| 2011-01-19 12:50:59 | ****PROVISO**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | ****REVISION REQUIRED**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | REVISE PLAN TO SHOW COMPLIANCE WITH THE FOLLOWING: |
| | |
| | 1. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR |
| | BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING |
| | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| | ORIGINALS FAC61G15-23.002. BUILDING HEIGHT IS REQUIRED |
| | TO DETERMINE DESIGN PRESSURES. |
| | |
| | REVISE PLAN TO SHOW BUILDING HEIGHT. BASED ON |
| | CONTRACTOR'S RESUBMITTAL FORM, BUILDING HEIGHT IS 40 |
| | FEET. PROPOSED DESIGN PRESSURES IN FIRST SUBMITTAL NOT |
| | CODE COMPLIANT, AND NO NEW DOCUMENTS SUBMITTED WITH 2ND |
| | SUBMITTAL. |
| | |
| | THIS PERMIT IS ISSUED AT CONTRACTOR'S RISK. CONTRACTOR |
| | IS TO REVISE THE PLAN TO STATE BUILDING HEIGHT AND |
| | PROPOSED DESIGN PRESSURES FOR 140MPH, EXPOSURE C. NOTE |
| | THAT BASED ON INFORMATION PROVIDED, THE NON IMPACT |
| | WINDOWS WHICH ARE LOCATED IN ZONE 5 DO NOT COMPLY. |
| | REVISION IS TO SHOW COMPLIANCE WITH DESIGN PRESSURE |
| | REQUIREMENTS OR SUBMIT NEW PRODUCT APPROVAL IF |
| | NECESSARY. |
| | |
| | SEE ASCE 7-05 FIGURE 6-3, -47.2 PSF REQUIRED FOR 10 SF, |
| | ZONE 5, TIMES 1.49 ADJUSTMENT FACTOR FOR 40' EXPOSURE |
| | C, -70.328 PSF REQUIRED. |
| | |
| | 2. REVISE PLAN TO STATE EXISTING SUBSTRATE. |
| | |
| | NOTE - SPOKE WITH CONTRACTOR'S OFFICE REGARDING PROVISO |
| | |
| | |
| | |
| | |
| | |
| | |