Plan Review Details - Permit 10120202
Plan Review Stops For Permit 10120202
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-12-20 Cont ID  
Sent By shill Date 2010-12-20 Time 12:07 Rev Time 0.00
Received By shill Date 2010-12-20 Time 12:07 Sent To  
Notes
2010-12-20 12:15:58PROVISO
  
 1. FBC TABLE 11 4.1.3(19), 30 ACCESSIBLE SEATS REQUIRED
 WITH COMPANION SEATS.
  
 2. WHEELCHAIR SEATING TO BE PROVIDED IN MORE THAN ONE
 LOCATION FBC11 4.33.3.
  
 3. ACCESSIBLE SEATING TO BE AVAILABLE IN ALL PRICE
 RANGES AND SIGHT LINES FBC 11-4.33.3.
  
 4. INSTALLATION TO BE IN A LOCATION WITH SMOKE
 PROTECTION FBC 1025.6.2.1. IF PROPOSED LOCATION IS NOT
 SMOKE PROTECTED, MEANS OF EGRESS TO COMPLY WITH FBC
 TABLE 1025.9.2.1.
  
 5. SPECIAL INSPECTOR REQUIRED, FBC109.3.6.
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-17 Cont ID  
Sent By mcarsill Date 2010-12-17 Time 15:57 Rev Time 0.00
Received By mcarsill Date 2010-12-16 Time 12:53 Sent To  
Notes
2010-12-16 14:01:40PALM BEACH COUNTY CONVENTION CENTER
 650 OKEECHOBEE BOULEVARD
 "CHAIR RISERS FOR 10 DAYS FOR THE PUBLIC TO VIEW THE
 CIRCUS"
  
  
 1. THE BLEACHER INSTALLATIONS WITHIN THE BUILDING ARE
 FOR TEMPORARY PURPOSES ONLY. IT IS EXPECTED THAT THE
 BLEACHER INSTALLATIONS WILL BE REMOVED WHEN THE
 RINGLING BROTHERS CIRCUS COMPLETES ITS EVENTS.
  
 2. ALL BLEACHER ASSEMBLIES SHALL BE INSTALLED AND
 MAINTAINED FOR SAFE OPERATION WHILE IN USE.
  
 3. AFTER EACH CIRCUS PERFORMANCE THE UNDERNEATH OF THE
 BLEACHER ASSEMBLIES SHALL BE CHECKED FOR TRASH AND
 DEBRIS. TRASH AND DEBRIS SHALL NOT BE ALLOWED TO
 ACCUMULATE UNDERNEATH THE BLEACHERS.
  
 4. AFTER EACH PERFORMANCE, THE BLEACHER ASSEMBLIES
 SHALL BE CHECKED FOR FOR ANY LOOSE CONNECTIONS,
 ABNORMALITIES, DAMAGE, OR DEFORMITIES. HANDRAILS AND
 GUARDRAILS SHALL ALSO BE INSPECTED AFTER EACH
 PERFORMANCE TO ENSURE THAT THEY ARE CAPABLE OF
 PROVIDING THE SAFETY MEASURES THAT THEY ARE INTENDED
 FOR. DIAGONAL AND ANY HORIZONTAL BRACING SHALL BE
 INSTALLED IN A MANNER AS DIRECTED BY QUALIFIED PERSONS.
  
 5. IN ALL CASES WHERE MORE THAN 200 SEATS EXIST, THEY
 ARE TO BE SECURED IN GROUPS NOT LESS THAN THREE.
  
 6. SEATING ACCOMMODATIONS ARE TO BE PROVIDED FOR THE
 PHYSICALLY CHALLENGED.
  
 7. NO ELECTRICAL EQUIPMENT, HEATING, OR OPEN FLAME
 DEVICES SHALL BE PERMITTED UNDERNEATH THE BLEACHER
 ASSEMBLIES.
  
 8. THE DESIGN, STRENGTH, AND INSTALLATION OF THE
 BLEACHERS SHALL COMPLY WITH NFPA 102, THE STANDARD FOR
 GRANDSTANDS, FOLDING AND TELESCOPIC SEATING, TENTS, AND
 MEMBRANE STRUCTURES.
  
 9. SEATING FOR THE GRANDSTAND OR BLEACHER SHALL COMPLY
 WITH SECTION 4-4 OF NFPA 102, THE STANDARD FOR
 GRANDSTANDS, FOLDING AND TELESCOPIC SEATING, TENTS, AND
 MEMBRANE STRUCTURES.
  
 10. ACCORDING TO SECTION 4-7.3 OF NFPA 102, "PORTABLE
 GRANDSTANDS SHALL BE PROVIDED WITH BASE PLATES, SILLS,
 FLOOR RUNNERS, OR SLEEPERS OF SUCH AREA THAT THE
 ALLOWABLE BEARING CAPACITY OF THE SUPPORTING MATERIAL
 IS NOT EXCEEDED".
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-20 Cont ID  
Sent By shill Date 2010-12-20 Time 12:16 Rev Time  
Received By shill Date   Time   Sent To  
Notes
***NONE***