Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-01-20 Cont ID  
Sent By shill Date 2011-01-20 Time 12:55 Rev Time 0.00
Received By shill Date 2011-01-20 Time 12:55 Sent To  
Notes
2011-01-20 13:04:10****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****CONTRACTOR TO PROVIDE REVISED FLOOR PLAN/REVISED
 DESIGN PRESSURES AT INSPECTION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 REVISE PLAN TO SHOW COMPLIANCE WITH THE FOLLOWING:
  
 1. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR
 BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002. BUILDING HEIGHT IS REQUIRED
 TO DETERMINE DESIGN PRESSURES.
  
 REVISE PLAN TO SHOW BUILDING HEIGHT. BASED ON
 CONTRACTOR'S RESUBMITTAL FORM, BUILDING HEIGHT IS 40
 FEET. PER TELEPHONE CONVERSATION, ALL OPENINGS ARE IN
 ZONE 4.
  
 PER ASCE7-05, +49.46/-56.91 REQUIRED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-01-19 Cont ID  
Sent By shill Date 2011-01-19 Time 12:24 Rev Time 0.00
Received By shill Date 2011-01-19 Time 12:24 Sent To  
Notes
2011-01-19 12:50:59****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 REVISE PLAN TO SHOW COMPLIANCE WITH THE FOLLOWING:
  
 1. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR
 BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002. BUILDING HEIGHT IS REQUIRED
 TO DETERMINE DESIGN PRESSURES.
  
 REVISE PLAN TO SHOW BUILDING HEIGHT. BASED ON
 CONTRACTOR'S RESUBMITTAL FORM, BUILDING HEIGHT IS 40
 FEET. PROPOSED DESIGN PRESSURES IN FIRST SUBMITTAL NOT
 CODE COMPLIANT, AND NO NEW DOCUMENTS SUBMITTED WITH 2ND
 SUBMITTAL.
  
 THIS PERMIT IS ISSUED AT CONTRACTOR'S RISK. CONTRACTOR
 IS TO REVISE THE PLAN TO STATE BUILDING HEIGHT AND
 PROPOSED DESIGN PRESSURES FOR 140MPH, EXPOSURE C. NOTE
 THAT BASED ON INFORMATION PROVIDED, THE NON IMPACT
 WINDOWS WHICH ARE LOCATED IN ZONE 5 DO NOT COMPLY.
 REVISION IS TO SHOW COMPLIANCE WITH DESIGN PRESSURE
 REQUIREMENTS OR SUBMIT NEW PRODUCT APPROVAL IF
 NECESSARY.
  
 SEE ASCE 7-05 FIGURE 6-3, -47.2 PSF REQUIRED FOR 10 SF,
 ZONE 5, TIMES 1.49 ADJUSTMENT FACTOR FOR 40' EXPOSURE
 C, -70.328 PSF REQUIRED.
  
 2. REVISE PLAN TO STATE EXISTING SUBSTRATE.
  
 NOTE - SPOKE WITH CONTRACTOR'S OFFICE REGARDING PROVISO
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-10 Cont ID  
Sent By shill Date 2010-12-10 Time 19:16 Rev Time 0.00
Received By shill Date 2010-12-10 Time 19:16 Sent To  
Notes
2010-12-10 19:18:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR
 BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002. BUILDING HEIGHT IS REQUIRED
 TO DETERMINE DESIGN PRESSURES.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. THE SHUTTER PERMIT IS "EXPIRED" FOR THIS
 ADDRESS (06040645).
  
 3. PROVIDE INFORMATION REGARDING THE SUBSTRATE. CONFIRM
 THAT PROPOSED INSTALLATION IS INCLUDED IN THE PRODUCT
 APPROVAL.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-10 Cont ID  
Sent By shill Date 2010-12-10 Time 19:21 Rev Time 0.00
Received By shill Date 2010-12-09 Time 13:15 Sent To  
Notes
2010-12-09 13:16:29UNDER 5 K BUILDING