Plan Review Details - Permit 10120168
Plan Review Stops For Permit 10120168
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-13 Cont ID  
Sent By jwitmer Date 2010-12-13 Time 14:15 Rev Time 0.25
Received By jwitmer Date 2010-12-13 Time 14:00 Sent To  
Notes
2010-12-13 14:22:44BUILDING PLAN REVIEW
 PERMIT: 10060173/ REV: 10120168
 ADD: 201 S NARCISSUS AV
 CONT: CM CONSULTING
 TEL: (561)373-3902
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE NEWLY REVERSED DOOR WITHIN THE TENANT WALL IS
 REVERSED TO THE EGRESS FLOW. EVEN THOUGH THIS DOOR NOW
 IS NOT MARKED AS A EGRESS DOOR THE OCCUPANT LOAD IS
 OVER 50. 2007 FBC-BUILDING SECTION 1008.1.2 DOORS SHALL
 SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR
 A GROUP H OCCUPANCY.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-12-14 Cont ID  
Sent By rlecky Date 2010-12-14 Time 15:09 Rev Time 0.00
Received By rlecky Date 2010-12-14 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-12-17 Cont ID  
Sent By wjolin Date 2010-12-17 Time 10:19 Rev Time 0.00
Received By wjolin Date 2010-12-17 Time 09:55 Sent To  
Notes
2010-12-17 10:19:55201 SOUTH NARCISSUS AVENUE, SUITE #2
 TRACKING #10120168
 PERMIT #10060173
 REVIEW COMMENTS - FIRE
  
 FIRE-RATED VESTIBULE DOOR ON SHEET A.3 IS REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT
 LOAD OF 50 OR GREATER PERSONS PER SECTION 7.2.1.4.2 OF
 THE FLORIDA FIRE PREVENTION CODE (NFPA 101 - LIFE
 SAFETY CODE).
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-17 Cont ID  
Sent By wjolin Date 2010-12-17 Time 10:22 Rev Time 0.00
Received By wjolin Date 2010-12-08 Time 17:12 Sent To  
Notes
2010-12-08 17:20:51B--8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-16 Cont ID  
Sent By hmoser Date 2010-12-16 Time 11:06 Rev Time 0.00
Received By hmoser Date 2010-12-16 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-12-14 Cont ID  
Sent By lwagner Date 2010-12-14 Time 13:30 Rev Time 0.00
Received By lwagner Date 2010-12-14 Time 11:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2010-12-21 Cont ID  
Sent By astelly Date 2010-12-21 Time 15:47 Rev Time 0.00
Received By astelly Date 2010-12-21 Time 15:47 Sent To  
Notes
***NONE***