date 2010-12-14 Time 10:29 Sent To M
Notes
2010-12-14 11:08:27901--45TH STREET (CATH LAB)
 PERMIT #10120203
 REVIEW COMMENTS - FIRE
  
 PROVIDE TEMPORARY SPRINKLER COVERAGE FOR SMALL
 TEMPORARY VESTIBULE CREATED WEST OF THE PROCEDURE ROOM.
  
 SYSTEM PRESSURES EXCEED 100 PSI. PROVIDE APPROPRIATE
 HANGER RESTRICTIONS AND SPACING PER NFPA 13.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-27 Cont ID  
Sent By hmoser Date 2010-12-27 Time 11:59 Rev Time 0.00
Received By hmoser Date 2010-12-10 Time 13:55 Sent To  
Notes
2010-12-10 13:56:11SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-27 Cont ID  
Sent By hmoser Date 2010-12-27 Time 11:59 Rev Time 0.00
Received By hmoser Date 2010-12-27 Time 11:20 Sent To  
Notes
***NONE***