Plan Review Details - Permit 10120063
Plan Review Stops For Permit 10120063
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-12-22 Cont ID  
Sent By jwitmer Date 2010-12-22 Time 15:25 Rev Time 2.22
Received By jwitmer Date 2010-12-22 Time 14:30 Sent To  
Notes
2010-12-22 16:25:46BUILDING PLAN REVIEW
 PERMIT: 10120063
 ADD: 353 LAURIE RD
 CONT: O/B CHOPLIN, CHRISTOPHER
 TEL: (561)543-8030
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 PLANS ARE CONCEPTUAL IN NATURE, NOT ENOUGH DETAIL TO
 BUILD BY THIS WILL BE A LIST OF REQUIREMENTS AND OR
 ADDITIONAL INFORMATION TO BUILD THIS PORCH.
  
 1) THE PLANS WILL NEED A TITLE BLOCK INDICATING WHO THE
 DESIGNER OF THE PLANS WILL BE, WILL NEED SIGNATURE OF
 DESIGNER.
  
 2) THE PLANS ALSO WILL NEED TO PROVIDE WIND DESIGN
 CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 2.5) DESIGN PRESSURES.
  
 3) PLANS NEED TO BE DRAWN TO A SCALE AND OR DIMENSION
 ALL PORTIONS OF THE PORCH. EXAMPLE:
 3A) THE SIDE ELEVATION DOES PROVIDE THE DIMENSIONS FOR
 THE NEW SLAB BUT DOES NOT INDICATE :
 1) A VAPOR BARRIER, AND SOIL PRETREAT FOR TERMITES,
 2) THE PLANS DO NOT INDICATE THE AMOUNT OS STEEL
 REINFORCING BARS ARE TO BE IN THE FOOTER AND THE SIZE
 OF THE BARS, NOR DOES THE
 PLANS INDICATE IF FIBER MESH OR WELDED WIRE 6X6 MESH
 WILL BE INSTALLED IN THE SLAB. WHAT TYPE OF CHAIRS WILL
 THE WIRE MESH BE
 PLACED ON?
 3) THE PLANS ALSO FAIL TO INDICATE THE TYPE OF CONCRETE
 MIX THAT WILL BE USED FOR THIS APPLICATION.
  
 4) POST AND HEADERS:
 4A) PLANS INDICATE A SIMPSON CB66 COLUMN BASE PLEASE
 IDENTIFY WHICH ANCHOR IS TO BE INSTALLED PRIMER GRAY OR
 THE HDG (HEAVY DIPPED GALVANIZED) SINCE IT WILL BE
 EMBEDDED IN CONCRETE, PLEASE ALS OPROVIDE WHAT THE
 UPLIFT AND LATERAL LOADS THESE ANCHORSS WILL SUPPORT?
  
 4B) PLEASE PROVIDE SIZE OF POST AND BEAM, PROVIDE TYPE
 OF SPECIES OF WOOD, GRADE OF WOOD AND ALLOWABLE AMOUNT
 OF MEMBERS IN BEAM, SPANS FOR THE BUILT UP BEAM, WHERE
 SPLICES WILL OCCUR AND IF BEAM IS TO BE CONSIDERED A
 SIMPLE SPAN OR WILL MULTILE SPANS.
  
 4C) POST TO BEAM CONNECTION TYPE OF FINISH ON ANCHOR
 PRIMER GRAY OR HDG.
  
 5) THE SECTION OF ELEVATION INDICATES WHAT APPEARS TO
 BE A PARTIAL TRUSS ATTACHING TO THE ROOF FRAMING HIGHER
 THAN THE FACIA, A PIGGYBACK TRUSS WITH WHAT APPEARS TO
 BE A LARGE TRIANGLAR WEDGE THAT SITS BENEATH THE NEW
 ROOF TTRUSS SYSTEM.
 5A) PLEASE PROVIDE ADDITIONAL INFOMATION TO WHERE THE
 UPPER AND LOWER LEG OF THE TRUSS ANCHORS INTO THE
 EXISSTING ROOF FRAMING?
  
 5B) PLEASE PROVIDE WHAT TYPE OF MATERIAL THIS
 TRIANGULAR WEDGE WILL BE BUILT? PLEASE PROVIDE AT WHAT
 CENTERS THE TRUSSES WILL INSTALLED?
  
 5C) PLEASE PROVIDE THE GRAVITY, LATERAL AND UPLIFT
 LOADS WILL BE IMPOSED ON THESE TRUSSES AS WELL AS THE
 BEAM TO COLUMN CONNECTIONS.
  
 6) TYPICAL WALL SEECTION PLEASE IDENTIFY THE ROOF
 FRAMING IF A TRUE TRUSS OR DIMENSIONAL LUMBER AND
 SPECIES OF WOOD, GRADE AND SPACING AS WELL AS ROOF
 SHEATHING INFORMATION.
  
 7) THE PLANS DO NOT INDICATE THE SLOPE OF THE NEW ROOF
 FRAMING?
  
 8) PLEASE ALSO PROVIDE THE TYPE OF ROOFING ASSEMBLY TO
 BE ATTACHED TO THE ROOF SHEATHING, INCLUDE TYPE OF
 UNDERLAYMENT AND FINAL
 ROOFING PRODUCT, PROVIDE TYPE OF FASTENERS AND SPACING
 ?
  
 9) PLEASE PROVIDE IF THE CEILING OF THE NEW PORCH IS TO
 BE A ENCLOSED CEILING OR WILL THE ROOF FRAMING MEMBRS
 BE EXPOSED?
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-12-22 Cont ID  
Sent By jwitmer Date 2010-12-22 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2010-12-03 Time 11:06 Sent To  
Notes
2010-12-09 17:25:2212/9 TO MISC 2
  
2010-12-03 11:06:32SENT TO ZONING BOX.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-12-22 Cont ID  
Sent By jwitmer Date 2010-12-22 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2010-12-22 Time 15:25 Sent To  
Notes
2010-12-22 15:27:08BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-12-08 Cont ID  
Sent By astelly Date 2010-12-08 Time 14:26 Rev Time 0.00
Received By astelly Date 2010-12-08 Time 14:26 Sent To  
Notes
***NONE***