Plan Review Details - Permit 10120067
Plan Review Stops For Permit 10120067
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-12-09 Cont ID  
Sent By wjolin Date 2010-12-09 Time 10:01 Rev Time 0.00
Received By wjolin Date 2010-12-09 Time 09:37 Sent To M
Notes
2010-12-09 10:00:57222 LAKEVIEW AVENUE - 14TH FLOOR COMMON AREA
 TRACKING #10120067
 PERMIT #10100194
 REVIEW COMMENTS - FIRE
  
 HANGERS ARE REQUIRED FOR ARMOVERS EXCEEDING 12-INCHES
 WHEN SYSTEM PRESSURES EXCEED 100 PSI.
  
 RESTROOM SPRINKLERS LOCATED CLOSER THAN SIX FEET APART.
 SPRINKLER LOCATIONS MAY NEED TO BE STAGGERED TO PREVENT
 COLD SOLDERING.
  
 ELEVATOR LOBBY SPRINKLERS TO COMPLY WITH THE
 OBSTRUCTION RULES OF NFPA 13 CONCERNING THE ELEVATOR
 LOBBY SOFFITS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-10 Cont ID  
Sent By hmoser Date 2010-12-10 Time 10:13 Rev Time 0.00
Received By hmoser Date 2010-12-10 Time 10:13 Sent To  
Notes
2010-12-03 10:15:41SENT TO FIRE BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-12-10 Cont ID  
Sent By hmoser Date 2010-12-10 Time 10:13 Rev Time 0.00
Received By hmoser Date 2010-12-10 Time 10:13 Sent To  
Notes
***NONE***